18.10 3 wires proportional motor valve control
z
Available
Models
:
FY900 / PFY900
,
FY700 / PFY700
FY800 / PFY800
,
FY600 / PFY600
FY400 / PFY400
,
FY100 / PFY100
FY101 / PFY101
z
Data
Change
:
OUTY=3
CYT1=1 ~ 100sec.
(Manufacturing default setting “5” seconds.)
RUCY=5 ~ 200 seconds.
※
After change “RUCY” the controller must be reset
1. CYT1 is the cycle time of Open / Close
2. RUCY is the 0 ~ 100% running time of motor valve
MOTOR VALVE
CONTROLLER
CLOSE
OPEN
COM
OPEN
CLOSE
COM
OUT1
Relay
OUT2
Relay
R
S