Instruction Manual
HWS
HWS HD
HWS ME
HWS-P
ITEMS/UNITS
MODEL HWS1500
-3
HWS1500
-5
HWS1500
-6
HWS1500
-7
HWS1500
-12
HWS1500
-15
HWS1500
-24
HWS1500
-36
HWS1500
-48
HWS1500
-60
Input
Voltage Range
(*2)
V
AC85 - 265 or DC120 - 330
Frequency
(*2)
Hz
47 - 63
Power Factor (100/230VAC)(typ) (*1)
0.98 / 0.94
Efficiency (100/200VAC)(typ)
(*1)
%
72 / 75
77 / 81
79 / 82
81 / 83
82 / 85
83 / 87
84 / 88
86 / 90
Current (100/200VAC)(typ)
(*1)
A
15.0 / 8.0
19.5 / 10.0
19.0 / 10.0
Inrush Current (100/200VAC)(typ) (*3)
A
20 / 40
Leakage Current (100/240VAC) (*10) mA
1.5 max
Output
Nominal Voltage
VDC
3.3
5
6
7.5
12
15
24
36
48
60
Maximum Current (100/200VAC)
A
300 / 300
250 / 250 200 / 200 125 / 125 100 / 100
65 / 70
42 / 46.5
32 / 32
25.6 / 28
Maximum Peak Current
(*13)
A
−
300
240
−
105
70
−
42
Maximum Power (100/200VAC)
W
990 / 990
1500 / 1500
1560 / 1680 1512 / 1674 1536 / 1536 1536 / 1680
Maximum Peak Power
(*13)
W
−
1800
−
2520
−
2520
Maximum Line Regulation
(*5) mV
36
40
48
60
96
144
192
240
Maximum Load Regulation
(*6) mV
60
72
90
144
150
288
360
Temperature Coefficient
Less than 0.02%/
℃
Maximum
Ripple & Noise
(*4)
+25 to +70
℃
mVp-p
150
200
400
0
℃
mVp-p
200
150
200
400
-10
℃
mVp-p
220
200
240
400
600
Hold-up Time (typ)
(*9)
ms
20
16
20
Voltage Adjustable Range
VDC 2.64 - 3.96 4.0 - 6.0
4.8 - 7.2
6.0 - 9.0
9.6 - 14.4
12.0 - 18.0 19.2 - 28.8 28.8 - 43.2 38.4 - 52.8 48.0 - 66.0
Function
Over Current Protection
(*7)
A
>315.0
>262.5
>210.0
>131.2
>105.0
>68.2
>44.1
>33.6
>26.8
Over Voltage Protection
(*8) VDC 4.12 - 4.62
6.25 - 7.0
7.5 - 8.4
9.37 - 10.5
15.0 - 17.4
18.7 - 21.8 30.0 - 34.8 45.0 - 49.7 55.2 - 64.8 69.0 - 75.0
Remote Sensing
Possible
Remote ON/OFF Control
Possible
Parallel Operation
Possible
Series Operation
Possible
Monitoring Signal
PF (Open collector output)
Line DIP
Built to meet SEMI-F47 (200VAC Line only)
Environment
Operating Temperature
(*11)
℃
-10 to +70, start up -20 to +70
at Input Voltage
100VAC/200VAC
-10 to +40°C
W
990
1500
1560 / 1680 1512 / 1674
1536
1536 / 1680
+50°C
W
825
1250
1500
1560 / 1680 1512 / 1674
1536
1536 / 1680
+60°C
W
660
1000
1125
1170 / 1260 1134 / 1255
1152
1152 / 1260
+70°C
W
495
750
780 / 840
756 / 837
768
768 / 840
Storage Temperature
℃
-30 to +85
Operating Humidity
%
RH
10 - 90 (No Condensing)
Storage Humidity
%
RH
10 - 95 (No Condensing)
Vibration
At no operating, 10 - 55Hz (sweep for 1min.) 19.6m/s² constant, X, Y, Z 1hour each.
Shock (In package)
Less than 196.1m/s²
Cooling
Forced air by blower fan
Isolation
Withstand Voltage
Input - FG : 2kVAC (20mA), Input - Output : 3kVAC (20mA), Output - CNT : 100VAC (100mA)
Output - FG : 500VAC (300mA), (60V model 651VAC (390mA) ) for 1min.
Isolation Resistance
More than 100M
Ω
Output - FG : 500VDC More than 10M
Ω
Output - CNT 100VDC at 25
℃
and 70%RH
Standards
Safety Standards
(*12)
Approved by UL60950-1, CSA C22.2 No.60950-1, EN60950-1, EN50178. Built to meet DENAN.
PFHC
Built to meet IEC61000-3-2
EMI
Built to meet EN55011/EN55022-A, FCC-ClassA, VCCI-ClassA.
Immunity
Built to meet IEC61000-4-2(Level 2,3), -3(Level 3), -4(Level 3), -5(Level 3,4), -6(Level 3), -8(Level 4), -11
Mechanical
Weight (typ)
g
4000
3800
Size (W x H x D)
mm
126.5 x 82 x 280 (Refer to outline drawing)
(*1) At Ta=25
℃
and maximum output power.
(*2) For cases where conformance to various safety specs (UL, CSA, EN) are required, input voltage range will be 100 - 240VAC (50/60Hz).
(*3) First in-rush current. Not applicable to the first 0.2ms in-rush current flowing into the power supply noise filter.
(*4) Measure with JEITA RC-9131A probe, bandwidth of scope: 100MHz.
(at 100uF electric capacitor and 0.47uF film capacitor on the test fixture board.)
Ripple noise spec for ambient temperature between -10 to 25 is a linearity value with respect to the -10 degrees
C and 25 degrees C specs.
(*5) 85 - 265VAC, constant load.
(*6) No load-Full load, constant input voltage.
(*7) Constant current limit with automatic recovery. Over current condition for more than 5 seconds will cause the out-
put to shutdown. Output current exceeding maximum rated output current for more then 10 seconds continuously
will result to output shutdown.
(*8) OVP circuit will shut down output, manual reset (power cycle) or ON/OFF CNT signal reset.
(*9) At 100/200VAC, nominal output voltage and maximum output current.
(*10) Measured by the each measuring method of UL, CSA, EN and DENAN (at 60Hz), Ta=25
℃
.
(*11) Ratings - Derating at standard mounting.
- Load (%) is percent of maximum output power or maximum output current, whichever is greater.
- As for other mountings, refer to derating curve.
(*12) As for DENAN, built to meet at 100VAC.
(*13) Peak output current is less than 10 seconds, and duty 35% max. (200VAC Line only)
Please refer to "TDK-Lambda
EMC Filters" catalog.
●Recommended EMC Filter
RSEN-2030
HWS
1500
HWS1500 Specifications
(Read instruction manual carefully, before using the power supply unit.)