Pointmap Table for SZ1017N
NPT
NPA
UNITS
POINT DESCRIPTION
RANGE/VALUE
ADDITIONAL NOTES
ADI
1
#
DI2 control mode
0=Aquastat,
See programming step #39.
1=monitor, 2=service
ADI
2
#
Unocc Analog output action
0=0or4 mA, 1=20 mA
See programming step #26.
2=Modulating
ADI
3
#
Analog output mode
0=heat, 1= cool,
See programming step #23.
2=Aquastat
ADI
4
#
DI3 control mode
0=filter service,
See programming step #41.
1=external override,
2= external timeclock
ADI
5
#
Occupied Fan mode
0=on, 1=cool, 2=auto
"Fan Switch" button on keypad.
ADI
6
#
System mode
0=off,1=auto,2=heat
"System Switch" button on keypad.
3=cool
ADI
7
Day
Internal time clock "day"
0-6, mon to sunday
Day of Week.
ADI
8
Hours
Internal time clock "hours"
0-23
0-12 (AM), 13-23 (PM).
ADI
9
DegF
Setpoint adjust limit from keypad
0-50
Limits keypad adjustment of occupied
heating and cooling setpoints.
ADI
10
DegF
Differential for stage 1
0-50
ADI
11
DegF
Offset for stage 1
0-50
ADI
12
DegF
Differential for stage 2
0-50
ADI
13
DegF
Offset for stage 2
0-50
ADI
14
DegF
Setpoint shift value
0-50
When DI2 is selected "Monitor", this is
number of degrees that the occupied
cooling setpoint is shifted up and the
heating setpoint is shifted down.
ADI
15
DegF
(space) Setpoint offset
0-50
See programming step #28.
ADI
16
DegF
AO Proportional Band
0-50
See programming step #27.
ADI
17
Seconds
Internal time clock "second"
0-59
ADI
18
Minutes
Internal time clock "minute"
0-59
ADI
19
DegF
Occupied heating setpoint
40-90
Occupied heating setpoint must be less
than occupied cooling setpoint.
ADI
20
DegF
Unoccupied heating setpoint
40-90
Unoccupied heating setpoint must be
less
than unoccupied cooling setpoint.
ADI
21
DegF
Occupied cooling setpoint
40-90
ADI
22
DegF
Unoccupied cooling setpoint
40-90
ADI
23
DegF
Room temperature
40-90
Read only.
ADI
24
%
Analog Output
0-100%
Read only.
ADI
25
DegF
Discharge air setpoint
0-150
See programming step #33.
ADI
26
#
Reset ratio
0-150
See programming step #34 (Note 6).
ADI
27
DegF
Discharge air low limit
0-150
Discharge air high limit must be less
than discharge air low limit.
ADI
28
DegF
Discharge air high limit
0-150
ADI
29
DegF
Discharge air temperature
0-150
Read only.
ADI
30
DegF
Outdoor heat lockout temp
-40 to 160
See programming step #37.
ADI
31
DegF
Outdoor cool lockout
-40 to 160
See programming step #36.
ADI
32
DegF
Outdoor air temperature
-40 to 160
See Note 4
ADI
33
Minutes
Override period
0-255
Unoccupied override time allowed.
ADI
34
Seconds
Power on delay time
0-255
Time before control begins on powerup.
ADI
35
Minutes
Remaining override time
0-255
Read Only. Time remaining before the
override period expires.
ADI
36
DegF
Current user setpoint adjust
Min=-50, Max=50
Read Only. + or - amount the occupied
setpoint has been adjusted from actual
settings.
ADI
37
Minutes
Monday Occupied start time
0-1439
There are two occupied and two un-
for schedule A
occupied time periods allowed per day.
ADI
38
Minutes
Monday Occupied end time
0-1439
All times are measured in minutes from
for schedule A
midnight.
R