Pointmap Table for SZ1017N (continued)

NPT

NPA

UNITS

POINT DESCRIPTION

RANGE/VALUE

ADDITIONAL NOTES

BD

17

DI1 source 

0=local contact

"Local" means read by or controlled by
Thermostat.

1=remote request

"Remote" means the state of the input

or

output is controlled only by computer.

BD

18

DI2 source

0=local contact
1=remote request

BD

19

DI3 source 

0=local contact
1=remote request

BD

20

Override function source

0=local keypad
1=remote request

BD

21

Fan relay source

0=local mode
1=remote requset

BD

22

Remote DI1 request

0=off, 1=on

When selected to be "Remote", turns
input or output on and off.

BD

23

Remote DI2 request

0=off, 1=on

BD

24

Remote DI3 request

0=off, 1=on

BD 

25

Remote override request

0=off, 1=on

This is a permanent override.

BD

26

Remote Fan request

0=off, 1=on

BD

27

Stage 1 relay status

0=off, 1=on

Read only.

BD

28

Stage 2 relay status

0=off, 1=on 

Read Only

BD

29

Fan relay status

0=off, 1=on

Read only.

BD

30

Timeclock relay status

0=off, 1=on 

Read only.

BD

31

DI1 status

0=off, 1=on

Read only.

BD

32

DI2 status

0=off, 1=on

Read only.

BD

33

DI3 status

0=off, 1=on

Read only.

BD

34

Override status

0=off, 1=on

Read only. Timed override.

BD

35

Device's occupied status

0=Occupied

Read only.

1=Unoccupied

BD

36

Service status

0=OK, 1= fail

Read only. See Note 1.

BD

37

Fan interlock status

0= OK,  

Read only. DI1 Fan Proving.

1= Fan interlock fail

BD

38

Filter service status

0=OK, 1=check

Read only. DI3 Filter Status.

Filter

BD 

39

Discharge air high limit

0=OK, 1= Above 

Read only. Discharge air function.

high limit

BD

40

Discharge air low limit

0=OK, 1= Below

Read only. Discharge air function.

low limit

BD

41

DI2 service status

0=OK, 1= Check DI2

Read only. DI2 Service.

NOTE 1:

The Service status point represents general Check status, if this is point is 1, then by polling point 37 to 41 the user

can find out actual failing condition. If this point is 0 then points 37 to 41 will be also 0. 

NOTE 2: 

All of the ADI and BD points support the override function. The value overridden will be stored permanently, so the sta-

tus attribute will never have any override active status. Because none of these points support the override release function, the
controller will acknowledge the override release function but never release the value. The controller will respond with NAK error
N10 if the value for the override command is outside the limits for that point. Points that are "Read Only" can not be overridden.
The controller will acknowledge the override command, but the actual change will never happen.

NOTE 3: 

All of the points in this map can be adjusted through the keypad except: “Read Only” points, ADI 32, and BDpoints 17

through 26. In the case of loss of communications for 15 minutes (i.e., if the controller is not addressed for 15 minutes), the con-
troller will revert BD points 17 to 26 to zero value (make them all local requests).

NOTE 4:

ADI point 32, Outdoor Air Temp., can be overridden for a default of 10 minutes. After 10 minutes it reverts back to its

original port value.

NOTE 5:

Communications are disabled when programming mode or clock/schedule mode is entered via the keypad. Entering

programming mode via the keypad can be disabled. 

NOTE 6:

0-150 number represents 0.0 to 15.0°F.

R

2800 LAURA LANE 

I

MIDDLETON, WI 53562 

I

(800) 288-9383 

I

FAX (608) 836-9044 

I

www.tcs-basys.com

15

Содержание SZ1017N

Страница 1: ...e locked out or limited with the use of an access code Fahrenheit or Celsius temperature display Product Manual Contents Description 1 Features 1 Mounting 1 N2 Bus Connections 2 Wiring 2 Setup 3 Progr...

Страница 2: ...ughout because these are half wave recti fied devices SZ1017N thermostats require 8 VA 24 VAC When the SZ1017N is used as a stand alone thermostat with out communications the unit transformer may be u...

Страница 3: ...e two set screws located at the top right and the left side to prevent tampering Setup Note If using remote sensor s the calibration may need to be adjusted See Checkout and Troubleshooting section SE...

Страница 4: ...S TEMPS SHOWN IN 4 FAHRENHEIT program setup Main Monitoring Screen Press the pro gram setup button to access the following screens Access Code Entry Screen Will appear if access code is required for p...

Страница 5: ...pear if stage outputs 1 and 2 are disabled Stage 2 Differential Screen Enter a differential value for stage 2 This screen does not appear if stage out puts 1 and 2 are disabled Control Mode Screen Ent...

Страница 6: ...by 1 degree for cooling Outdoor Air Sensor Screen Choose whether or not you are using an outdoor air sensor function To monitor only select no See setup instructions for dip switch settings which must...

Страница 7: ...l be maintained and the fan will operate according to its unoc cupied setting The occupied LED will be lit when the unit is operating in the occupied mode The occupied schedule may be set utilizing th...

Страница 8: ...ns or dis charge air reset function See Discharge Air Reset section for further programming options If NO is chosen the dis charge air is still monitored When the function is enabled a LOW LIMIT and H...

Страница 9: ...ences to protect equipment The fan has a minimum on and off time of 30 seconds When the fan is in AUTO or COOL mode it will come on 30 seconds before the heating or cooling stages are allowed to seque...

Страница 10: ...roubleshooting section TROUBLESHOOTING No Display Check for 24 VAC on terminals 24 and 24 Check the cable connecting the cover to the base for a good connec tion Fan Does Not Come On The fan is on whe...

Страница 11: ...a PC Additional monitoring is available by continually pressing the service key MON 72F 12 00 AM DISCHARGE AIR 55F OUTDOOR AIR OVERRIDE ON 178 MINUTES 75F HEAT STAGE 1 OFF MOD OUT 100 SERVICE STATUS O...

Страница 12: ...ry default the unit will remain in the occupied mode for 180 minutes This value may be changed from 0 to 255 minutes in programming step 15 FAN SWITCHING The option to allow the occupant to change th...

Страница 13: ...0 90 Occupied heating setpoint must be less than occupied cooling setpoint ADI 20 DegF Unoccupied heating setpoint 40 90 Unoccupied heating setpoint must be less than unoccupied cooling setpoint ADI 2...

Страница 14: ...itch 0 No 1 Yes Enables System Switch button BD 5 Use of discharge air sensor 0 No 1 Yes Always monitored enables discharge air function BD 6 Use of outdoor air sensor 0 No 1 Yes BD 7 Enable smart rec...

Страница 15: ...it 0 OK 1 Below Read only Discharge air function low limit BD 41 DI2 service status 0 OK 1 Check DI2 Read only DI2 Service NOTE 1 The Service status point represents general Check status if this is po...

Страница 16: ...Rev 1000 R 2800 LAURA LANE IMIDDLETON WI 53562 I 800 288 9383 IFAX 608 836 9044 Iwww tcs basys com 16...

Отзывы: