4

occupied deadband Screen. 

Enter 

an occupied deadband. This is +/- the 

setpoint where no control is done, during 

the occupied time period. This is a num-

ber from 0 to 100% of input span.

unoccupied deadband Screen. 

Enter 

an unoccupied deadband. This is +/- the 

setpoint where no control is done, dur-

ing the unoccupied time period. This is a 

number from 0 to 100% of input span.

AI2 Control Mode Screen. 

Choose 

the control mode for AI2. Select from 

Remote Setpoint, Reset or Monitor. 

Select Monitor if AI2 is not used. Note: 

Must be MONITOR if dew point control 

is selected.

Setpoint Low Limit Value Screen. 

Enter a setpoint low limit value. The set-

point will not be allowed to be set lower 

than this setting.

Setpoint high Limit Value Screen. 

Enter a setpoint high limit value. The set-

point will not be allowed to be set higher 

than this setting.

Setpoint Screen. 

Enter a setpoint value 

for control. (This screen does not appear 

if the AI2 Control Mode is chosen to be 

Remote Setpoint.) 

Reset Setpoint Screen. 

Enter a setpoint 

value for AI2. (This screen only appears 

if the AI2 Control Mode is chosen to be 

Reset.)

Reset Ratio Factor Screen. 

Enter a 

reset ratio factor. This is the number 

of units +/- (%RH, °F, etc.) that the AI1 

Setpoint is raised when the AI2 input 

falls 1 unit below its setpoint. (This 

screen only appears if the AI2 Control 

Mode is chosen to be Reset.)

Analog output Range Screen. 

Choose 

whether the analog output range will be 

0-20mA or 4-20mA. 

 

 

 

Analog output Action Screen. 

Choose 

whether the analog output will be direct 

or reverse acting. (When DI2 is set to 

Aquastat, the output will automatically 

reverse action when DI2 is closed.) 

AI2 USED FOR:

MONITOR

16.

SETPOINT LOW

LIMIT: 

0

17.

SETPOINT HIGH

LIMIT: 

100

18.

PRIMARY 

SETPOINT: 

75

19.

RESET

SETPOINT: 

75

20.

RESET RATIO

FACTOR: 

1.0

21.

MOD OUT

RANGE: 

4-20MA

22.

MOD OUT

ACTION: 

DIRECT

23.

MOD OUT TYPE:

MIDPOINT

24.

MOD OUT UNOCC

ACTION: 

MOD

25.

Analog output Type Screen. 

Select 

whether the analog output will be 

modulated from an endpoint or the mid-

point. Note: Set to MIDPOINT if dew 

point control is selected.

Analog output unoccupied Action 

Screen. 

Select whether during unnoc-

cupied mode the analog output will 

modulate go to 0 to 4 mA, or go to 20 

mA.

Analog output Mode Screen. 

Choose 

whether the analog output mode will be 

Heat or Cool. With heat mode, modula-

tion occurs when the input is below the 

setpoint. With cool mode, modulation 

occurs when the input is above the 

setpoint. (This screen only appears if 

the Analog Output Type is chosen to be 

Endpoint.) 

Analog output Setpoint offset 

Screen. 

Enter a setpoint offset. This is 

a value below the setpoint (Heat Mode) 

or above the setpoint (Cool Mode) 

where the analog output begins to 

modulate. (This screen only appears if 

the Analog Output Type is chosen to be 

Endpoint.) 

Analog output unoccupied Action 

Screen. 

Choose whether the unoccu-

pied analog output will be Modulating, 

0mA or 4mA, or 20mA.

Analog output Proportional Band 

Screen. 

Enter a proportional band. 

This is in percent of input span.  It is 

how much AI1 must change to have the 

analog output change from 0 or 4 mA 

to 20mA. 

Analog output Integral Value Screen. 

Enter a integral value. This a number 

between 0 and 100%. Choose 0 if inte-

gral is not used.  

 

 

 

Analog output differential Value 

Screen. 

Enter a derivative value. This a 

number between 0 and 100%. Choose 

0 if derivative is not used. 

 

 

 
digital output 1 Mode Screen. 

Choose whether the mode for digital 

output one will be Heat or Cool. With 

heat mode, relay energizes when the 

input is below the setpoint. With cool 

mode, relay energizes when the input is 

above the setpoint.

digital output 2 Mode Screen. 

Choose whether the mode for digital 

output two will be Heat or Cool. With 

heat mode, relay energizes when the 

input is below the setpoint. With cool 

mode, relay energizes when the input is 

above the setpoint.

MOD OUT SETPOINT

OFFSET: 

0%

27.

MOD OUT UNOCC

ACTION: 

MOD

28.

AO PROPORTIONAL

BAND: 

1

29.

AO INTEGRAL

FACTOR: 

15

30.

AO DIFFERENTIAL

FACTOR: 

2

31.

STAGE OUTPUT 1

AS: 

HEAT

32.

STAGE OUTPUT 2

AS: 

COOL

33.

OCCUPIED 

DEADBAND: 

1%

14.

UNOCCUPIED 

DEADBAND: 

5%

15.

MOD OUT

IS: 

HEAT

26.

Содержание SZ1143b

Страница 1: ...a broad variety of transducers Two digital inputs for switches alarms clocks etc One 4 20 mA modulating output Two relay outputs Adjustable P I D control on modulating output Adjustable offsets and d...

Страница 2: ...r sensing Powering the SZ1143b The SZ1143b is powered from 24 VAC 20 Caution Do not connect to 120 VAC When multiple TCS Basys Controls devices are using a single transformer the polarity of the power...

Страница 3: ...the analog output range will be 0 20mA or 4 20mA This screen is the last screen if High Low control mode is enabled and is the same as step 22 when not enabled Enable Dew Point Control Select yes to e...

Страница 4: ...t Type Screen Select whether the analog output will be modulated from an endpoint or the mid point Note Set to MIDPOINT if dew point control is selected Analog Output Unoccupied Action Screen Select w...

Страница 5: ...e IN1 or IN2 terminal of the first SZ1143b Remove the RTN1 or RTN2 jumper from the second SZ1143b Refer to Sharing analog inputs on an SZ1143b Application note for more detail HIGH LOW CONTROL The ana...

Страница 6: ...gramming screens 22 through 31 AI2 MODE PARAMETERS Analog input two can be selected as either Monitor Remote Setpoint or Reset If monitor is chosen the analog output and digital out puts are controlle...

Страница 7: ...point In most cases the first stage is set to zero The differential value is the differ ence between the on and off points Setpoint O N O N O N O N O FF O FF O FF O FF Differential Differential O ffse...

Страница 8: ...res off will instantly turn all outputs off and reset the controller Analog Output Not Working Properly Check wiring A separate transformer should be used for the SZ1143b and a separate transformer sh...

Страница 9: ...ed Setpoint and Analog Output Screen Shows the current setpoint used for control and the output value for the analog output The analog output is dis played as a percentage 0 100 Analog Output Screen S...

Отзывы: