uNoCCuPIEd SETBACK

The SZ1143b operates in either an occupied or unoc-

cupied mode. During the occupied mode, the occupied 

deadband will be used. During the unoccupied mode, 

the unoccupied deadband will be used.
Digital Input 1 is used to set the occupied and unoccu-

pied mode of the SZ1143b. If the connection from "DI1" 

to "COM" (ground) is "Open", the SZ1143b functions in 

Occupied Mode. If the connection from "DI1" to "COM" 

(ground) is "Closed", or "Shorted", the SZ1143b func-

tions in Unoccupied Mode.

ANALog INPuT

The SZ1143b's 4 to 20mA inputs utilize differntial input 

circuits. The +P terminal is a DC power supply for 2-wire 

(loop powered) 4 to 20mA inputs. To connect a  2-wire  

4 to 20mA transmitter (temperature, pressure, humidity) 

to the SZ1143b, connect the +P terminal of the SZ1143b 

to the (+) terminal of the transmitter and connect the IN1 

(or IN2) terminal of the SZ1143b to the (-) terminal of the 

transmitter. Leave the respective RTN1 or RTN2 jumper 

installed. This jumper connects terminal RTN1 or RTN2 

to the GND or C terminal and completes the circuit.
If connecting a self powered 4 to 20mA signal to the 

SZ1143b, connect the (+) signal to the IN1 (or IN2) ter-

minal of the SZ1143b and the (-) signal or return to the 

RTN1 (or RTN2) terminal of the SZ1143b. Remove the 

respective RTN1 or RTN2 jumper.
If sending one signal to two SZ1143b units, for example 

outdoor air temperature, Connect the +P terminal one 

of the SZ1143b’s to the (+) terminal of the transmitter. 

Connect the (-) terminal of the transmitter to the IN1 

(or IN2) terminal of the second SZ1143b. Connect the 

RTN1 (or RTN2) terminal of the second SZ1143b to 

the IN1 (or IN2) terminal of the first SZ1143b. Remove 

the RTN1 (or RTN2) jumper from the second SZ1143b. 

Refer to “Sharing analog inputs on an SZ1143b” 

Application note for more detail.

hIgh / LoW CoNTRoL

The analog input and analog outputs can be setup to 

perform High/Low signal selection. This is done by 

selecting "YES" in programming step # 4. When using 

the SZ1143b as a High/Low signal selector no other 

modes of operation work. 

STAGE 1

OFFSET: 

0%

34.

STAGE 1

DIFF: 

2%

35.

STAGE 2

OFFSET: 

2%

36.

STAGE 2

DIFF: 

2%

37.

DI2 USED FOR:

MONITOR

38.

DO2 SETPOINT

USED:     SETPOINT 1

39.

DO2 PRIMARY

SETPOINT2: 

75

40.

DO2 UNOCCUPIED

DEADBAND2: 

5%

41.

SET ACCCESS

CODE: 

248

42.

AI1 

0

AI2 

 

0

digital output 1 offset Screen. 

Enter 

an offset value for digital output one. A 

first stage is normally set to 0 offset. The 

offset is a percentage of input span.

digitaI output 1 differential Screen. 

Enter a differential value for digital output 

one. The differential is a percentage of 

input span. 

 

 

 

 

 

 

digital output 2 offset Screen. 

Enter 

an offset value for digital output two. The 

offset is a percentage of input span.
 

 

 

 

digital output 2 differential Screen. 

Enter a differential value for digital output 

one. The differential is a percentage of 

input span.

digitaI Input 2 Mode Screen. 

Choose 

DI2 as Monitor or Aquastat. Aquastat 

reverses the action of the analog output.

 

 

 

do2 Setpoint Mode Screen. 

Choose 

whether DO2 will be controlled by 

the "Main" Setpoint1 or from its own 

Setpoint2.
 

 

 

 

do2 Setpoint Screen. 

Enter a setpoint 

value for control. (This screen only 

appears if the DO2 Setpoint Mode is 

chosen to be Setpoint2.)

unoccupied deadband Screen. 

Enter 

an unoccupied deadband for DO2. This 

is a number from 0 to 100% of input 

span. (This screen only appears if the 

DO2 Setpoint Mode is chosen to be 

Setpoint2.)

Access Code Screen. 

Enter an access 

(0-255) code that will be used to enter 

the programming mode. The default is 

248.

Main Monitoring Screen.

Содержание SZ1143b

Страница 1: ...a broad variety of transducers Two digital inputs for switches alarms clocks etc One 4 20 mA modulating output Two relay outputs Adjustable P I D control on modulating output Adjustable offsets and d...

Страница 2: ...r sensing Powering the SZ1143b The SZ1143b is powered from 24 VAC 20 Caution Do not connect to 120 VAC When multiple TCS Basys Controls devices are using a single transformer the polarity of the power...

Страница 3: ...the analog output range will be 0 20mA or 4 20mA This screen is the last screen if High Low control mode is enabled and is the same as step 22 when not enabled Enable Dew Point Control Select yes to e...

Страница 4: ...t Type Screen Select whether the analog output will be modulated from an endpoint or the mid point Note Set to MIDPOINT if dew point control is selected Analog Output Unoccupied Action Screen Select w...

Страница 5: ...e IN1 or IN2 terminal of the first SZ1143b Remove the RTN1 or RTN2 jumper from the second SZ1143b Refer to Sharing analog inputs on an SZ1143b Application note for more detail HIGH LOW CONTROL The ana...

Страница 6: ...gramming screens 22 through 31 AI2 MODE PARAMETERS Analog input two can be selected as either Monitor Remote Setpoint or Reset If monitor is chosen the analog output and digital out puts are controlle...

Страница 7: ...point In most cases the first stage is set to zero The differential value is the differ ence between the on and off points Setpoint O N O N O N O N O FF O FF O FF O FF Differential Differential O ffse...

Страница 8: ...res off will instantly turn all outputs off and reset the controller Analog Output Not Working Properly Check wiring A separate transformer should be used for the SZ1143b and a separate transformer sh...

Страница 9: ...ed Setpoint and Analog Output Screen Shows the current setpoint used for control and the output value for the analog output The analog output is dis played as a percentage 0 100 Analog Output Screen S...