TCS Basys Controls SZ1017N Скачать руководство пользователя страница 5

program

setup

program

setup

program

setup

program

setup

program

setup

program

setup

program

setup

program

setup

30.

DISCHARGE AIR

LOW LIMIT:             45F

29.

28.

ENABLE DISCHARGE

AIR SENSOR?       YES

SETPOINT

OFFSET:                00F

27.

UNOCCUPIED ACTION

25.

              MODULATING

MODULATING OUT

RANGE:           4-20 MA

24.

OUTPUT ACTION:

.

                         DIRECT

22.

MODULATING OUT

IS:                        COOL

21.

SET CONTROL

MODE:                    P+I

23.

program

setup

PROPORTIONAL

BAND:                     5F

26.

program

setup

TIME CLOCK OUTPUT

OCCUPIED=CLOSED

program

setup

program

setup

program

setup

program

setup

program

setup

program

setup

program

setup

program

setup

STAGE 2

DIFF:                        2F

20.

STAGE 2

OFFSET:                  2F

19.

18.

STAGE 1

DIFF:                        2F

STAGE 1

OFFSET:                 0F

17.

STAGE OUTPUT 1&2

16.

AS:                      HEAT

SET OVERRIDE

TIME:     180 MINUTES

15.

LIMIT SETPOINT

14.

/-:              5F

13.

UNOCCUPIED COOL

SETPOINT:             80F

12.

OCCUPIED COOL

SETPOINT:             72F

program

setup

Occupied Cool Setpoint  Screen.

Set

the occupied cool setpoint.

Unoccupied Cool Setpoint Screen.

Set the unoccupied cool setpoint.

User Setpoint Limit Screen.

Enter

the number of degrees you want the
user to be allowed to change the pre-
set occupied setpoints up or down.

Override Time Screen.

Enter the

number of minutes (0 to 255) that the
SZ1017N will maintain occupied set-
points when overridden.  

Stage Mode Screen.

Choose whether

stages 1 and 2 perform heating or
cooling functions, or whether both
stages are to be disabled.

Stage 1 Offset  Screen.

Enter an off-

set value for stage 1. First stage is nor-
mally 0 offset. This screen does not
appear if stage outputs 1 and 2 are
disabled.

Stage 1 Differential Screen.

Enter a

differential value for stage 1. This
screen does not appear if stage out-
puts 1 and 2 are disabled.

Stage 2 Offset  Screen.

Enter an off-

set value for stage 2. This screen does
not appear if stage outputs 1 and 2 are
disabled.

Stage 2 Differential Screen.

Enter a

differential value for stage 2. This
screen does not appear if stage out-
puts 1 and 2 are disabled.

Control Mode Screen.

Enter whether you

want to control by temperature only (P) or
add a time factor (P+I). This applies to both
the stage outputs.

Time Clock Output Screen. 

Choose

whether the auxiliary output will be OPEN
during occupied periods (and closed during
unoccupied periods) or CLOSED during
occupied periods (and open during unoccu-
pied periods). 

Modulating Output Define Screen.

Choose whether the modulating output will
be used for COOL, HEAT or AQUASTAT.
With DI2 set to AQUASTAT, the analog out-
put will be used for cooling with DI2 open
and heating with DI2 closed.

Modulating Output Action Screen

.

Choose whether the output will be direct or
reverse acting. (When DI2 is set to AQUAS-
TAT, the output will automatically reverse
action when DI2 is closed.)

Modulating Output Range Screen.

Choose whether the modulating output
range will be 0-20 mA or 4-20 mA.

Unoccupied Action Screen. 

Choose

whether the unoccupied action will be mod-
ulating, 0 or 4 mA, or 20 mA.

Modulating Output Proportional Band
Screen. 

Enter the number of degrees away

from the setpoint that the valve or damper
will be fully open. 

Analog Output Setpoint Offset Screen.

Enter a setpoint offset. This is a value below
the heating setpoint or above the cooling
setpoint where the analog output begins to
modulate.

