STEP FIVE

The main control functions on the PC705-2 can be tested by pressing and holding the UP button. While the UP button is pressed, the 

boiler and the system pump are turned on, and the variable speed injection pump is turned to 100% of its output speed. Once the UP 

button is released, the control returns to normal operation.

STEP SIX

As in any troubleshooting procedure, it is important to isolate a problem as much as possible before proceeding. The Error Messages 

greatly simplify troubleshooting of the PC705-2. When the control displays an error message, identify the fault from the look-up table 

on page 12 and follow standard testing procedures to confirm the problem. If you suspect a wiring fault, return to step three and 

carefully check all external wiring and wiring connections.

Sensor and Internal Faults

• If an outdoor sensor fault occurs, the PC705-2 will assume a fixed outdoor temperature of 32°F (0°C) and will target the appropriate 

supply water temperature. An error message is displayed.

• If a supply sensor fault occurs, and a boiler sensor is installed, the PC705-2 operates the variable speed at an output of 15% and 

displays an error message. If a supply sensor fault occurs, and a boiler sensor is not installed, the PC705-2 operates the variable 

speed at an output of 30% and displays an error message.

• If a boiler sensor fault occurs, the PC705-2 operates the boiler as if the sensor was not installed and displays an error message. 

If  the sensor was deliberately removed, remove power from the control to clear the error message.

• If an EEPROM fault occurs, the PC705-2 stops operation until all the settings are verified. An error message is displayed.

Adjustment of Settings

• If the outdoor temperature is cold and the rooms are cold, increase the MIX DSGN setting by 5°F (3°C) per day.

• If the outdoor temperature is near the WWSD temperature and the rooms are cold, increase the MIX Start setting.

Testing the Sensors

A good quality test meter capable of measuring up to 5,000 kΩ  (1 kΩ = 1000 Ω) is 

required to measure the sensor resistance. In addition to this, the actual temperature 

must be measured with either a good quality digital thermometer, or if a thermometer 

is not available, a second sensor can be placed alongside the one to be tested and the 

readings compared.

First measure the temperature using the thermometer and then measure the resistance of 

the sensor at the control. The wires from the sensor must not be connected to the control 

while the test is performed. Using the chart below, estimate the temperature measured 

by the sensor. The sensor and thermometer readings should be close. If the test meter 

reads a very high resistance, there may be a broken wire, a poor wiring connection or 

a defective sensor. If the resistance is very low, the wiring may be shorted, there may 

be moisture in the sensor or the sensor may be defective. To test for a defective sensor, 

measure the resistance directly at the sensor location.

Do not apply voltage to a sensor at any time as damage to the sensor may result.

Troubleshooting

Temperature

Resistance

Temperature

Resistance

Temperature

Resistance

Temperature

Resistance

°F

°C

°F

°C

°F

°C

°F

°C

-30
-20
-10

0

10
20

30
40
50
60
70
80

90

100
110
120
130
140

150
160
170
180
190
200

-34
-29
-23
-18
-12

-7

-1

4

10
16
21
27

32
38
43
49
54
60

66
71
77
82
88
93

234,196
165,180
118,018

85,362
62,465
46,218

34,558
26,099
19,900

15,311
11,883

9,299

7,334
5,828
4,665
3,760
3,050
2,490

2,045
1,689
1,403
1,172

983
829

STEP SEVEN

• Install the wiring cover over the wiring chamber and secure it with the screw provided.

• Place the front cover on the control and snap it into place.

• It is important to explain the operation of this control within the system to the end user, and to anyone else who may be operating 

the system.

Содержание PC705-2

Страница 1: ...ng system the heat supplied to the building must equal the heat lost by the building The heat supplied to a building is proportional to the temperature of the water and the surface area of the heating element A small surface area such as baseboard radiators requires a higher water temperature than a larger surface area such as radiant floors The heat lost from a building is dependent on the outdoo...

Страница 2: ...up the flue and reduced boiler jacket losses Differential An on off boiler must be operated with a differential in order to prevent short cycling When the supply water temperature drops below the bottom rail of the differential the boiler is turned on The boiler is then kept on until the supply water temperature rises above the top rail of the differential If the differential is too wide there can...

Страница 3: ...hen all zones are turned on If one of these variables is unknown use Equation 1 or 2 to calculate the other variable 3 Compute Tb Ts Look up the flow ratios on Figure 2 4 The design injection flow rate for direct injection is calculated from Equation 3 If the injection flow rate is greater than 45 US GPM it may be necessary to use a 4 way mixing valve instead of a variable speed injection system 5...

Страница 4: ...the injection pump SYSTEM PUMP OPERATION ThePC705 2hasaninternalsystempumpcontact ThiscontactturnsonwhenthePC705 2hasamixingdemandandisnotinaWWSD The system pump as well as the boiler pump may be controlled by this relay By providing proper flow in the boiler loop the boiler temperature can be accurately controlled based on the mixing load Equation1 System Flow Rate US GPM Design Heating Load Btu ...

Страница 5: ... push the front cover onto the enclosure until it snaps into place The variable speed injection pump and system pump wiring terminates in the electrical box All other electri calwiringterminatesinthetwowiringchambersonthe control The wiring is roughed in to the electrical box prior to installation of the control BOILEROPERATION Boiler Sensor Installed WhilethePC705 2hasamixingdemand theboilersuppl...

Страница 6: ...T T Zone 4 Zone 3 Zone 2 Zone 1 END SWITCH A Zone 4 Zone 3 Zone 2 Zone 1 Taco Zone Control ZVC404 EXP END SWITCH B T Boiler Pump Injection Pump Boiler Pump System Pump Injection Pump 120 V ac Outdoor Sensor Boiler Sensor Supply Sensor Priority Zone Switch set to ON DHW Tank T T T T POWER Zone 4 Zone 3 Zone 2 Zone 1 INPUT END SWITCH ZR X X ZC Zone 4 Zone 3 Zone 2 Zone 1 Taco Zone Control SR 506 EXP...

Страница 7: ...3 Zone 2 Zone 1 Taco Zone Control SR 503 EXP Boiler Pump Boiler Pump Injection Pump Injection Pump DHW Tank POWER Zone 3 Zone 2 Zone 1 INPUT END SWITCH ZR X X ZC Zone 3 Zone 2 Zone 1 Taco Zone Control SR 503 EXP A Expansion Switch set to Master Mode Switch set to Normal Expansion Switch set to Slave Mode Switch set to Normal PC 705 2 PC 702 1 PC 700 2 DHW Tank POWER Zone 3 Zone 2 Zone 1 INPUT END ...

Страница 8: ...on the Taco Zone Control Ensure the Mode switch on the Zone Control is set to Reset if boiler control is desired orNormalifboilerenableisdesired refertotheBoilerOperationsection Wiring the Sensors Do not apply power to these terminals as this will damage the control OutdoorSensor Connect the two wires from the Outdoor Sensor directly to the Com Out 1 and 3 terminals The Outdoor Sensor measures the...

Страница 9: ...F 27 to 107 C The MIX MAX should be set to the maximum temperature allowed in the system loop There are many factors which may limit the allowable supply water temperature in a radiant floor heating slab a few are provided below Nowhere in the concrete should the temperature be maintained above 170 F 77 C The surface temperature of a radiant floor heating slab should normally not exceed 85 F 29 C ...

Страница 10: ...mperature Press and release the Item button until the MIX TARGET elements are displayed Boiler Temperature Press and release the Item button until the BOIL element is displayed To view all control settings the Item button may be pressed and held while in the View Menu The contol will then scroll through all the adjustable items MIX Start Use the and buttons to set the desired mixing starting tempe...

Страница 11: ...by 5 F 3 C per day If the outdoor temperature is near the WWSD temperature and the rooms are cold increase the MIX Start setting Testing the Sensors A good quality test meter capable of measuring up to 5 000 kΩ 1 kΩ 1000 Ω is required to measure the sensor resistance In addition to this the actual temperature must be measured with either a good quality digital thermometer or if a thermometer is no...

Страница 12: ...aged to try to correct the interference by reorienting or relocating the receiving antenna relocating the receiver with respect to this control and or connecting the control to a different circuit from that to which the receiver is connected Do It Once Do It Right TACO INC 1160 Cranston Street Cranston RI 02920 Telephone 401 942 8000 Fax 401 942 2360 TACO Canada Ltd 6180 Ordan Drive Mississauga On...

Отзывы: