T-K3 Service Manual
Ver. 1.05
11
CONFIDENTIAL
9. Operational flow chart
Power supply ON
Opeartion SW ON
OPEN FAV BV
Pre-check
NORMAL?
OPEN the tap
Flow Sensor
Above 0.5GPM?
FM speed
(Below
1,000rpm?)
Start FM
Pseudo-flame
Below
DC0.15ƒÊ A?
Iginiter ON
Hi-limit
Normal?
OHCF
Normal?
MV ON
SV1 ON
GPV ON
Detect Flame
Above
DC1.0uA?
Burning lamp ON
Iginiter OFF
Proportional control
Change over
point?
SV2 SV3 ON
Above water
heat capability?
FAV OPEN
Safety devise
work?
FAV close
SV2 SV3 OFF
Miss select
gas type
InTH failure
PCB failure
SV circuit failure
031 blink
321 blink
701 blink
511 blink
611 blink
Stop FM
721 blink
Peseudo-flame
Igniter OFF
Retry ignite
Success?
OuTH OPEN
or SH ORT
A bnormal
F M Speed
MV OFF
SV1 OFF
GPV OFF
SV1, SV2, SV3 OFF
STOP FM
CLOSE the tap
Flow sensor OFF
Remove cause
Opeartion lamp OFF
OPEARTION OFF
YES
NO
YES
NO
NO
YES
YES
NO
(20sec later)
YES
NO
NO
YES
YES
NO
YES
NO
(5sec later)
(3sec later)
YES
YES
NO
YES
NO
(20sec later)
YES
NO
NO
NO
‡F
YES
FAV ; Flow Adjustment Valve
B V ; Bypass Valve
F M ; Fan Motor
OHCF; Over Heat Cut-off Fuse
M V ; Main gas Valve
SV1 ; Solenoid Valve 1
SV2 ; Solenoid Valve 2
SV3 ; Solenoid Valve 3
GPV ; Gas Proportional Valve
InTH; Inlet thermistor
OuTH; Outlet thermistor
MiTH; Mixing thermistor
PCB ; Print Circuit board
(Computer board)
AFR ; Air Fuel Ratio
FM speed
(Above
1,000rpm?)
Above
Max flow rate
ristriction?
111 blink
121 blink
6 11 blink
311 blink
OuTH failure
311 blink
MiTH failure
331 blink
Flame rod
failure
Melt OHCF
Above 363 ‹ F
AFR rod failure
Abnorm al
AFR
121 blink
121 blin k
991 blink
391 blink
BV action
32 1 blink
InT H OPEN
or SHORT
331 blink
MiTH OPE N
or SHORT