Discharge Air Sensor Screen.

Choose whether

or not you are using the discharge air sensor
function. To monitor only, select no.See setup
instructions for dipswitch settings which must also
be set.

Discharge Air Low Limit Screen.

Enter a

discharge air low limit value. This screen
will not appear if the discharge air sensor
function is disabled.

R

2800 LAURA LANE 

I

MIDDLETON, WI 53562 

I

(800) 288-9383 

I

FAX (608) 836-9044 

I

www.tcs-basys.com

5

Содержание SZ1017N

Страница 1: ...e locked out or limited with the use of an access code Fahrenheit or Celsius temperature display Product Manual Contents Description 1 Features 1 Mounting 1 N2 Bus Connections 2 Wiring 2 Setup 3 Progr...

Страница 2: ...ughout because these are half wave recti fied devices SZ1017N thermostats require 8 VA 24 VAC When the SZ1017N is used as a stand alone thermostat with out communications the unit transformer may be u...

Страница 3: ...e two set screws located at the top right and the left side to prevent tampering Setup Note If using remote sensor s the calibration may need to be adjusted See Checkout and Troubleshooting section SE...

Страница 4: ...S TEMPS SHOWN IN 4 FAHRENHEIT program setup Main Monitoring Screen Press the pro gram setup button to access the following screens Access Code Entry Screen Will appear if access code is required for p...

Страница 5: ...pear if stage outputs 1 and 2 are disabled Stage 2 Differential Screen Enter a differential value for stage 2 This screen does not appear if stage out puts 1 and 2 are disabled Control Mode Screen Ent...

Страница 6: ...by 1 degree for cooling Outdoor Air Sensor Screen Choose whether or not you are using an outdoor air sensor function To monitor only select no See setup instructions for dip switch settings which must...

Страница 7: ...l be maintained and the fan will operate according to its unoc cupied setting The occupied LED will be lit when the unit is operating in the occupied mode The occupied schedule may be set utilizing th...

Страница 8: ...ns or dis charge air reset function See Discharge Air Reset section for further programming options If NO is chosen the dis charge air is still monitored When the function is enabled a LOW LIMIT and H...

Страница 9: ...ences to protect equipment The fan has a minimum on and off time of 30 seconds When the fan is in AUTO or COOL mode it will come on 30 seconds before the heating or cooling stages are allowed to seque...

Страница 10: ...roubleshooting section TROUBLESHOOTING No Display Check for 24 VAC on terminals 24 and 24 Check the cable connecting the cover to the base for a good connec tion Fan Does Not Come On The fan is on whe...

Страница 11: ...a PC Additional monitoring is available by continually pressing the service key MON 72F 12 00 AM DISCHARGE AIR 55F OUTDOOR AIR OVERRIDE ON 178 MINUTES 75F HEAT STAGE 1 OFF MOD OUT 100 SERVICE STATUS O...

Страница 12: ...ry default the unit will remain in the occupied mode for 180 minutes This value may be changed from 0 to 255 minutes in programming step 15 FAN SWITCHING The option to allow the occupant to change th...

Страница 13: ...0 90 Occupied heating setpoint must be less than occupied cooling setpoint ADI 20 DegF Unoccupied heating setpoint 40 90 Unoccupied heating setpoint must be less than unoccupied cooling setpoint ADI 2...

Страница 14: ...itch 0 No 1 Yes Enables System Switch button BD 5 Use of discharge air sensor 0 No 1 Yes Always monitored enables discharge air function BD 6 Use of outdoor air sensor 0 No 1 Yes BD 7 Enable smart rec...

Страница 15: ...it 0 OK 1 Below Read only Discharge air function low limit BD 41 DI2 service status 0 OK 1 Check DI2 Read only DI2 Service NOTE 1 The Service status point represents general Check status if this is po...

Страница 16: ...Rev 1000 R 2800 LAURA LANE IMIDDLETON WI 53562 I 800 288 9383 IFAX 608 836 9044 Iwww tcs basys com 16...

Отзывы: