Quick Manual / Basic
①
②
③
④
Charge the 48V battery in Manual CV mode up to 50 V with the charging current 1A.
●Make sure that the power supply, a voltage of 300 V - 380 V and a power of 1A or
more, are connected to the high voltage side of EZA.
●On the main screen, start up as follows.
①
Click on the "Main" tab in a state where it can communicate with EZA.
②
Turn on the radio buttons of "Other driving" and "Battery CC", respectively,
surrounded by the red line in the above figure.
③
Click the “Battery CV”.
※
EZA starts and the fan starts rotating. EZA charges the battery with charging
current 1 A until it reaches 50 V. When the battery voltage reaches 50 V, EZA
controls the charging current to 0 A.
④
By clicking "Stop", the main converter of EZA stops.
⑥
Start EZA and charge the battery.
When EZA 2500 starts, EZA 2500 self-consumes about 100 W at
maximum with main circuit and cooling fan. Here we use 50 V × 1 A =
50 W electric power for battery charging, so connect a power supply of
300 W or more with enough margin.