background image

9 of 12 

Before adjusting the dial settings, read through the sequence of operation to ensure that you understand how the control operates. 

STEP FOUR

 

Mixing Starting Temperature (MIX Start)

 

The MIX Start setting is the starting supply water temperature of the reset ratio, and can be adjusted from 35 to 150

°

F (2 to 66

°

C). 

This setting is typically set to the desired building temperature. In applications where fan coils are used, the MIX Start may need to 
be set higher to prevent cold drafts during mild outdoor conditions. If the building feels cool during mild outdoor conditions, the MIX 
Start setting should be increased. 

Outdoor Starting Temperature (OUTDR Start)

 

The OUTDR Start setting is the outdoor temperature at which the mixing starting temperature is supplied. The adjustment range is 
from 35 to 85 

°

F (2 to 29

°

C). This setting is typically set to the desired building temperature. 

Mixing Design Temperature (MIX DSGN)

 

The MIX DSGN setting is the water temperature required to satisfy the building heat loss during the coldest outdoor temperature. This 
adjustment is typically dependent on the type of heating terminal used. The following are suggested settings for different terminal units: 

• Inslab Radiant  .....................  100 to 140

°

F (38 to 60

°

C) 

• Radiant Baseboard  .................  130 to 160

°

F (54 to 71

°

C) 

• Staple-up Radiant 

..........  130 to 160

°

F (54 to 71

°

C) 

• Convective Baseboard 

.......  160 to 190

°

F (71 to 88

°

C) 

• Radiators  ............................  140 to 160

°

F (60 to 71

°

C) 

• Fan Coil 

.............................. 180 

to 200

°

F (82 to 93

°

C) 

Outdoor Design Temperature (OUTDR DSGN)

 

The OUTDR DSGN setting is the outdoor temperature used in the heat loss calculation. It is set to the typical coldest outdoor 
temperature. 

Mixing Maximum Temperature (MIX MAX)

 

The PC705-2 prevents the mixed supply water temperature from rising above the MIX MAX setting. The adjustment range is from 
80 to 225

°

F (27 to 107

°

C). The MIX MAX should be set to the maximum temperature allowed in the system loop. There are many 

factors which may limit the allowable supply water temperature in a radiant floor heating slab; a few are provided below. 
• Nowhere in the concrete should the temperature be maintained above 170

°

F (77

°

C). 

• The surface temperature of a radiant floor heating slab should normally not exceed 85

°

F (29

°

C). The slab surface temperature is 

  affected by the slab thermal resistance, the heating load, and the supply water temperature to the slab. 

Boiler Minimum Supply Temperature (BOIL MIN)

 

Most boilers require a minimum operating temperature to prevent corrosion from flue gas condensation. The minimum boiler setting 
should be programmed to the lowest supply water temperature at which the boiler can operate without causing the boiler flue gases 
to condense. Consult the boiler manufacturer for recommended minimum boiler supply temperatures. Some typical settings are as 
follows: 

• Steel fire tube boiler  …..........  140 to 160

°

F (60 to 71

°

C) 

• Condensing boiler  .................  Off 

• Cast iron boiler  …..................  135 to 160

°

F (57 to 71

°

C) 

• Electric boiler  ........................  Off 

• Copper tube boiler  ….............  125 to 150

°

F (52 to 66

°

C) 

Note: This setting is only available if a boiler sensor is connected to the PC705-2. 

Warm Weather Shut Down (WWSD)

 

The WWSD can be adjusted from 35 to 100

°

F (2 to 38

°

C). The system will be shut down when the outdoor temperature is warmer 

than this setting. 

Settings

 

Control Adjustments

 

Mixing Start: 

Outdoor Start: 

Mixing Design: 

Outdoor Design: 

Mixing Maximum: 

Boiler Minimum: 

WWSD: 

System Pump

 

The PC705-2 has an internal relay rated for 5 Amps to operate a system pump. Connect the  black wire from the back of the control 
to the live (L) side of the 120 V (ac) power source. Connect one of the wires from the system pump to the red wire from the back 
of the control. The other wire on the system pump must be connected to the neutral (N) side of the 120 V (ac) power supply. Connect 
the green wire on the back of the control to ground. 

Содержание PC705-2

Страница 1: ...ng system the heat supplied to the building must equal the heat lost by the building The heat supplied to a building is proportional to the temperature of the water and the surface area of the heating element A small surface area such as baseboard radiators requires a higher water temperature than a larger surface area such as radiant floors The heat lost from a building is dependent on the outdoo...

