background image

TENTATIVE 

 

19-11-01 

TDK-Lambda 

EZA2500 series 

Quick Manual /Basic

 

 

 

 

 

 

 

 

EZA2500-32048 

Quick Manual 
Basic version 

BEFORE USING THE POWER SUPPLY UNIT (Common) 

Be sure to read this instruction manual thoroughly before using this product. Pay attention to all cautions and 
warnings before using this product. Incorrect usage could lead to an electrical shock, damage to the unit or a fire 
hazard. 
 

DANGER! 

   

 

Never use this product in locations where flammable gas or ignitable substances are present. 

 

INSTALLATION WARNING 

• When installing, ensure that work is done in accordance with the instruction manual. When installation is improper, there is risk 
of electric shock and fire. 
• Installation shall be done by Service personnel with necessary and appropriate technical training and experience. There is a 
risk of electric shock and fire. 
• Do not cover the product with cloth or paper etc. Do not place anything flammable around. This might cause damage, electric 
shock or fire.. 
 

WARNING on USE 

• Do not touch this product or its internal components while circuit in operation, or shortly after shutdown. You may receive a 
burn. 
• While this product is operating, keep your hands and face away from it as you may be injured by an unexpected situation. 
• There are cases where high voltage charge remains inside the product. Therefore, do not touch even if they are not in 
operation as you might get injured due to high voltage and high temperature. You might also get electric shock or burn. 
• Do not make unauthorized changes to this product nor remove the cover as you might get an electric shock or might damage 
the product. We will not be held responsible after the product has been modified, changed or dis-assembled. 
• Do not use this product under unusual condition such as emission of smoke or abnormal smell and sound etc. Please stop 
using it immediately and shut off the product. It might lead to fire and electric shock. In such cases, please contact us. Do not 
attempt repair by you,   as it is dangerous for the user. 
• Do not operate and store these products in environments where condensation occurs due to moisture and humidity. It might 
lead fire and electric shock. 
• Do not drop or apply shock to this product. It might cause failure. Do not operate these products mechanical stress is applied. 
 

CAUTION on MOUNTING 

• Confirm connections to input/output terminals are correct as indicated in the instruction manual before switching on. 
• Input voltage, Output current, Output power, ambient temperature and ambient humidity should be kept within specifications, 
otherwise the product will be damaged, or cause electric shock or fire.  
• Do not use this product in special environment with strong electromagnetic field, corrosive gas or conductive substances and 
direct sunlight, or places where product is exposed to water or rain. 
• Mount this product properly in accordance with the instruction manual, mounting direction and shall be properly be ventilated. 
• Please shut down the input when connecting input and output of the product. 
• The power supply may cause damage when it intake conductive material, dust and liquid. When use this product, please be 
careful to prevent entry of those materials to inside the product by using filter etc. 
• Do not use this product in environments where causes the salt damage. 
 

CAUTION on USE 

• Product individual notes are shown in the instruction manual. If there is any difference with common notes individual notes 
shall have priority. 
• Before using this product, be sure to read the catalog and instruction manual. There is risk of electric shock or damage to the 
product or fire due to improper use. 
• Input voltage, Output current, Output power, ambient temperature and ambient humidity should be kept within specifications, 
otherwise the product will be damaged, or cause electric shock or fire.  

Содержание EZA2500 Series

Страница 1: ...tc Please stop using it immediately and shut off the product It might lead to fire and electric shock In such cases please contact us Do not attempt repair by you as it is dangerous for the user Do no...

Страница 2: ...of usage and perform maintenance Also note that there are cases when EOL products cannot be overhauled Take care not to apply external abnormal voltage to the output Especially applying reverse volta...

Страница 3: ...300 380 VDC AC DC power supply CNVCommCC is distributed by TDK lambda Contents 1 Basic operation of EZA boost step down 2 EZA panel and terminal description 3 What to prepare before using EZA a Create...

Страница 4: ...during the conversion operation There are roughly two ways to switch the direction of power conversion and there are two modes a mode in which it switches over upon receiving an external command signa...

Страница 5: ...ary Switch The rotary switch functions as the RS 485 address setting for this converter It is used to set the lowest digits last 4 bits and DIP SW is used to set the highest digits Light up at Dischar...

Страница 6: ...Serial Interface Connector LAN cable can be used with the same shape as Ether net used on RJ 45 PC LAN However it is not compatible with LAN Ether net Check the pin assignment of RS 485 in the instru...

Страница 7: ...refer to p4 of EZA 2500 communication manual which is separately distributed The following points are listed below Item Specification Note EZA side connector RJ45 It is the same shape as Ether net of...

Страница 8: ...rsonal computer using RS 485 In the figure the inverter is supposed to be capable of bidirectional power conversion from AC to DC from DC to AC called a regenerative function and supplies electric pow...

Страница 9: ...voltage power supply eg GENESYS series of TDK lambda that can output 300 380 VDC instead of DC AC inverter However when the EZA is discharged the constant voltage power supply may be damaged so be sur...

Страница 10: ...RS485 converter driver is installed EZA does not have volume for output adjustment Output voltage current etc are all set by setting parameters via RS485 Install CNVCommCC according to the operation m...

Страница 11: ...ED that is visible through the punching metal on the back panel lights up Confirm that you are connected as shown in p8 or p9 of this manual Launch CNVCommCC exe on your computer The following message...

Страница 12: ...gs and opens the port If opening the port fails an error message is displayed Click the CLOSE button to close the window Check the COM port and the EZA DIP switch settings and start over from step Com...

Страница 13: ...setting panel Please select the EZA address and PC address you want to communicate with Set the address of the EZA you want to communicate with in communication with EZA Turn ON the single target radi...

Страница 14: ...f the sensor for each voltage current power internal temperature of EZA are displayed on the screen When communication with the EZA fails Timeout is displayed in Communication status at the upper righ...

Страница 15: ...on of the menu bar in a state where it can communicate with EZA Calibration is done automatically Calibration information is automatically acquired from EZA Once calibration is performed information i...

Страница 16: ...ng parameters to the area surrounded by the red line in the above figure Target Battery Voltage 50 V Limit of Battery Voltage for Discharging 40 V Turn on the radio buttons of Battery Over Charging Pr...

Страница 17: ...it of Battery of the battery is now set to 1A And when the battery reaches the target voltage the EZA controls the charge current to 0A In the unlikely event that the battery voltage drops below 38V o...

Страница 18: ...driving and Battery CC respectively surrounded by the red line in the above figure Click the Battery CV EZA starts and the fan starts rotating EZA charges the battery with charging current 1 A until i...

Страница 19: ...485 is explained below Click the Main tag in a state where it can communicate with EZA 02 Converter Status Click the READ in Converter Status Charging is displayed in the square under Running State Cl...

Страница 20: ...moved the operation state will not return unless the return signal is input In this case the red LED of ALM on the front panel will light and pin1 of the external signal connector CN will be open To r...

Страница 21: ...ual Basic Click the Main tag in a state where it can communicate with EZA Click the READ in 09 Alarm Operation status is displayed in the square If there are multiple lines you can confirm by clicking...

Страница 22: ...o 0 01 1 the grid target voltage drops by 3 8 V at 7 8A output It should be noted that the input unit in CNVCommCC is CIB Current Limit of Battery A 52 006 0 56 77 Nominal value is 52A DIG Current Lim...

Страница 23: ...02 0 12 Set deviation of volts for warning of discharging lower limit When Battery Volt DLB DDB Warning signal is outputted DDR Deviation of Volts for Cancel Warning of Discharging Lower Limit V 0 0 1...

Страница 24: ...24 TDK Lambda EZA2500 series Quick Manual Basic...