102
Operation description
Required tool
Approximate timing
Primary circuits contact resistance check
1)
ISM shall be closed before the test, there
should not be any external circuits
connected to ISM main terminals that
provide parallel circuit with the ISM main
circuits otherwise tests will be invalid.
Visual check, no tool is required
1 minute
Test equipment shall be connected to ISM
main circuits terminals according to Figure
155 in order exclude any additional
contact resistance and to decrease
measurement error. Main contact
resistance shall be measured by
appropriate equipment at test current not
less than 50 A.
Resistance measurement test
equipment with test current not less
than 50 A
10 minutes
Measured values for VCB15_LD,
VCB25_LD and VCB15_MD must not
exceed limits specified in Table 1
Measured values for VCB15_Shell and
VCB15_HD must not exceed limits
specified in Table 1 increased on 2
μOhm.
These 2
μOhm are added by contact
resistance between ISM terminals and
additional burs attached to them (see in
the Figure 155)
Visual check, no tool is required
-
1)
If the Module has contact resistance which exceeds the specified limit but is less than twice this limit, continuation of use is possible, if actual
continuous current does not exceed the following value:
where:
Ia, Ra
— actual current and corresponding contact resistance,
Ir, Rr
— rated values (Table 1).
If the contact resistance is at least twice as high as the specified limit, the ISM must be replaced.
Additionally switchboards can be subjected to extra tests that are specified in corresponding documentation for the switchboards.
Содержание VCB Series
Страница 1: ...COMPATIBLE SERIES USER GUIDE...
Страница 2: ......
Страница 4: ......
Страница 5: ...1 Product description...
Страница 13: ...13 2 Nameplates and seals...
Страница 18: ...18 3 Product handling...
Страница 37: ...4 Installation...
Страница 51: ...51 Figure 86 ISM15_MD insulation clearances 75 kV BIL Figure 87 ISM15_MD insulation clearances 95 kV BIL...
Страница 87: ......
Страница 88: ...5 Commissioning...
Страница 94: ...94 Figure 155 The connection points of the contact resistance meter...
Страница 95: ......
Страница 96: ...6 Operation...
Страница 100: ...7 Maintenance and troubleshooting...
Страница 105: ......
Страница 106: ...8 Disposal...
Страница 109: ...109 Appendix 2 Overall Drawings...
Страница 110: ...110 Dimensions of Indoor Switching Modules ISM15_LD_1 67 PCD 150 mm Weight 34 kg ISM15_LD_1 55 PCD 210 mm Weight 36 kg...
Страница 111: ...111 ISM15_LD_1 80 two lower terminals continuous busbar PCD 150 mm Weight 36 kg ISM15_LD_1 90 PCD 180 mm Weight 36 kg...
Страница 112: ...112 ISM15_LD_3 Weight 13 kg ISM15_LD_6 PCD 133 mm Weight 55 kg...
Страница 113: ...113 ISM15_LD_8 PCD 210 mm Weight 26 kg...
Страница 114: ...114 ISM15_MD_1 150_L PCD 150 mm Weight 33 kg ISM15_MD_1 210_L PCD 210 mm Weight 35 kg...
Страница 115: ...115 ISM15_MD_3 Weight 13 kg ISM15_Shell_2 150_L PCD 150 mm Weight 51 kg...
Страница 120: ...120 ISM15_HD_1 275 PCD 275 mm Weight 72 kg ISM25_LD_1 210_Par2 PCD 210 mm Weight 36 kg...
Страница 123: ...123 ISM25_LD_2 2 PCD 150 mm Weight 37 kg ISM25_LD_3 Weight 14 kg...
Страница 124: ...124 ISM25_LD_3 with CBkit_Ins_3 installed Weight 14 5 kg upper busbar shown for reference and is not supplied...
Страница 125: ...125 Dimensions of Control Module CM_16_1 Par1_Par2_Par3_Par4_Par5 Weight 1 kg...
Страница 127: ...127 Dimensions of Interlocking Kits CBkit_Interlock_1 CBkit_Interlock_3...
Страница 128: ...128 CBkit_Interlock_4 CBkit_Interlock_5...
Страница 129: ...Appendix 3 Secondary Schemes...
Страница 130: ...130...
Страница 131: ...131...
Страница 132: ...132...
Страница 133: ...133...
Страница 134: ...134...
Страница 135: ...135...
Страница 136: ...136...
Страница 137: ...137...
Страница 138: ...138...
Страница 139: ...139...
Страница 140: ...140...
Страница 142: ...Bartlett...