Taco PC705-2 Скачать руководство пользователя страница 2

2 of 12 

Reset Ratio

 

Operation of a hot water heating system can generally be improved by modulating the 
supply water temperature as the outdoor temperature changes. Using this approach, the 
heat lost from the building is matched by the heat input to the building. The PC705-2 
Variable Speed Injection Mixing Control utilizes a reset ratio to set the relationship 
between outdoor temperature and supply water temperature. The reset ratio determines 
the amount the supply water temperature is raised for every 1

°

 drop in outdoor air 

temperature, and it is determined from the starting point and the system design 
conditions. In order for the control to automatically determine the reset ratio, a starting 
point and design conditions must be established. These two points are set by the 
following 4 adjustments: 

• Mixing starting temperature 
• Outdoor starting temperature 
• Mixing design supply water temperature 
• Outdoor design temperature 

See Settings - Step Four for a complete description of each setting. 

Reset Ratio Starting Point

 

The first point used to establish the reset ratio calculation is the starting point. It is a combination of an adjustable mixing starting water 
temperature setting and the outdoor starting temperature setting. 

Design Conditions

 

The second point to establish the reset ratio calculation is the design conditions. This point represents the required water temperature 
during the coldest day of the year. 

Warm Weather Shut Down (WWSD)

 

When the outdoor air temperature is warmer than the Warm Weather Shut Down setting, no additional heat is required in the building; 
therefore, the heating system can be shut down. This setting has no effect on the reset ratio calculation. 

BOILER OPERATION

 

The supply water temperature from a boiler can be controlled by cycling 
the boiler on and off. Modulation of the boiler’s operating temperature in 
hot water heating systems not only provides more comfort but also offers 
significant energy savings. The cooler the boiler runs, the more efficient 
it is due to less heat losses up the flue and reduced boiler jacket losses. 

Differential

 

An on / off boiler must be operated with a differential in order to prevent 
short cycling. When the supply water temperature drops below the 
bottom rail of the differential, the boiler is turned on. The boiler is then 
kept on until the supply water temperature rises above the top rail of the 
differential. If the differential is too wide, there can be large supply water 
temperature swings; however, if the differential is too narrow, the boiler 
short cycles and operates inefficiently. This control automatically calcu-
lates the boiler differential in order to achieve an appropriate balance 
between temperature swings and boiler efficiency. This also permits the 
control to adapt to changing loads and conditions. 

Minimum Boiler Supply

 

Most boilers require a minimum supply water temperature in order to 
prevent corrosion from flue gas condensation. The control should 
therefore only modulate the boiler supply water temperature down to 
the boiler manufacturer’s minimum recommended operating tempera-
ture. Some boilers are designed to condense and should be operated 
at low water temperatures as much as possible for maximum efficiency. 

MIXING OPERATION

 

The full range of water temperatures required through a heating season 
can be provided with a standard (non-condensing) boiler by incorporating 
a modulating mixing device into the system. Mixing valves or variable 
speed injection pumps are commonly used to modulate both the system 
supply water temperature and the boiler return water temperature. The 
modulation of water temperatures improves comfort in the building and 
also protects the boiler from cool return water. 

Design

Conditions

Reset

Ratio

Starting

Point

Outdoor Temperature

Supply W

ater 

T

emper

ature

90

(32)

70

(21)

50

(10)

30

(-1)

10

(-12)

-10

(-23)

°

F

(

°

C)

70

(21)

90

(32)

110

(43)

130

(54)

150

(65)

170

(77)

190

(88)

210

(99)

Supply W

ater 

T

emper

ature

Time

Differential = 10

°

F (5

°

C)

165

°

F(74

°

C)

B

o

ile

r

o

ff

B

o

ile

r

o

n

155

°

F (68

°

C)

160

°

F (71

°

C)

B

o

ile

r

o

ff

B

o

ile

r

o

n

Outdoor air  temperature

50

(10)

30

(-1)

10

(-12)

-10

(-23)

70

(21)

90

(32)

WWSD

Temperature

°

F

(

°

C)

Supply w

ater temper

ature

110

(43)

70

(21)

90

(32)

210

(99)

170

(77)

150

(65)

130

(54)

190

(88)

Boiler

Minimum

Boiler

Loop

System

Loop

Mixing

Device

Содержание PC705-2

Страница 1: ...ng system the heat supplied to the building must equal the heat lost by the building The heat supplied to a building is proportional to the temperature of the water and the surface area of the heating element A small surface area such as baseboard radiators requires a higher water temperature than a larger surface area such as radiant floors The heat lost from a building is dependent on the outdoo...

Страница 2: ...up the flue and reduced boiler jacket losses Differential An on off boiler must be operated with a differential in order to prevent short cycling When the supply water temperature drops below the bottom rail of the differential the boiler is turned on The boiler is then kept on until the supply water temperature rises above the top rail of the differential If the differential is too wide there can...

Страница 3: ...hen all zones are turned on If one of these variables is unknown use Equation 1 or 2 to calculate the other variable 3 Compute Tb Ts Look up the flow ratios on Figure 2 4 The design injection flow rate for direct injection is calculated from Equation 3 If the injection flow rate is greater than 45 US GPM it may be necessary to use a 4 way mixing valve instead of a variable speed injection system 5...

Страница 4: ...the injection pump SYSTEM PUMP OPERATION ThePC705 2hasaninternalsystempumpcontact ThiscontactturnsonwhenthePC705 2hasamixingdemandandisnotinaWWSD The system pump as well as the boiler pump may be controlled by this relay By providing proper flow in the boiler loop the boiler temperature can be accurately controlled based on the mixing load Equation1 System Flow Rate US GPM Design Heating Load Btu ...

Страница 5: ... push the front cover onto the enclosure until it snaps into place The variable speed injection pump and system pump wiring terminates in the electrical box All other electri calwiringterminatesinthetwowiringchambersonthe control The wiring is roughed in to the electrical box prior to installation of the control BOILEROPERATION Boiler Sensor Installed WhilethePC705 2hasamixingdemand theboilersuppl...

Страница 6: ...T T Zone 4 Zone 3 Zone 2 Zone 1 END SWITCH A Zone 4 Zone 3 Zone 2 Zone 1 Taco Zone Control ZVC404 EXP END SWITCH B T Boiler Pump Injection Pump Boiler Pump System Pump Injection Pump 120 V ac Outdoor Sensor Boiler Sensor Supply Sensor Priority Zone Switch set to ON DHW Tank T T T T POWER Zone 4 Zone 3 Zone 2 Zone 1 INPUT END SWITCH ZR X X ZC Zone 4 Zone 3 Zone 2 Zone 1 Taco Zone Control SR 506 EXP...

Страница 7: ...3 Zone 2 Zone 1 Taco Zone Control SR 503 EXP Boiler Pump Boiler Pump Injection Pump Injection Pump DHW Tank POWER Zone 3 Zone 2 Zone 1 INPUT END SWITCH ZR X X ZC Zone 3 Zone 2 Zone 1 Taco Zone Control SR 503 EXP A Expansion Switch set to Master Mode Switch set to Normal Expansion Switch set to Slave Mode Switch set to Normal PC 705 2 PC 702 1 PC 700 2 DHW Tank POWER Zone 3 Zone 2 Zone 1 INPUT END ...

Страница 8: ...on the Taco Zone Control Ensure the Mode switch on the Zone Control is set to Reset if boiler control is desired orNormalifboilerenableisdesired refertotheBoilerOperationsection Wiring the Sensors Do not apply power to these terminals as this will damage the control OutdoorSensor Connect the two wires from the Outdoor Sensor directly to the Com Out 1 and 3 terminals The Outdoor Sensor measures the...

Страница 9: ...F 27 to 107 C The MIX MAX should be set to the maximum temperature allowed in the system loop There are many factors which may limit the allowable supply water temperature in a radiant floor heating slab a few are provided below Nowhere in the concrete should the temperature be maintained above 170 F 77 C The surface temperature of a radiant floor heating slab should normally not exceed 85 F 29 C ...

Страница 10: ...mperature Press and release the Item button until the MIX TARGET elements are displayed Boiler Temperature Press and release the Item button until the BOIL element is displayed To view all control settings the Item button may be pressed and held while in the View Menu The contol will then scroll through all the adjustable items MIX Start Use the and buttons to set the desired mixing starting tempe...

Страница 11: ...by 5 F 3 C per day If the outdoor temperature is near the WWSD temperature and the rooms are cold increase the MIX Start setting Testing the Sensors A good quality test meter capable of measuring up to 5 000 kΩ 1 kΩ 1000 Ω is required to measure the sensor resistance In addition to this the actual temperature must be measured with either a good quality digital thermometer or if a thermometer is no...

Страница 12: ...aged to try to correct the interference by reorienting or relocating the receiving antenna relocating the receiver with respect to this control and or connecting the control to a different circuit from that to which the receiver is connected Do It Once Do It Right TACO INC 1160 Cranston Street Cranston RI 02920 Telephone 401 942 8000 Fax 401 942 2360 TACO Canada Ltd 6180 Ordan Drive Mississauga On...

Отзывы: