Check the Monitoring Screens. The “AO” Screen will tell 

you what the SZ1143b is trying to put out for an output. 

Compare this with the actual position of the modulating 

device.

MoNIToRINg SCREENS

Continually pressing the scroll button allows more exten-

sive monitoring. The screens are shown below. 

* (This screen does not appear if High/Low control mode is enabled)

AI1 

AI2 

0

1.

Rev:0809

C3569_REV3

2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

9

Power up Screen.

Main Monitoring Screen. 

Shows the 

scaled value for analog input one and 

analog input two.*

Main Monitoring Screen. 

Shows the 

actual value for analog input one and 

two.(This screen only appears if High/

Low control mode is enabled)

Setpoint and Analog output Screen. 

Shows the current setpoint used for 

control and the output value for the 

analog output. The analog output is dis-

played as a percentage (0 - 100%).*

Analog output Screen. 

Shows the 

actual analog output. (This screen only 

appears if High/Low control mode is 

enabled)

Relay one and Relay Two Status 

Screen. 

Shows the status of digital 

output one and two as either being On 

(Energized) or Off (De-energized).*

 

 

 

 

dI1 and dI2 Status Screen. 

Shows the 

status of digital input one and two as 

either being On (Closed) or Off (Open). 

Digital input One is a time clock input.  

Off is occupied and On is unoccupied.*

 

* SZ1143b *    

TCS V2.2 (c)

SET  POINT                  50

MOD  OUT                  5%

2.

DO1 

OFF

DO2 

OFF

3.

DI1 

OFF

DI2 

OFF

4.

AI1 

4.0mA

AI2 

4.0mA

1a.

AO                4.0mA

2a.

LED Description                      

PRogRAM/dATA

The Program/Data LED will be lit when the controller is with-

in the programming or clock setup menus. It will blink when 

the unit is being accessed by a PC.

Содержание SZ1143b

Страница 1: ...a broad variety of transducers Two digital inputs for switches alarms clocks etc One 4 20 mA modulating output Two relay outputs Adjustable P I D control on modulating output Adjustable offsets and d...

Страница 2: ...r sensing Powering the SZ1143b The SZ1143b is powered from 24 VAC 20 Caution Do not connect to 120 VAC When multiple TCS Basys Controls devices are using a single transformer the polarity of the power...

Страница 3: ...the analog output range will be 0 20mA or 4 20mA This screen is the last screen if High Low control mode is enabled and is the same as step 22 when not enabled Enable Dew Point Control Select yes to e...

Страница 4: ...t Type Screen Select whether the analog output will be modulated from an endpoint or the mid point Note Set to MIDPOINT if dew point control is selected Analog Output Unoccupied Action Screen Select w...

Страница 5: ...e IN1 or IN2 terminal of the first SZ1143b Remove the RTN1 or RTN2 jumper from the second SZ1143b Refer to Sharing analog inputs on an SZ1143b Application note for more detail HIGH LOW CONTROL The ana...

Страница 6: ...gramming screens 22 through 31 AI2 MODE PARAMETERS Analog input two can be selected as either Monitor Remote Setpoint or Reset If monitor is chosen the analog output and digital out puts are controlle...

Страница 7: ...point In most cases the first stage is set to zero The differential value is the differ ence between the on and off points Setpoint O N O N O N O N O FF O FF O FF O FF Differential Differential O ffse...

Страница 8: ...res off will instantly turn all outputs off and reset the controller Analog Output Not Working Properly Check wiring A separate transformer should be used for the SZ1143b and a separate transformer sh...

Страница 9: ...ed Setpoint and Analog Output Screen Shows the current setpoint used for control and the output value for the analog output The analog output is dis played as a percentage 0 100 Analog Output Screen S...