background image

3. Press the PROGRAM SETUP button until you reach the

screen # 14 which allows you to set the occupant set-
point adjustment limits. Change this to +/-20 °F (11.1
°C). Press the PROGRAM SETUP button once more to
store the change. Then press the SERVICE STATUS but-
ton once to exit the programming. 

4. Press the FAN SWITCH button to access the fan mode

and change the mode to AUTO. Press the FAN SWITCH
button once more to store the change.  Press the SYS-
TEM SWITCH button to access the system mode and
change the mode to AUTO. Press the SYSTEM
SWITCH button once more to store the change.  

5. Verify that the thermostat is operating in the occupied

mode by making sure that the top LED is lit. If not, press
the OVERRIDE button. The LED should light up. 

6. Take note of the current temperature reading. Press the

WARMER (up) button. The setpoint adjustment screen
should now be showing. Press the WARMER button
until the heating setpoint is greater than the current tem-
perature by at least five degrees. The fan will come on.
The heating stage(s) will sequence on after 30 seconds. 

7. Press the cooler (down) button until the heating setpoint

is one degree less than the current temperature. The heat-
ing stage(s) will sequence off. The fan will turn off 30
seconds after the last heating stage. 

8. Press the cooler button until the cooling setpoint is less

than the current temperature by at least five degrees. The
fan will come on.  The cooling stage(s) will sequence on
after 30 seconds. 

9. Press the warmer button until the cooling setpoint is

greater than the current temperature by one degree. The
cooling stage(s) will sequence off. The fan will turn off
30 seconds after the last cooling stage.

10. Take note of the room (and discharge) air temperatures.

If the analog output is set for Cooling, press the Cooler
button until the cooling setpoint is less than the current
room temperature by at least 5°. The cooling device
should start operating. If the analog output is set for
Heating, press the Warmer button until the heating set-
point is greater than the current room temperature by at
least 5°. The heating device should start operating.

11. Go back to programming step #14 and set the setpoint

adjust limit back to the desired value. Make any other
changes in programming, clock, and schedule. Set the
fan and system modes to their desired settings. 

12. If using remote sensors, verify that the reading is cor-

rect. If not, see 

Wrong Temperature Display 

in

“Troubleshooting” section.

TROUBLESHOOTING

No Display

Check for 24 VAC on terminals “+24” and “-24”. Check the
cable connecting the cover to the base for a good connec-
tion.

Fan Does Not Come On

The fan is on whenever the fan LED is on. If the fan should
be on, but the fan LED is off, check the fan and system switch
modes, and the unoccupied fan mode in programming. If the
fan is off but the fan LED is on, check wiring. Short terminals
“R” to “G” and see if the fan comes on. This is a check for a
mechanical relay failure. 

Heating or Cooling Does Not Come On

At least one stage of heating is on whenever the  heating LED
is on, and at least one stage of cooling is on whenever the
cooling LED is on. If heating or cooling should be on but the
heating or cooling LED is off, check the fan and system
switch modes. Also, check the heating and cooling setpoints,
offsets and differentials, and the room temperature to be sure
heating or cooling should be on. If using outdoor air heating
and cooling lockouts, or discharge air high and low limits,
check their values to be sure heating or cooling is allowed. If
heating or cooling is off, but the corresponding LED is on,
check the wiring. Short terminals “R” to “Y/W1” or “Y/W2”
and see if the heating or cooling comes on. This is a check for
a mechanical relay failure. 

Wrong Temperature Display

If any of the temperatures is reading slightly high or low, there
are three adjustment pots located in the cover to adjust them.
“T1” is for the room temperature, “T2” is for the discharge air
temperature, and “T3” is for the outdoor air temperature. If the
temperature is at a minimum or maximum reading, check the
sensor dipswitch positions. (See setup instructions.) Check for
wiring problems (opens or shorts). A remote 1000 

sensor

should read 1080 to 1090 

at room temperature. The built-in

sensor should read 108 to 109 

at room temperature. 

Service LED is On

If the service LED is on, it may be for monitoring purposes or
it may indicate a critical problem. The first monitoring screen
accessed by pressing the service status button will display why
the light is on.

Outputs Will Not Shut Off

First check the room temperature and the setpoints and deter-
mine whether the output should be on. There are delays and
minimum on and off times for the fan and heating and cooling
stages. Also, check the service status menus to verify that the
outputs are on. Turning the system to “off” will instantly turn
all outputs off. The thermostat can be reset by pressing the
system switch button and the service status button simultane-
ously.  

R

2800 LAURA LANE 

I

MIDDLETON, WI 53562 

I

(800) 288-9383 

I

FAX (608) 836-9044 

I

www.tcs-basys.com

10

Содержание SZ1017N

Страница 1: ...e locked out or limited with the use of an access code Fahrenheit or Celsius temperature display Product Manual Contents Description 1 Features 1 Mounting 1 N2 Bus Connections 2 Wiring 2 Setup 3 Progr...

Страница 2: ...ughout because these are half wave recti fied devices SZ1017N thermostats require 8 VA 24 VAC When the SZ1017N is used as a stand alone thermostat with out communications the unit transformer may be u...

Страница 3: ...e two set screws located at the top right and the left side to prevent tampering Setup Note If using remote sensor s the calibration may need to be adjusted See Checkout and Troubleshooting section SE...

Страница 4: ...S TEMPS SHOWN IN 4 FAHRENHEIT program setup Main Monitoring Screen Press the pro gram setup button to access the following screens Access Code Entry Screen Will appear if access code is required for p...

Страница 5: ...pear if stage outputs 1 and 2 are disabled Stage 2 Differential Screen Enter a differential value for stage 2 This screen does not appear if stage out puts 1 and 2 are disabled Control Mode Screen Ent...

Страница 6: ...by 1 degree for cooling Outdoor Air Sensor Screen Choose whether or not you are using an outdoor air sensor function To monitor only select no See setup instructions for dip switch settings which must...

Страница 7: ...l be maintained and the fan will operate according to its unoc cupied setting The occupied LED will be lit when the unit is operating in the occupied mode The occupied schedule may be set utilizing th...

Страница 8: ...ns or dis charge air reset function See Discharge Air Reset section for further programming options If NO is chosen the dis charge air is still monitored When the function is enabled a LOW LIMIT and H...

Страница 9: ...ences to protect equipment The fan has a minimum on and off time of 30 seconds When the fan is in AUTO or COOL mode it will come on 30 seconds before the heating or cooling stages are allowed to seque...

Страница 10: ...roubleshooting section TROUBLESHOOTING No Display Check for 24 VAC on terminals 24 and 24 Check the cable connecting the cover to the base for a good connec tion Fan Does Not Come On The fan is on whe...

Страница 11: ...a PC Additional monitoring is available by continually pressing the service key MON 72F 12 00 AM DISCHARGE AIR 55F OUTDOOR AIR OVERRIDE ON 178 MINUTES 75F HEAT STAGE 1 OFF MOD OUT 100 SERVICE STATUS O...

Страница 12: ...ry default the unit will remain in the occupied mode for 180 minutes This value may be changed from 0 to 255 minutes in programming step 15 FAN SWITCHING The option to allow the occupant to change th...

Страница 13: ...0 90 Occupied heating setpoint must be less than occupied cooling setpoint ADI 20 DegF Unoccupied heating setpoint 40 90 Unoccupied heating setpoint must be less than unoccupied cooling setpoint ADI 2...

Страница 14: ...itch 0 No 1 Yes Enables System Switch button BD 5 Use of discharge air sensor 0 No 1 Yes Always monitored enables discharge air function BD 6 Use of outdoor air sensor 0 No 1 Yes BD 7 Enable smart rec...

Страница 15: ...it 0 OK 1 Below Read only Discharge air function low limit BD 41 DI2 service status 0 OK 1 Check DI2 Read only DI2 Service NOTE 1 The Service status point represents general Check status if this is po...

Страница 16: ...Rev 1000 R 2800 LAURA LANE IMIDDLETON WI 53562 I 800 288 9383 IFAX 608 836 9044 Iwww tcs basys com 16...

Отзывы: