Ask us for replacement of the fan. This will be a charged service. If you are replacing the fan by yourself, note the following.
*1. Be careful in handling the fan unit so as not to cause an impact by dropping it or hitting it, etc.
*2. Shut down the input before starting the replacement operation.
*3. Check that there are no loose parts in connectors or harness tucking, etc.
*4. Safety standards (UL, CE, etc.) are not applicable.
Name of fan unit for replacement Applicable models
Appearance
Pin assignments
Price
1500-FAN-01
HWS1000
HWS1500
HWS1800T
(of standard
specifications)
Wind direction
Open
Housing = XHP-3(J.S.T.)
Contact = SXH-001T-P0.6(J.S.T.)
Length of fan harness = 65 ± 10mm
Pin No.
Description
1
Power supply
2
Fan alarm
3
GND
8. Option
We have prepared an optional fan unit for replacement.
Fan unit for replacement
7. Warranty
This product is warranted for a period of 5 years from the
date of shipment. As for the breakdown under a normal
use during free warrantee term, repair is at free of charge.
However, the Built-in Fan Motor replacement is for a fee.
Please contact your nearest sales offi ce for replacement.
The Fan-life has limitation. Therefore, periodic maintenance
by replacing the life-expired fan is required.
The following fi gure shows the life of fan.
Conditions of usage at the free of charge warrantee are as
follows.
⑴ Average operating temperature (ambient temperature of the
power supply unit) is 40℃
⑵ Average load factor is 80% or less
⑶ Installation method: Standard installation. However, the
maximum rating is within the output derating.
Following cases are not covered by warranty.
⑴ Improper usage like dropping products, applying shock and
defects from operation exceeding specifi cation of the units.
⑵ Defects resulting from natural disaster (fi re, fl ood).
⑶ Unauthorized modifi cations or repair by the buyers.
⑷ Defects not cause by
TDK-Lambda.
Air flow
Measuring point of fan exhaust temperature
Measuring point
50mm
P.S.
10
7
5
3
2
1
0
50
60
70
80
40
100
Life expectancy(years)
Fan exhaust temperature(℃)
Life expectancy
Fan exhaust temperature 45℃ 45,000 hour
Fan exhaust temperature 80℃ 11,000 hour
Insulation tube for HWS1500
The following insulation tube can becuse for output terminal.
・TCV-2001 (shinagawa shoko)
Please confi rm shape and size from manufacturer catalog.
Example of use for insulation tube