Pointmap Table for SZ1017N (continued)

NPT

NPA

UNITS

POINT DESCRIPTION

RANGE/VALUE

ADDITIONAL NOTES

ADI

39

Minutes

Monday Occupied start time

0-1439

for schedule B

ADI

40

Minutes

Monday Occupied end time

0-1439

for schedule B

ADI

41

Tuesday

0-1439

ADI

42

Tuesday

0-1439

ADI

43

Tuesday

0-1439

ADI

44

Tuesday

0-1439

ADI

45

Wednesday

0-1439

ADI

46

Wednesday

0-1439

ADI

47

Wednesday

0-1439

ADI

48

Wednesday

0-1439

ADI

49

Thursday

0-1439

ADI

50

Thursday

0-1439

ADI

51

Thursday

0-1439

ADI

52

Thursday

0-1439

ADI

53

Friday

0-1439

ADI

54

Friday

0-1439

ADI

55

Friday

0-1439

ADI

56

Friday

0-1439

ADI

57

Saturday

0-1439

ADI

58

Saturday

0-1439

ADI

59

Saturday

0-1439

ADI

60

Saturday

0-1439

ADI

61

Sunday

0-1439

ADI

62

Sunday

0-1439

ADI

63

Sunday

0-1439

ADI

64

Sunday

0-1439

BD

1

DI1 control mode

0=fan proving, 

See programming step #38.

1=Monitor

BD

2

Unocc fan mode

0=cool, 1= auto

Not accessible with "Fan Switch" button.

BD

3

Enable occupied fan  switch

0 = No, 1=Yes

Enables "Fan Switch" button.

BD

4

Enable system  switch

0 = No, 1=Yes

Enables "System Switch" button.

BD

5

Use of discharge air sensor

0 = No, 1=Yes

Always monitored, enables discharge
air function.

BD

6

Use of outdoor air sensor

0 = No, 1=Yes

BD

7

Enable smart recovery routine

0 = No, 1=Yes

4° per hour setpoint ramp prior to oc-
cupancy forboth heating and cooling.

BD

8

Require access code

0 = No, 1=Yes

Programming access from keypad.

for programming?

BD

9

Require access code

0 = No, 1=Yes

Clock/Schedule access from keypad.

for clock/schedule?

BD

10

Enable stage 1 & 2

0=disable, 1=enable

See programming step #16.

BD

11

Stage 1 & 2 action

0=cool, 1=heat

See programming step #16.

BD

12

Time clock relay output

0=Normally Open

State of relay output during occupied

1=Normally Closed

period.

BD

13

Control mode

0=Proportional

Stages turned on and off using offsets
and differentials only.

1=Prop. + Integral

Stages turned on and off using offsets
and differe a time factor.

BD

14

Control is based on 

0=Space

See programming step #32.

1=Discharge

BD

15

Analog output range 

0 = 0 - 20 ma,

See programming step #25.

1 = 4 - 20 ma

BD

16

Analog output action

0 = Direct,

See programming step #24.

1 = Reverse

R

2800 LAURA LANE 

I

MIDDLETON, WI 53562 

I

(800) 288-9383 

I

FAX (608) 836-9044 

I

www.tcs-basys.com

14

Содержание SZ1017N

Страница 1: ...e locked out or limited with the use of an access code Fahrenheit or Celsius temperature display Product Manual Contents Description 1 Features 1 Mounting 1 N2 Bus Connections 2 Wiring 2 Setup 3 Progr...

Страница 2: ...ughout because these are half wave recti fied devices SZ1017N thermostats require 8 VA 24 VAC When the SZ1017N is used as a stand alone thermostat with out communications the unit transformer may be u...

Страница 3: ...e two set screws located at the top right and the left side to prevent tampering Setup Note If using remote sensor s the calibration may need to be adjusted See Checkout and Troubleshooting section SE...

Страница 4: ...S TEMPS SHOWN IN 4 FAHRENHEIT program setup Main Monitoring Screen Press the pro gram setup button to access the following screens Access Code Entry Screen Will appear if access code is required for p...

Страница 5: ...pear if stage outputs 1 and 2 are disabled Stage 2 Differential Screen Enter a differential value for stage 2 This screen does not appear if stage out puts 1 and 2 are disabled Control Mode Screen Ent...

Страница 6: ...by 1 degree for cooling Outdoor Air Sensor Screen Choose whether or not you are using an outdoor air sensor function To monitor only select no See setup instructions for dip switch settings which must...

Страница 7: ...l be maintained and the fan will operate according to its unoc cupied setting The occupied LED will be lit when the unit is operating in the occupied mode The occupied schedule may be set utilizing th...

Страница 8: ...ns or dis charge air reset function See Discharge Air Reset section for further programming options If NO is chosen the dis charge air is still monitored When the function is enabled a LOW LIMIT and H...

Страница 9: ...ences to protect equipment The fan has a minimum on and off time of 30 seconds When the fan is in AUTO or COOL mode it will come on 30 seconds before the heating or cooling stages are allowed to seque...

Страница 10: ...roubleshooting section TROUBLESHOOTING No Display Check for 24 VAC on terminals 24 and 24 Check the cable connecting the cover to the base for a good connec tion Fan Does Not Come On The fan is on whe...

Страница 11: ...a PC Additional monitoring is available by continually pressing the service key MON 72F 12 00 AM DISCHARGE AIR 55F OUTDOOR AIR OVERRIDE ON 178 MINUTES 75F HEAT STAGE 1 OFF MOD OUT 100 SERVICE STATUS O...

Страница 12: ...ry default the unit will remain in the occupied mode for 180 minutes This value may be changed from 0 to 255 minutes in programming step 15 FAN SWITCHING The option to allow the occupant to change th...

Страница 13: ...0 90 Occupied heating setpoint must be less than occupied cooling setpoint ADI 20 DegF Unoccupied heating setpoint 40 90 Unoccupied heating setpoint must be less than unoccupied cooling setpoint ADI 2...

Страница 14: ...itch 0 No 1 Yes Enables System Switch button BD 5 Use of discharge air sensor 0 No 1 Yes Always monitored enables discharge air function BD 6 Use of outdoor air sensor 0 No 1 Yes BD 7 Enable smart rec...

Страница 15: ...it 0 OK 1 Below Read only Discharge air function low limit BD 41 DI2 service status 0 OK 1 Check DI2 Read only DI2 Service NOTE 1 The Service status point represents general Check status if this is po...

Страница 16: ...Rev 1000 R 2800 LAURA LANE IMIDDLETON WI 53562 I 800 288 9383 IFAX 608 836 9044 Iwww tcs basys com 16...

Отзывы: