Configuration
4
Room Temperature and Setpoints
The room temperature is rounded to the nearest whole number. The active heat and cool setpoints will appear in place
of the room temperature when using the up/down arrows to adjust the temperature value or when touching the Room
Temperature display. The up/down arrows will change color to indicate the current setpoints are being overridden
(blue for cooler, orange for warmer). The arrows change the heat and cool setpoints (User Setpoint Adjust) together
incrementally, to a deafault value of +/– 5°F from the programmed setpoint.
Setpoint Override Indication: Warmer
Setpoint Override Indication: Cooler
DI Setpoint Setback Active Indicator
The Digital Input (DI) Setpoint Setback feature allows the user to adjust the effective heat and cool setpoint values based
on the state of a DI. This allows the controller to increase the cooling setpoint and decrease the heating setpoint by a
predetermined amount and effectively create a setback response to an energy demand. The
indicator becomes
visible then the DI Setpoint Setback feature is active. Touch the symbol to bring up a brief explanation of the feature.
Information Text
The two line text field displays outside air when a remote temperature sensor is connected to the UbiquiSTAT. It can also
be configured to display other system information.
Settings Screens
NOTE:
Several of the settings described here were assigned during the initial setup of the UbiquiSTAT via the Startup
Wizard
(refer to the
). Follow these instructions if you need to change those settings.
Access to this menu can be controlled by the use of an access code, which can be assigned via the Startup Wizard (refer
to the
) or via the Advanced section.
Touching the SETTINGS button at the bottom of the HOME screen brings up the Settings section, from which you can
configure all settings.
Settings Screen