YE-REMAUX Remote Auxiliary Interface Box
The Remote Auxiliary Interface Box allows a user to utilize the AUX1 and AUX2 buttons located on the monitor operator
station or any remote operator station. The Interface Box is equipped with two relays that can operate lights, interface to a
valve controller or in some cases operate a valve directly, etc. The contact rating of the relay is 16 amps @ 30VDC for
resistive loads and 8 amps @ 30VDC for inductive loads.
The installer will need to mount the interface box and connect the cable to power and the communication link of the
monitor.
1.0 ENCLOSURE MOUNTING
Select proper enclosure location. Enclosure is designed to be surface mounted and the size is 5” x 3 1/8” (127 x 80mm).
Height of enclosure is 2 3/8” (60mm). Refer to Figure 1.0.1 for mounting hole dimensions.
Figure 1.0.1
Hole Dimensions
1.1 ELECTRICAL WIRING
The interface box needs to be connected to +12/24VDC (red) and ground (black). The blue & white wires from the
interface box cable need to be connected to the blue & white wires from the monitor. A terminal box or a high quality,
protected splice can be used to make these connections. See section 5.0 of installation manuals for further wiring
information.
Each relay has one Form-C contact (common, normally open, normally closed) that can be used.
MOUNT ENCLOSURE
WITH (2) 1/4-20 FASTENERS
TIGHTEN SECURELY.
4.45
2.05
The Interface Box provides no overload protection for the device it is controlling. Failure
to provide overload protection will damage relay contacts, which will disable device
being controlled.
WARNING