background image

 

Page 

5

 of 

11

 

 

TDK-Lambda 

DBM20 

 

INSTRUCTION MANUAL

 

PA640-04-01B 

4-3.2  Ready and buffer signals as indicator of the 
operation status of the buffer module. Ready signal will 
change to logic high when the bulk electrolytic capacitors 
charged  up to more than 220Vdc typical after starts up, 
and the green LED lights up. The RED LED will only 
light up during buffering mode and at the same time the 
buffer signal change to logic high. RED LED will be off 
when the bulk electrolytic capacitors discharged to less 
than 50Vdc typical. 

 
Ready and buffer signals with 10mA max. are common 
supply type with voltage range 3.3 - 30V.  
 

Caution on use : 
a)

 

  Kindly take note that both signals may be mistriggered       
during brown out conditions.  

b)

 

In Ready mode, buffer signal may appear if dynamic 
load occurred.  
 

4-3.3  Inhibit signal with 10mA max. is common 
supply type with voltage range 3.3  - 30V.  

 

Inhibit function can be activated by simply pulling the 
inhibit  signal  line  to  logic  low.  The  buffer  unit  will 
immediate  stop  the  existing  charging/buffering 
operation  and start to discharge the energy stored in the 
bulk electrolytic capacitors to the safe level in about 3 ~ 
5 seconds. 

 

Caution on use : 
Please do not touch the buffer module immediately after 
the inhibit function because of high voltage might still 
present across the bulk electrolytic capacitors. 

 

Please refer to figure 6 for general connection diagram 
for signals.  

          

 

For example : 

Common supply 

R1 = R2 

R3 

12V±10% 

1500Ω ±5% 

(1W) 

150Ω ±5% 

(3W) 

 

4-4.   F

ixed Mode and Vin-1 Mode  

Buffer  module  provides  two  option  for  buffer  voltage 
that  is  fixed  mode  and  Vin-1  mode.  Executed  using 
toggle switch to choose between the two options. (refer 
to Figure 1). 
At fixed mode the buffer voltage is set at 22.4V. While 
in Vin-1 mode, the buffer voltage is typically 1V lower 
than  the regulated  output  voltage  of  the  power  supply 
source.  Vin-1  mode  is  suitable  for  adjustable  output 
upstream power supply, this is to keep buffer voltage as 
close as possible to the regulated output voltage of the 
power supply 

4.5. Input Over Voltage Protection ( OVP )  

Input OVP circuit will shut down the boost converter if 
the input to the buffer module is greater than 30V. If the 
input voltage drops back to the normal operating range 
of 23 - 30V, the buffer module will operate as per normal 
again. 

 

4-6. Over Current Protection ( OCP )  

The OCP function is provided for the buffer voltage. When 
the buffering current exceeds 105% of the maximum DC 
buffer  current  specification,  OCP  operation  will  be 
activated.  The  buffering  current  will  be  automatically 
recovered when overload condition is removed.  

4-7. 

Parallel Operation

     

The buffer module can be connected in parallel to increase 
the buffer time. Please refer to wiring diagram shown in 
3-1  (2)  for  parallel  connection.  The  total  output  current 
and charge current must not exceed the maximum output 
current of  the upstream  power  supply.  The  voltage  may 
drop  due  to  the  overcurrent  protection  of  the  upstream 
power supply. 

4-8. Series

 Operation

     

Not possible. 

 

4-9. Buffer

 Module Operation

     

The product can be used to : 

a)

 

To extend the hold  up time after AC loss. 

Buffer Module 

AC

DC

GND

buffer time

 

 

b)

 

To bridge the mains failure 

Buffer Module

AC

DC

GND

buffer time

 

Figure 6 

Содержание DBM20

Страница 1: ...Ne pas utiliser ce produit dans des conditions anormales comme la pr sence de fum es ou d odeurs inhabituelles ou de bruits suspects etc Merci d arr ter l utilisation imm diatement et d teindre le pro...

Страница 2: ...environnement o des particules conductrices de la poussi re ou des liquides peuvent tre pr sents merci d installer des filtres afin de pr venir toute intrusion de corps trangers l int rieur du produi...

Страница 3: ...Earth Terminal RED LED Discharging Indicator LED will be ON during Buffering mode GREEN LED Charged Indicator LED will be ON during Ready mode DC OK Relay Photo Mosfet Logic low when input voltage is...

Страница 4: ...which is out of specification or reversed may damage the unit 4 2 Nominal Buffer Voltage Range 4 2 1 Fixed mode during buffering mode the nominal buffer voltage level 22 4VDC 4 2 2 VIN 1 mode during b...

Страница 5: ...uffer module provides two option for buffer voltage that is fixed mode and Vin 1 mode Executed using toggle switch to choose between the two options refer to Figure 1 At fixed mode the buffer voltage...

Страница 6: ...C input to the power supply the output from the power supply which is connected to the input output of the buffer module will charge up the internal circuit of the buffer module 2 Once the input outpu...

Страница 7: ...ffering take place buffer signal will change from logic low to high And Ready signal will change from logic high to low 6 During the upstream power supply is still turn ON case and customer system wil...

Страница 8: ...limit of withstand voltage test equipment at 100mA The applied voltage must be gradually increased from zero to testing value and then gradually decreased for shut down When timer is used the buffer m...

Страница 9: ...ng Please refer to section 6 Leave enough space surround the units to ventilate heat efficiently Minimum Installation clearances 40mm on top 20mm at the bottom A 5mm which is recommended on the left a...

Страница 10: ...citor varies depending on the method of mounting the buffer module the load current and the ambient temperature Please refer to the Electronic Capacitor Lifetime Please do not use the product which pa...

Страница 11: ...Ltd Sales Services and R D 1008 Toa Payoh North 06 01 08 07 01 03 Singapore 318996 Telephone 65 62517211 Facsimile 65 62509171 WEBSITE www tdk lambda com sg Note Name plate s contents shown in this in...

Отзывы: