background image

2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

6

Simplty wire 2 4-20mA devices into IN1 and IN2, in pro-

gramming step #4 select "YES", step # 5 select whether 

you would like to pass the "LOW" or the "HIGH" of the 

2 4-20mA signal that are wired. Either the highest or to 

lowest shall be passed directly to the AO1. Step # 6 in 

the programming screens allows yo to rescale the IN's 

for 4-20mA to 0-20mA be selecting "0-20mA". See con-

version chart below.

dEW PoINT CoNTRoL

The analog output and digital outputs on the SZ1143b 

can be setup to use a calculated dew point temperature 

as the actual input. This is done by selecting "YES" in 

programming step # 7. When using dew point control, 

AI1 is the temperature input (automatically scaled for 0 

to 100 °F) and AI2 is the relative humidity input (auto-

matically scaled for 0 to 100 %RH). In programming 

screen #19, you are asked to enter a primary setpoint 

which is the dew point setpoint. This setpoint will typical-

ly be the  temperature of the area where condensation 

is a potential problem , (i.e. cooler temperature, freezer 

temperature, supply air temperature). The analog and 

digital outputs behave as they normally would but use 

the calculated dew point, the primary setpoint, and their 

programmed parameters (heat/cool, proportional band 

offsets, differentials, etc.). 
Example: Door Heater Control in a Convenience Store. 

The temperature inside the store is 76°F with 49% rela-

tive humidity. The coolers are kept at 37°F (entered as 

the setpoint in programming screen #19).

The calculated dew point comes out to be 55°F, so:
DO1 will be OPEN (if factory defaults are used and 

stage 1 is set to HEAT).

DO2 will be CLOSED (if factory defaults are used and 

stage 2 is set to COOL).

AO1 will modulate based on the setpoint of 37°F, an 

input of 55°F, the deadband
(programming screens #14 and #15), and the settings 

chosen in programming screens #22 through #31.

AI2 ModE / PARAMETERS

Analog input two can be selected as either "Monitor", 

"Remote Setpoint" or "Reset".
If monitor is chosen, the analog output and digital out-

puts are controlled based on a comparison between the 

scaled AI1 value and the setpoint entered in program-

ming step #19.
If remote setpoint is chosen, the analog output and 

digital outputs are controlled based on a comparison 

between the scaled AI1 value, and the "setpoint" or 

"scaled AI2 value".
If reset is chosen, the analog output and digital outputs 

are controlled based on a comparison between AI1 and 

a calculated setpoint derived from the scaled AI2 value, 

the reset setpoint entered in programming step #17 and 

the reset factor entered in programming step #18.

RESET

The analog output and digital outputs on the SZ1143b 

can be setup to use a reset function. This is done by 

selecting "Reset" in programming step # 16. When 

using the reset function, AI1 is the "Primary" input and 

AI2 is the "Reset" input.
In programming screen #19, you are asked to enter a 

primary setpoint. This setpoint will be adjusted up and 

down based on the AI2 value, the reset setpoint and the 

reset factor. AI1 will be controlled to this calculated set-

point by modulating the device connected to the analog 

output.
In programming screen #20, you are asked to enter a 

reset setpoint. A comparison between AI2 and this set-

ting will be used in determining the calculated setpoint 

for AI1.
In programming screen #21, you are asked to enter a 

reset ratio factor. This is the number of units that the 

AI1 setpoint is raised when the AI2 value falls below the 

reset setpoint by 1 unit, or the number of units that the 

AI1 setpoint is lowered when the AI2 value rises above 

the reset setpoint by 1 unit.
Example:  A hot water valve is controlled using an out-

4-20mA

0-20mA

4-20mA

0-20mA

4-20mA

0-20mA

4-20mA

0-20mA

4-20mA

0-20mA

4.00

0.00

8.00

5.00

12.00

10.00

16.00

15.00

20.00

20.00

5.00

1.25

9.00

6.25

13.00

11.25

17.00

16.25

6.00

2.50

10.00

7.50

14.00

12.50

18.00

17.50

7.00

3.75

11.00

8.75

15.00

13.75

19.00

18.75

Содержание SZ1143b

Страница 1: ...a broad variety of transducers Two digital inputs for switches alarms clocks etc One 4 20 mA modulating output Two relay outputs Adjustable P I D control on modulating output Adjustable offsets and d...

Страница 2: ...r sensing Powering the SZ1143b The SZ1143b is powered from 24 VAC 20 Caution Do not connect to 120 VAC When multiple TCS Basys Controls devices are using a single transformer the polarity of the power...

Страница 3: ...the analog output range will be 0 20mA or 4 20mA This screen is the last screen if High Low control mode is enabled and is the same as step 22 when not enabled Enable Dew Point Control Select yes to e...

Страница 4: ...t Type Screen Select whether the analog output will be modulated from an endpoint or the mid point Note Set to MIDPOINT if dew point control is selected Analog Output Unoccupied Action Screen Select w...

Страница 5: ...e IN1 or IN2 terminal of the first SZ1143b Remove the RTN1 or RTN2 jumper from the second SZ1143b Refer to Sharing analog inputs on an SZ1143b Application note for more detail HIGH LOW CONTROL The ana...

Страница 6: ...gramming screens 22 through 31 AI2 MODE PARAMETERS Analog input two can be selected as either Monitor Remote Setpoint or Reset If monitor is chosen the analog output and digital out puts are controlle...

Страница 7: ...point In most cases the first stage is set to zero The differential value is the differ ence between the on and off points Setpoint O N O N O N O N O FF O FF O FF O FF Differential Differential O ffse...

Страница 8: ...res off will instantly turn all outputs off and reset the controller Analog Output Not Working Properly Check wiring A separate transformer should be used for the SZ1143b and a separate transformer sh...

Страница 9: ...ed Setpoint and Analog Output Screen Shows the current setpoint used for control and the output value for the analog output The analog output is dis played as a percentage 0 100 Analog Output Screen S...

Отзывы: