
92
Operation description
Required tool
Approximate timing
Primary circuits insulation check
1)
Observe safety precautions listed in the danger
and warning advisories. Construct proper barriers
and warning light systems
Equipment to provide safety in the test
area
10 minutes
Ground each pole of ISM that is not under
test
2)
Wires
2 minutes
Apply slowly rising 100%
3)
of test voltage
4)
(50 or
60 Hz) across each pole for one minute
5)
. (ISM is
open)
Power frequency withstand voltage test
set
2 minutes
If the pole sustains the test voltage for that period,
its vacuum integrity has been verifed
6)
Power frequency withstand voltage test
set
-
Repeat actions above to check each pole of ISM
Power frequency withstand voltage test
set, wires
8 minutes
Close the ISM. Ground each pole of ISM that is
not under test
2)
Wires
1 minute
Apply slowly rising 100%
3)
of test voltage
3)
(50 or
60 Hz) between a primary conductor of the pole
and ground for one minute, repeat test for each
pole of ISM
Power frequency withstand voltage test
set
12 minutes
If no disruptive discharge occurs, the insulation
system is satisfactory
Power frequency withstand voltage test
set
-
After the test, ground all main circuit terminals to
dissipate any static charge
Wires
2 minutes
Auxiliary circuits insulation check
Connect all points of the secondary circuits with a
shorting wire. ISM coil connection wires must be
disconnected from connector X3 of CM before the
test
Wires
5 minutes
Connect the shorting wire to the high potential
lead of the high voltage tester and ground the
circuit breaker housing. Starting with zero volts,
gradually increase the test voltage to 1500 V
RMS, 50 or 60 Hz. Maintain test voltage for one
minute
Power frequency withstand voltage test
set
3 minutes
If no disruptive discharge occurs, the secondary
circuits insulation level is satisfactory
Power frequency withstand voltage test
set
-
Disconnect the shorting wire and re-attach the
wires to connector X3 of CM
Visual check, no tool is required
5 minutes
1)
This test includes not only the vacuum interrupter test, but also the other insulation components tested in parallel with the interrupter. These include
the standoff insulators and the insulated drive links, as well as the insulating (tension) struts between the upper and lower vacuum interrupter
supports. If these insulation components are contaminated or defective, the test voltage will not be sustained. If so, clean or replace the affected
components, and retest.
2)
Three phase ISM should be tested phase by phase only. Therefore poles not under the test should be grounded.
3)
For test of separate VCB - 100% level of test voltage, for test of Switchgear with installed VCB - 80% level of test voltage according to
IEC 62271-200.
4)
Rated test voltage levels (Ud) are given in Table 1.
5)
To apply test voltage single-core short cables should be used. Application of high voltage coaxial cables is strictly prohibited. To coordinate the
surge impedance between the test set and ISM extra resistor as shown in the Figure 154 shall be used.
6)
During testing of vacuum interrupter, self-fading restrikes may appear. In case of restrikes, reduce the voltage slightly until the restrikes disappear
(for 10-15 seconds) and then increase again.
Содержание VCB Series
Страница 1: ...COMPATIBLE SERIES USER GUIDE...
Страница 2: ......
Страница 4: ......
Страница 5: ...1 Product description...
Страница 13: ...13 2 Nameplates and seals...
Страница 18: ...18 3 Product handling...
Страница 37: ...4 Installation...
Страница 51: ...51 Figure 86 ISM15_MD insulation clearances 75 kV BIL Figure 87 ISM15_MD insulation clearances 95 kV BIL...
Страница 87: ......
Страница 88: ...5 Commissioning...
Страница 94: ...94 Figure 155 The connection points of the contact resistance meter...
Страница 95: ......
Страница 96: ...6 Operation...
Страница 100: ...7 Maintenance and troubleshooting...
Страница 105: ......
Страница 106: ...8 Disposal...
Страница 109: ...109 Appendix 2 Overall Drawings...
Страница 110: ...110 Dimensions of Indoor Switching Modules ISM15_LD_1 67 PCD 150 mm Weight 34 kg ISM15_LD_1 55 PCD 210 mm Weight 36 kg...
Страница 111: ...111 ISM15_LD_1 80 two lower terminals continuous busbar PCD 150 mm Weight 36 kg ISM15_LD_1 90 PCD 180 mm Weight 36 kg...
Страница 112: ...112 ISM15_LD_3 Weight 13 kg ISM15_LD_6 PCD 133 mm Weight 55 kg...
Страница 113: ...113 ISM15_LD_8 PCD 210 mm Weight 26 kg...
Страница 114: ...114 ISM15_MD_1 150_L PCD 150 mm Weight 33 kg ISM15_MD_1 210_L PCD 210 mm Weight 35 kg...
Страница 115: ...115 ISM15_MD_3 Weight 13 kg ISM15_Shell_2 150_L PCD 150 mm Weight 51 kg...
Страница 120: ...120 ISM15_HD_1 275 PCD 275 mm Weight 72 kg ISM25_LD_1 210_Par2 PCD 210 mm Weight 36 kg...
Страница 123: ...123 ISM25_LD_2 2 PCD 150 mm Weight 37 kg ISM25_LD_3 Weight 14 kg...
Страница 124: ...124 ISM25_LD_3 with CBkit_Ins_3 installed Weight 14 5 kg upper busbar shown for reference and is not supplied...
Страница 125: ...125 Dimensions of Control Module CM_16_1 Par1_Par2_Par3_Par4_Par5 Weight 1 kg...
Страница 127: ...127 Dimensions of Interlocking Kits CBkit_Interlock_1 CBkit_Interlock_3...
Страница 128: ...128 CBkit_Interlock_4 CBkit_Interlock_5...
Страница 129: ...Appendix 3 Secondary Schemes...
Страница 130: ...130...
Страница 131: ...131...
Страница 132: ...132...
Страница 133: ...133...
Страница 134: ...134...
Страница 135: ...135...
Страница 136: ...136...
Страница 137: ...137...
Страница 138: ...138...
Страница 139: ...139...
Страница 140: ...140...
Страница 142: ...Bartlett...