TCS Basys Controls SZ1017N Скачать руководство пользователя страница 13

Pointmap Table for SZ1017N 

NPT

NPA

UNITS

POINT DESCRIPTION

RANGE/VALUE

ADDITIONAL NOTES

ADI

1

#

DI2 control mode

0=Aquastat, 

See programming step #39.

1=monitor, 2=service

ADI

2

#

Unocc Analog output action

0=0or4 mA, 1=20 mA

See programming step #26.

2=Modulating

ADI 

3

#

Analog output mode

0=heat, 1= cool,

See programming step #23.

2=Aquastat

ADI

4

#

DI3 control mode

0=filter service, 

See programming step #41.

1=external override, 
2= external timeclock

ADI

5

#

Occupied Fan mode

0=on, 1=cool, 2=auto

"Fan Switch" button on keypad.

ADI

6

#

System mode

0=off,1=auto,2=heat

"System Switch" button on keypad.

3=cool

ADI

7

Day

Internal time clock "day"

0-6, mon to sunday

Day of Week.

ADI

8

Hours

Internal time clock "hours"

0-23

0-12 (AM), 13-23 (PM).

ADI

9

DegF

Setpoint adjust limit from keypad

0-50

Limits keypad adjustment of occupied
heating and cooling setpoints.

ADI

10

DegF

Differential for stage 1

0-50

ADI

11

DegF

Offset for stage 1

0-50

ADI

12

DegF

Differential for stage 2

0-50

ADI

13

DegF

Offset for stage 2

0-50

ADI

14

DegF

Setpoint shift value

0-50

When DI2 is selected "Monitor", this is
number of degrees that the occupied
cooling setpoint is shifted up and the
heating setpoint is shifted down.

ADI

15

DegF

(space) Setpoint offset

0-50

See programming step #28.

ADI

16

DegF

AO Proportional Band

0-50

See programming step #27.

ADI

17

Seconds

Internal time clock "second"

0-59

ADI

18

Minutes

Internal time clock "minute"

0-59

ADI

19

DegF

Occupied heating setpoint 

40-90

Occupied heating setpoint must be less
than occupied cooling setpoint.

ADI

20

DegF

Unoccupied heating setpoint

40-90

Unoccupied heating setpoint must be

less

than unoccupied cooling setpoint.

ADI

21

DegF

Occupied cooling setpoint

40-90

ADI

22

DegF

Unoccupied cooling setpoint

40-90

ADI

23

DegF

Room temperature

40-90

Read only.

ADI

24

%

Analog Output

0-100%

Read only.

ADI

25

DegF

Discharge air setpoint

0-150

See programming step #33.

ADI

26

#

Reset ratio

0-150

See programming step #34 (Note 6).

ADI

27

DegF

Discharge air low limit

0-150

Discharge air high limit must be less
than discharge air low limit.

ADI

28

DegF

Discharge air high limit

0-150

ADI

29

DegF

Discharge air temperature

0-150

Read only.

ADI

30

DegF

Outdoor heat lockout temp

-40 to 160

See programming step #37.

ADI

31

DegF

Outdoor cool lockout

-40 to 160

See programming step #36.

ADI

32

DegF

Outdoor air temperature

-40 to 160

See Note 4

ADI

33

Minutes

Override period

0-255

Unoccupied override time allowed.

ADI

34

Seconds

Power on delay time

0-255

Time before control begins on powerup.

ADI

35

Minutes

Remaining override time

0-255

Read Only. Time remaining before the 
override period expires.

ADI

36

DegF

Current user setpoint adjust

Min=-50, Max=50

Read Only. + or - amount the occupied
setpoint has been adjusted from actual
settings.

ADI

37

Minutes

Monday Occupied start time

0-1439

There are two occupied and two un-

for schedule A

occupied time periods allowed per day.

ADI

38

Minutes

Monday Occupied end time

0-1439

All times are measured in minutes from

for schedule A

midnight.

R

2800 LAURA LANE 

I

MIDDLETON, WI 53562 

I

(800) 288-9383 

I

FAX (608) 836-9044 

I

www.tcs-basys.com

13

Содержание SZ1017N

Страница 1: ...e locked out or limited with the use of an access code Fahrenheit or Celsius temperature display Product Manual Contents Description 1 Features 1 Mounting 1 N2 Bus Connections 2 Wiring 2 Setup 3 Progr...

Страница 2: ...ughout because these are half wave recti fied devices SZ1017N thermostats require 8 VA 24 VAC When the SZ1017N is used as a stand alone thermostat with out communications the unit transformer may be u...

Страница 3: ...e two set screws located at the top right and the left side to prevent tampering Setup Note If using remote sensor s the calibration may need to be adjusted See Checkout and Troubleshooting section SE...

Страница 4: ...S TEMPS SHOWN IN 4 FAHRENHEIT program setup Main Monitoring Screen Press the pro gram setup button to access the following screens Access Code Entry Screen Will appear if access code is required for p...

Страница 5: ...pear if stage outputs 1 and 2 are disabled Stage 2 Differential Screen Enter a differential value for stage 2 This screen does not appear if stage out puts 1 and 2 are disabled Control Mode Screen Ent...

Страница 6: ...by 1 degree for cooling Outdoor Air Sensor Screen Choose whether or not you are using an outdoor air sensor function To monitor only select no See setup instructions for dip switch settings which must...

Страница 7: ...l be maintained and the fan will operate according to its unoc cupied setting The occupied LED will be lit when the unit is operating in the occupied mode The occupied schedule may be set utilizing th...

Страница 8: ...ns or dis charge air reset function See Discharge Air Reset section for further programming options If NO is chosen the dis charge air is still monitored When the function is enabled a LOW LIMIT and H...

Страница 9: ...ences to protect equipment The fan has a minimum on and off time of 30 seconds When the fan is in AUTO or COOL mode it will come on 30 seconds before the heating or cooling stages are allowed to seque...

Страница 10: ...roubleshooting section TROUBLESHOOTING No Display Check for 24 VAC on terminals 24 and 24 Check the cable connecting the cover to the base for a good connec tion Fan Does Not Come On The fan is on whe...

Страница 11: ...a PC Additional monitoring is available by continually pressing the service key MON 72F 12 00 AM DISCHARGE AIR 55F OUTDOOR AIR OVERRIDE ON 178 MINUTES 75F HEAT STAGE 1 OFF MOD OUT 100 SERVICE STATUS O...

Страница 12: ...ry default the unit will remain in the occupied mode for 180 minutes This value may be changed from 0 to 255 minutes in programming step 15 FAN SWITCHING The option to allow the occupant to change th...

Страница 13: ...0 90 Occupied heating setpoint must be less than occupied cooling setpoint ADI 20 DegF Unoccupied heating setpoint 40 90 Unoccupied heating setpoint must be less than unoccupied cooling setpoint ADI 2...

Страница 14: ...itch 0 No 1 Yes Enables System Switch button BD 5 Use of discharge air sensor 0 No 1 Yes Always monitored enables discharge air function BD 6 Use of outdoor air sensor 0 No 1 Yes BD 7 Enable smart rec...

Страница 15: ...it 0 OK 1 Below Read only Discharge air function low limit BD 41 DI2 service status 0 OK 1 Check DI2 Read only DI2 Service NOTE 1 The Service status point represents general Check status if this is po...

Страница 16: ...Rev 1000 R 2800 LAURA LANE IMIDDLETON WI 53562 I 800 288 9383 IFAX 608 836 9044 Iwww tcs basys com 16...