Programming                    

The SZ1017N may be programmed through the display and
keypad, or with a PC. 

If programming with a PC, the following must be set
through the keypad prior to programming:

!

Address (step #3)

!

Temperature scale (step #4) 

For more information on programming through the PC, con-
sult your software manuals. 

PROGRAMMING THROUGH THE KEYPAD

To access the programming screens, press the program setup
button. To make changes, use the warmer and cooler keys.
Access may be locked out with dipswitches, or an access
code may be required. 

fan

Occupied

Heating

Cooling

Fan

Service

Program/

COOLER

WARMER

Data

switch

system

switch

program

setup

clock
setup

override

service

status

program

setup

program

setup

SET ADDRESS:

000

2.

ENTER ACCESS

000

1.

CODE

MON

72F

12:00 AM

program

setup

3.

program

setup

program

setup

program

setup

program

setup

program

setup

program

setup

program

setup

11.

UNOCCUPIED HEAT

SETPOINT:            60F

OCCUPIED HEAT

10.

SETPOINT:            68F

SET UNOCCUPIED

FAN MODE:       AUTO

9.

8.

SET OCCUPIED FAN

MODE:                    ON

USER ACCESS TO

FAN MODE?         YES

7.

SET SYSTEM

6.

MODE:                 AUTO

USER ACCESS TO

5.

SYSTEM MODE?   YES

TEMPS SHOWN IN:

4.

FAHRENHEIT

program

setup

Main Monitoring Screen.

Press the pro-

gram setup button to access the following
screens. 

Access Code Entry  Screen.

Will appear

if access code is required for programming.
Use 248 as the default. If the wrong code is
entered, it will revert to the previous screen. 

Controller Address Screen.

If using a PC

to access the SZ1017N, set a unique
address from 1 to 255.

Display Type Screen.

Choose between

FAHRENHEIT and CELSIUS for tempera-
ture indication.

System Access Screen. 

Choose whether

or not to enable user’s access to the sys-
tem switch to set the system mode. 

System Mode Screen.

Choose from

AUTO, HEAT, COOL, or OFF for system
mode. In the OFF mode, all outputs are off.

Fan Access Screen. 

Choose whether or

not to enable the user’s access to the fan
switch to set the occupied fan mode. 

Occupied Fan Mode Screen. 

Choose

between ON (continuous), COOL (gas heat
or no heat), or AUTO for your fan run times
during the occupied modes.

Unoccupied Fan Mode Screen.

Choose

from AUTO or COOL for fan run times in
the unoccupied mode.

Occupied Heat Setpoint  Screen.

Set the

occupied heat setpoint.

Unoccupied Heat Setpoint Screen.

Set

the unoccupied heat setpoint.

R

2800 LAURA LANE 

I

MIDDLETON, WI 53562 

I

(800) 288-9383 

I

FAX (608) 836-9044 

I

www.tcs-basys.com

4

Содержание SZ1017N

Страница 1: ...e locked out or limited with the use of an access code Fahrenheit or Celsius temperature display Product Manual Contents Description 1 Features 1 Mounting 1 N2 Bus Connections 2 Wiring 2 Setup 3 Progr...

Страница 2: ...ughout because these are half wave recti fied devices SZ1017N thermostats require 8 VA 24 VAC When the SZ1017N is used as a stand alone thermostat with out communications the unit transformer may be u...

Страница 3: ...e two set screws located at the top right and the left side to prevent tampering Setup Note If using remote sensor s the calibration may need to be adjusted See Checkout and Troubleshooting section SE...

Страница 4: ...S TEMPS SHOWN IN 4 FAHRENHEIT program setup Main Monitoring Screen Press the pro gram setup button to access the following screens Access Code Entry Screen Will appear if access code is required for p...

Страница 5: ...pear if stage outputs 1 and 2 are disabled Stage 2 Differential Screen Enter a differential value for stage 2 This screen does not appear if stage out puts 1 and 2 are disabled Control Mode Screen Ent...

Страница 6: ...by 1 degree for cooling Outdoor Air Sensor Screen Choose whether or not you are using an outdoor air sensor function To monitor only select no See setup instructions for dip switch settings which must...

Страница 7: ...l be maintained and the fan will operate according to its unoc cupied setting The occupied LED will be lit when the unit is operating in the occupied mode The occupied schedule may be set utilizing th...

Страница 8: ...ns or dis charge air reset function See Discharge Air Reset section for further programming options If NO is chosen the dis charge air is still monitored When the function is enabled a LOW LIMIT and H...

Страница 9: ...ences to protect equipment The fan has a minimum on and off time of 30 seconds When the fan is in AUTO or COOL mode it will come on 30 seconds before the heating or cooling stages are allowed to seque...

Страница 10: ...roubleshooting section TROUBLESHOOTING No Display Check for 24 VAC on terminals 24 and 24 Check the cable connecting the cover to the base for a good connec tion Fan Does Not Come On The fan is on whe...

Страница 11: ...a PC Additional monitoring is available by continually pressing the service key MON 72F 12 00 AM DISCHARGE AIR 55F OUTDOOR AIR OVERRIDE ON 178 MINUTES 75F HEAT STAGE 1 OFF MOD OUT 100 SERVICE STATUS O...

Страница 12: ...ry default the unit will remain in the occupied mode for 180 minutes This value may be changed from 0 to 255 minutes in programming step 15 FAN SWITCHING The option to allow the occupant to change th...

Страница 13: ...0 90 Occupied heating setpoint must be less than occupied cooling setpoint ADI 20 DegF Unoccupied heating setpoint 40 90 Unoccupied heating setpoint must be less than unoccupied cooling setpoint ADI 2...

Страница 14: ...itch 0 No 1 Yes Enables System Switch button BD 5 Use of discharge air sensor 0 No 1 Yes Always monitored enables discharge air function BD 6 Use of outdoor air sensor 0 No 1 Yes BD 7 Enable smart rec...

Страница 15: ...it 0 OK 1 Below Read only Discharge air function low limit BD 41 DI2 service status 0 OK 1 Check DI2 Read only DI2 Service NOTE 1 The Service status point represents general Check status if this is po...

Страница 16: ...Rev 1000 R 2800 LAURA LANE IMIDDLETON WI 53562 I 800 288 9383 IFAX 608 836 9044 Iwww tcs basys com 16...

Отзывы: