103
7.2 Secondary circuits
The CM is inherently maintenance free. However when maintenance is carried out on the switchgear then
commissioning tests should be repeated. It is also recommended to conduct regular visual checks of the
module housing and insulation of the wires connected to the CM. Test results should be treated as given in
the Table 19.
Table 19 - List of tests and check-ups of CM during maintenance
Operation description
Required tool
Approximate timing
Auxiliary circuits insulation check
Connect all points of the secondary circuits
with a shorting wire. ISM coil connection
wires must be disconnected from connector
X3 of the CM before the test.
Wires
5 minutes
Connect the shorting wire to the high
potential lead of the high voltage tester and
ground the circuit breaker housing. Start
with zero volts, gradually increase the test
voltage to 1500 V RMS, 50 or 60 Hz.
Maintain test voltage for one minute.
Power frequency withstand voltage test set
3 minutes
If no disruptive discharge occurs, the
secondary circuits insulation level is
satisfactory.
Power frequency withstand voltage test set
-
Disconnect the shorting wire and reattach
the wires to connector X3 of the CM.
Visual check, no tool is required
5 minutes
Содержание VCB Series
Страница 1: ...COMPATIBLE SERIES USER GUIDE...
Страница 2: ......
Страница 4: ......
Страница 5: ...1 Product description...
Страница 13: ...13 2 Nameplates and seals...
Страница 18: ...18 3 Product handling...
Страница 37: ...4 Installation...
Страница 51: ...51 Figure 86 ISM15_MD insulation clearances 75 kV BIL Figure 87 ISM15_MD insulation clearances 95 kV BIL...
Страница 87: ......
Страница 88: ...5 Commissioning...
Страница 94: ...94 Figure 155 The connection points of the contact resistance meter...
Страница 95: ......
Страница 96: ...6 Operation...
Страница 100: ...7 Maintenance and troubleshooting...
Страница 105: ......
Страница 106: ...8 Disposal...
Страница 109: ...109 Appendix 2 Overall Drawings...
Страница 110: ...110 Dimensions of Indoor Switching Modules ISM15_LD_1 67 PCD 150 mm Weight 34 kg ISM15_LD_1 55 PCD 210 mm Weight 36 kg...
Страница 111: ...111 ISM15_LD_1 80 two lower terminals continuous busbar PCD 150 mm Weight 36 kg ISM15_LD_1 90 PCD 180 mm Weight 36 kg...
Страница 112: ...112 ISM15_LD_3 Weight 13 kg ISM15_LD_6 PCD 133 mm Weight 55 kg...
Страница 113: ...113 ISM15_LD_8 PCD 210 mm Weight 26 kg...
Страница 114: ...114 ISM15_MD_1 150_L PCD 150 mm Weight 33 kg ISM15_MD_1 210_L PCD 210 mm Weight 35 kg...
Страница 115: ...115 ISM15_MD_3 Weight 13 kg ISM15_Shell_2 150_L PCD 150 mm Weight 51 kg...
Страница 120: ...120 ISM15_HD_1 275 PCD 275 mm Weight 72 kg ISM25_LD_1 210_Par2 PCD 210 mm Weight 36 kg...
Страница 123: ...123 ISM25_LD_2 2 PCD 150 mm Weight 37 kg ISM25_LD_3 Weight 14 kg...
Страница 124: ...124 ISM25_LD_3 with CBkit_Ins_3 installed Weight 14 5 kg upper busbar shown for reference and is not supplied...
Страница 125: ...125 Dimensions of Control Module CM_16_1 Par1_Par2_Par3_Par4_Par5 Weight 1 kg...
Страница 127: ...127 Dimensions of Interlocking Kits CBkit_Interlock_1 CBkit_Interlock_3...
Страница 128: ...128 CBkit_Interlock_4 CBkit_Interlock_5...
Страница 129: ...Appendix 3 Secondary Schemes...
Страница 130: ...130...
Страница 131: ...131...
Страница 132: ...132...
Страница 133: ...133...
Страница 134: ...134...
Страница 135: ...135...
Страница 136: ...136...
Страница 137: ...137...
Страница 138: ...138...
Страница 139: ...139...
Страница 140: ...140...
Страница 142: ...Bartlett...