Pointmap Table for SZ1017N (continued)
NPT
NPA
UNITS
POINT DESCRIPTION
RANGE/VALUE
ADDITIONAL NOTES
ADI
39
Minutes
Monday Occupied start time
0-1439
for schedule B
ADI
40
Minutes
Monday Occupied end time
0-1439
for schedule B
ADI
41
Tuesday
0-1439
ADI
42
Tuesday
0-1439
ADI
43
Tuesday
0-1439
ADI
44
Tuesday
0-1439
ADI
45
Wednesday
0-1439
ADI
46
Wednesday
0-1439
ADI
47
Wednesday
0-1439
ADI
48
Wednesday
0-1439
ADI
49
Thursday
0-1439
ADI
50
Thursday
0-1439
ADI
51
Thursday
0-1439
ADI
52
Thursday
0-1439
ADI
53
Friday
0-1439
ADI
54
Friday
0-1439
ADI
55
Friday
0-1439
ADI
56
Friday
0-1439
ADI
57
Saturday
0-1439
ADI
58
Saturday
0-1439
ADI
59
Saturday
0-1439
ADI
60
Saturday
0-1439
ADI
61
Sunday
0-1439
ADI
62
Sunday
0-1439
ADI
63
Sunday
0-1439
ADI
64
Sunday
0-1439
BD
1
DI1 control mode
0=fan proving,
See programming step #38.
1=Monitor
BD
2
Unocc fan mode
0=cool, 1= auto
Not accessible with "Fan Switch" button.
BD
3
Enable occupied fan switch
0 = No, 1=Yes
Enables "Fan Switch" button.
BD
4
Enable system switch
0 = No, 1=Yes
Enables "System Switch" button.
BD
5
Use of discharge air sensor
0 = No, 1=Yes
Always monitored, enables discharge
air function.
BD
6
Use of outdoor air sensor
0 = No, 1=Yes
BD
7
Enable smart recovery routine
0 = No, 1=Yes
4° per hour setpoint ramp prior to oc-
cupancy forboth heating and cooling.
BD
8
Require access code
0 = No, 1=Yes
Programming access from keypad.
for programming?
BD
9
Require access code
0 = No, 1=Yes
Clock/Schedule access from keypad.
for clock/schedule?
BD
10
Enable stage 1 & 2
0=disable, 1=enable
See programming step #16.
BD
11
Stage 1 & 2 action
0=cool, 1=heat
See programming step #16.
BD
12
Time clock relay output
0=Normally Open
State of relay output during occupied
1=Normally Closed
period.
BD
13
Control mode
0=Proportional
Stages turned on and off using offsets
and differentials only.
1=Prop. + Integral
Stages turned on and off using offsets
and differe a time factor.
BD
14
Control is based on
0=Space
See programming step #32.
1=Discharge
BD
15
Analog output range
0 = 0 - 20 ma,
See programming step #25.
1 = 4 - 20 ma
BD
16
Analog output action
0 = Direct,
See programming step #24.
1 = Reverse
R