Страница 2: ...up the flue and reduced boiler jacket losses Differential An on off boiler must be operated with a differential in order to prevent short cycling When the supply water temperature drops below the bottom rail of the differential the boiler is turned on The boiler is then kept on until the supply water temperature rises above the top rail of the differential If the differential is too wide there can...

Страница 3: ...hen all zones are turned on If one of these variables is unknown use Equation 1 or 2 to calculate the other variable 3 Compute Tb Ts Look up the flow ratios on Figure 2 4 The design injection flow rate for direct injection is calculated from Equation 3 If the injection flow rate is greater than 45 US GPM it may be necessary to use a 4 way mixing valve instead of a variable speed injection system 5...

Страница 4: ...the injection pump SYSTEM PUMP OPERATION ThePC705 2hasaninternalsystempumpcontact ThiscontactturnsonwhenthePC705 2hasamixingdemandandisnotinaWWSD The system pump as well as the boiler pump may be controlled by this relay By providing proper flow in the boiler loop the boiler temperature can be accurately controlled based on the mixing load Equation1 System Flow Rate US GPM Design Heating Load Btu ...

Страница 5: ... push the front cover onto the enclosure until it snaps into place The variable speed injection pump and system pump wiring terminates in the electrical box All other electri calwiringterminatesinthetwowiringchambersonthe control The wiring is roughed in to the electrical box prior to installation of the control BOILEROPERATION Boiler Sensor Installed WhilethePC705 2hasamixingdemand theboilersuppl...

Страница 6: ...T T Zone 4 Zone 3 Zone 2 Zone 1 END SWITCH A Zone 4 Zone 3 Zone 2 Zone 1 Taco Zone Control ZVC404 EXP END SWITCH B T Boiler Pump Injection Pump Boiler Pump System Pump Injection Pump 120 V ac Outdoor Sensor Boiler Sensor Supply Sensor Priority Zone Switch set to ON DHW Tank T T T T POWER Zone 4 Zone 3 Zone 2 Zone 1 INPUT END SWITCH ZR X X ZC Zone 4 Zone 3 Zone 2 Zone 1 Taco Zone Control SR 506 EXP...

Страница 7: ...3 Zone 2 Zone 1 Taco Zone Control SR 503 EXP Boiler Pump Boiler Pump Injection Pump Injection Pump DHW Tank POWER Zone 3 Zone 2 Zone 1 INPUT END SWITCH ZR X X ZC Zone 3 Zone 2 Zone 1 Taco Zone Control SR 503 EXP A Expansion Switch set to Master Mode Switch set to Normal Expansion Switch set to Slave Mode Switch set to Normal PC 705 2 PC 702 1 PC 700 2 DHW Tank POWER Zone 3 Zone 2 Zone 1 INPUT END ...

Страница 8: ...on the Taco Zone Control Ensure the Mode switch on the Zone Control is set to Reset if boiler control is desired orNormalifboilerenableisdesired refertotheBoilerOperationsection Wiring the Sensors Do not apply power to these terminals as this will damage the control OutdoorSensor Connect the two wires from the Outdoor Sensor directly to the Com Out 1 and 3 terminals The Outdoor Sensor measures the...

Страница 9: ...F 27 to 107 C The MIX MAX should be set to the maximum temperature allowed in the system loop There are many factors which may limit the allowable supply water temperature in a radiant floor heating slab a few are provided below Nowhere in the concrete should the temperature be maintained above 170 F 77 C The surface temperature of a radiant floor heating slab should normally not exceed 85 F 29 C ...

Страница 10: ...mperature Press and release the Item button until the MIX TARGET elements are displayed Boiler Temperature Press and release the Item button until the BOIL element is displayed To view all control settings the Item button may be pressed and held while in the View Menu The contol will then scroll through all the adjustable items MIX Start Use the and buttons to set the desired mixing starting tempe...

Страница 11: ...by 5 F 3 C per day If the outdoor temperature is near the WWSD temperature and the rooms are cold increase the MIX Start setting Testing the Sensors A good quality test meter capable of measuring up to 5 000 kΩ 1 kΩ 1000 Ω is required to measure the sensor resistance In addition to this the actual temperature must be measured with either a good quality digital thermometer or if a thermometer is no...

Страница 12: ...aged to try to correct the interference by reorienting or relocating the receiving antenna relocating the receiver with respect to this control and or connecting the control to a different circuit from that to which the receiver is connected Do It Once Do It Right TACO INC 1160 Cranston Street Cranston RI 02920 Telephone 401 942 8000 Fax 401 942 2360 TACO Canada Ltd 6180 Ordan Drive Mississauga On...

Отзывы: