90
Operation description
Required tool
Approximate timing
Operation check
Turn on the CM auxiliary power supply then check
the following:
-
The “Power“ LED must light up immediately;
-
The “Ready“ LED must light up continuously
within 15 s after switching on;
-
The “Malfunction“ LED must not light up;
-
The “Ready“ relay contact must close within
15 s.;
-
The “Malfunction or Loss of auxiliary
suppl
y“ relay contact must change its state
1)
;
-
The “ISM main contact position” relay contact
must not change its state;
-
ISM main contacts must not change their
state (ISM shall remain open).
Visual check, no tool is required
1 minute
Apply close command to the CM then check the
following:
-
The “Power“ LED must light continuously;
-
The “Ready“ LED must light continuously;
-
The “Malfunction“ LED must not light up;
-
The “Ready“ relay contact must not change
its state;
-
The “Malfunction or Loss of auxiliary
supply“ relay contact must not change its
state;
-
The “ISM main contact position” relay contact
must change its state;
-
ISM main contacts must change their state
(ISM shall be closed).
Visual check, no tool is required
1 minute
Apply trip command to the CM then check the
following:
-
The “Power“ LED must light continuously;
-
The “Ready“ LED must light continuously;
-
The “Malfunction“ LED must not light up;
-
The “Ready“ relay contact must not change
its state;
-
The “Malfunction of Loss of auxiliary
supply“ relay contact must not change its
state;
-
The “ISM main contact position” relay
contact must change its state;
-
ISM main contacts must change their state
(ISM shall be open).
Visual check, no tool is required
1 minute
1) „As earlier, after CM power supply disconnection this relay indicated the CM state: “Power supply voltage is absent for more than 1.5 seconds“
Содержание VCB Series
Страница 1: ...COMPATIBLE SERIES USER GUIDE...
Страница 2: ......
Страница 4: ......
Страница 5: ...1 Product description...
Страница 13: ...13 2 Nameplates and seals...
Страница 18: ...18 3 Product handling...
Страница 37: ...4 Installation...
Страница 51: ...51 Figure 86 ISM15_MD insulation clearances 75 kV BIL Figure 87 ISM15_MD insulation clearances 95 kV BIL...
Страница 87: ......
Страница 88: ...5 Commissioning...
Страница 94: ...94 Figure 155 The connection points of the contact resistance meter...
Страница 95: ......
Страница 96: ...6 Operation...
Страница 100: ...7 Maintenance and troubleshooting...
Страница 105: ......
Страница 106: ...8 Disposal...
Страница 109: ...109 Appendix 2 Overall Drawings...
Страница 110: ...110 Dimensions of Indoor Switching Modules ISM15_LD_1 67 PCD 150 mm Weight 34 kg ISM15_LD_1 55 PCD 210 mm Weight 36 kg...
Страница 111: ...111 ISM15_LD_1 80 two lower terminals continuous busbar PCD 150 mm Weight 36 kg ISM15_LD_1 90 PCD 180 mm Weight 36 kg...
Страница 112: ...112 ISM15_LD_3 Weight 13 kg ISM15_LD_6 PCD 133 mm Weight 55 kg...
Страница 113: ...113 ISM15_LD_8 PCD 210 mm Weight 26 kg...
Страница 114: ...114 ISM15_MD_1 150_L PCD 150 mm Weight 33 kg ISM15_MD_1 210_L PCD 210 mm Weight 35 kg...
Страница 115: ...115 ISM15_MD_3 Weight 13 kg ISM15_Shell_2 150_L PCD 150 mm Weight 51 kg...
Страница 120: ...120 ISM15_HD_1 275 PCD 275 mm Weight 72 kg ISM25_LD_1 210_Par2 PCD 210 mm Weight 36 kg...
Страница 123: ...123 ISM25_LD_2 2 PCD 150 mm Weight 37 kg ISM25_LD_3 Weight 14 kg...
Страница 124: ...124 ISM25_LD_3 with CBkit_Ins_3 installed Weight 14 5 kg upper busbar shown for reference and is not supplied...
Страница 125: ...125 Dimensions of Control Module CM_16_1 Par1_Par2_Par3_Par4_Par5 Weight 1 kg...
Страница 127: ...127 Dimensions of Interlocking Kits CBkit_Interlock_1 CBkit_Interlock_3...
Страница 128: ...128 CBkit_Interlock_4 CBkit_Interlock_5...
Страница 129: ...Appendix 3 Secondary Schemes...
Страница 130: ...130...
Страница 131: ...131...
Страница 132: ...132...
Страница 133: ...133...
Страница 134: ...134...
Страница 135: ...135...
Страница 136: ...136...
Страница 137: ...137...
Страница 138: ...138...
Страница 139: ...139...
Страница 140: ...140...
Страница 142: ...Bartlett...