66
・All specifications are subject to change without notice.
Instruction Manual
HWS
HWS HD
HWS ME
HWS-P
ITEMS/UNITS
MODEL
HWS1500-24/ME
HWS1500-36/ME
HWS1500-48/ME
Input
Voltage Range
(*2)
V
AC85 - 265
Frequency
(*2)
Hz
47 - 63
Power Factor (100/230VAC)(typ) (*1)
0.98 / 0.94
Efficiency (100/200VAC)(typ)
(*1)
%
84 / 88
86 / 90
Current (100/200VAC)(typ)
(*1)
A
19.0 / 10.0
Inrush Current (100/200VAC)(typ) (*3)
A
20 / 40
Leakage Current
(*10) mA
Less than 0.5. (0.2 (typ) at 100VAC / 0.4 (typ) at 230VAC)
Output
Nominal Voltage
VDC
24
36
48
Maximum Current (100/200VAC)
A
65 / 70
42 / 46.5
32 / 32
Maximum Peak Current
(*13)
A
105
70
-
Maximum Power (100/200VAC)
W
1560 / 1680
1512 / 1674
1536 / 1536
Maximum Peak Power
(*13)
W
2520
-
Maximum Line Regulation
(*5) mV
96
144
192
Maximum Load Regulation
(*6) mV
144
150
288
Temperature Coefficient
Less than 0.02%/
℃
Maximum
Ripple & Noise (*4)
0 to +70
℃
mVp-p
200
-10 to 0
℃
mVp-p
240
400
Hold-up Time (typ)
(*9)
ms
20
Voltage Adjustable Range
VDC
19.2 - 28.8
28.8 - 43.2
38.4 - 52.8
Function
Over Current Protection
(*7)
A
>110.2
>73.5
>33.6
Over Voltage Protection
(*8) VDC
30.0 - 34.8
45.0-49.7
55.2 - 64.8
Remote Sensing
Possible
Remote ON/OFF Control
Possible
Parallel Operation
Possible
Series Operation
Possible
Monitoring Signal
PF (Open collector output)
Line DIP
Built to meet SEMI-F47 (200VAC Line only)
Environment
Operating Temperature
(*11)
℃
-10 to +70 ( -10 to +50: 100%, +60: 75%, +70: 50%), start up -20 to 70
Storage Temperature
℃
-30 to +85
Operating Humidity
%RH
10 - 90 (No Condensing)
Storage Humidity
%RH
10 - 95 (No Condensing)
Vibration
At no operating, 10 - 55Hz (sweep for 1min.) 19.6m/s² constant, X, Y, Z 1hour each.
Shock (In package)
Less than 196.1m/s²
Cooling
Forced air by blower fan
Isolation
Withstand Voltage
Input - FG : 2kVAC (20mA), Input - Output : 3kVAC (20mA)
Output-FG : 500VAC (300mA), Output-CNT:100VAC (100mA) for 1min.
Isolation Resistance
More than 100M
Ω
Output - FG : 500VDC
More than 10M
Ω
Output - CNT : 100VDC at 25
℃
and 70%RH
Standards
Safety Standards
(*12)
Approved by
UL60601-1, EN60601-1, CSA C22.2 No.601.1-M90 (C-UL)
PFHC
Built to meet IEC61000-3-2
Voltage Fluctuations / Flicker Emissions
Built to meet IEC61000-3-3
EMI
Approved by EN55011 / EN55022-A, FCC-Class A, VCCI-Class A
Immunity
Built to meet IEC61000-4-2(Level 2,3), -3(Level 3), -4(Level 3),
-5(Level 3,4), -6(Level 3), -8(Level 4), -11
Mechanical
Weight (typ)
g
3800
Size (W x H x D)
mm
126.5 x 82 x 280 (Refer to outline drawing)
(*1) At Ta=25
℃
and maximum output power.
(*2) For cases where conformance to various safety specs (UL, CSA, EN) are required, input voltage range will be 100 - 240VAC (50/60Hz).
(*3) First in-rush current. Not applicable to the first 0.2ms in-rush current flowing into the power supply noise filter.
(*4) Measure with JEITA RC-9131A probe, Bandwidth of scope :100MHz. (at 100uF electric capacitor and 0.47uF film capacitor on the test fixture board.)
(*5) 85 - 265VAC, constant load.
(*6) No load-Full load, constant input voltage.
(*7) Constant current limit with automatic recovery. Over current condition for more than 5 seconds will cause the
output to shutdown.
Output current exceeding maximum rated output current for more than 10 seconds continuously
will result to output shutdown.
(*8) OVP circuit will shut down output, manual reset (Power cycle) or ON/OFF CNT signal reset.
(*9) At 100/200VAC, nominal output voltage and maximum output current.
(*10) Measured by the each measuring method of UL, EN and CSA (at 60Hz).
When using it as a patient care equipment, all outer surfaces of the equipment shall be
constructed of nonconductive material. See clause 19.5DV.2 of UL60601-1.
(*11) Ratings - Derating at standard mounting.
- Load (%) is percent of maximum output power or maximum output current, whichever is greater.
- As for other mountings, refer to derating curve.
(*12) As for UL60601-1, EN60601-1 and CSA-C22.2 No.601.1-M90 (C-UL) basic insulation.
(*13) Peak output current is less than 10 seconds, and duty 35% max. (200VAC Line only)
Please refer to "TDK-Lambda
EMC Filters" catalog.
●Recommended EMC Filter
RSEN-2030L
HWS
1500/ME
HWS1500/ME Specifications
(Read instruction manual carefully, before using the power supply unit.)