Pointmap Table for SZ1017N (continued)
NPT
NPA
UNITS
POINT DESCRIPTION
RANGE/VALUE
ADDITIONAL NOTES
BD
17
DI1 source
0=local contact
"Local" means read by or controlled by
Thermostat.
1=remote request
"Remote" means the state of the input
or
output is controlled only by computer.
BD
18
DI2 source
0=local contact
1=remote request
BD
19
DI3 source
0=local contact
1=remote request
BD
20
Override function source
0=local keypad
1=remote request
BD
21
Fan relay source
0=local mode
1=remote requset
BD
22
Remote DI1 request
0=off, 1=on
When selected to be "Remote", turns
input or output on and off.
BD
23
Remote DI2 request
0=off, 1=on
BD
24
Remote DI3 request
0=off, 1=on
BD
25
Remote override request
0=off, 1=on
This is a permanent override.
BD
26
Remote Fan request
0=off, 1=on
BD
27
Stage 1 relay status
0=off, 1=on
Read only.
BD
28
Stage 2 relay status
0=off, 1=on
Read Only
BD
29
Fan relay status
0=off, 1=on
Read only.
BD
30
Timeclock relay status
0=off, 1=on
Read only.
BD
31
DI1 status
0=off, 1=on
Read only.
BD
32
DI2 status
0=off, 1=on
Read only.
BD
33
DI3 status
0=off, 1=on
Read only.
BD
34
Override status
0=off, 1=on
Read only. Timed override.
BD
35
Device's occupied status
0=Occupied
Read only.
1=Unoccupied
BD
36
Service status
0=OK, 1= fail
Read only. See Note 1.
BD
37
Fan interlock status
0= OK,
Read only. DI1 Fan Proving.
1= Fan interlock fail
BD
38
Filter service status
0=OK, 1=check
Read only. DI3 Filter Status.
Filter
BD
39
Discharge air high limit
0=OK, 1= Above
Read only. Discharge air function.
high limit
BD
40
Discharge air low limit
0=OK, 1= Below
Read only. Discharge air function.
low limit
BD
41
DI2 service status
0=OK, 1= Check DI2
Read only. DI2 Service.
NOTE 1:
The Service status point represents general Check status, if this is point is 1, then by polling point 37 to 41 the user
can find out actual failing condition. If this point is 0 then points 37 to 41 will be also 0.
NOTE 2:
All of the ADI and BD points support the override function. The value overridden will be stored permanently, so the sta-
tus attribute will never have any override active status. Because none of these points support the override release function, the
controller will acknowledge the override release function but never release the value. The controller will respond with NAK error
N10 if the value for the override command is outside the limits for that point. Points that are "Read Only" can not be overridden.
The controller will acknowledge the override command, but the actual change will never happen.
NOTE 3:
All of the points in this map can be adjusted through the keypad except: “Read Only” points, ADI 32, and BDpoints 17
through 26. In the case of loss of communications for 15 minutes (i.e., if the controller is not addressed for 15 minutes), the con-
troller will revert BD points 17 to 26 to zero value (make them all local requests).
NOTE 4:
ADI point 32, Outdoor Air Temp., can be overridden for a default of 10 minutes. After 10 minutes it reverts back to its
original port value.
NOTE 5:
Communications are disabled when programming mode or clock/schedule mode is entered via the keypad. Entering
programming mode via the keypad can be disabled.
NOTE 6:
0-150 number represents 0.0 to 15.0°F.