background image

• The sensor should be mounted on a wall which best represents

the heat load on the building (i.e. a northern wall for most build-
ings  and  a  southern  facing  wall  for  buildings  with  large  south
facing glass areas). The sensor should not be installed near heat
sources such as ventilation or window openings.

• The sensor should be installed at an elevation above the ground

that will prevent accidental damage or tampering.

• Install the Outdoor Sensor and run the wiring back to the con-

trol mounting location. 

Installing the Boiler Sensor: 

Note:

This sensor is designed to mount on a pipe or in a tempera-

ture immersion well.

• The sensor can be strapped directly to the pipe using the cable

tie provided. Insulation should be placed around the sensor to
reduce the effect of air currents on the sensor measurement.

• The Boiler Sensor should be placed downstream of a pump or

after  an  elbow  or  similar  fitting.  This  is  especially  important  if
large diameter pipes are used because the thermal stratification
within the pipe can result in erroneous sensor readings. Proper
sensor location requires that the fluid is thoroughly mixed with-
in the pipe before it reaches the sensor. 

Step Three:

Wiring to the Zone Control: 

Line Voltage Connections –

Connect 120VAC incoming line voltage; Hot to the H terminal and
Neutral to the N terminal.

Connect 120VAC circulator; HOT lead of circulator to Zone H ter-
minal and Neutral lead of circulator to Zone N terminal.

Low Voltage Connections –

Connect thermostat or zone control end switch to the R and W
thermostat terminals.

Connect the DHW aquastat to the R and W DHW override terminals
(optional).

Connect boiler’s T and T terminal to the X and X boiler end switch
terminals.

Wiring the Sensors:  

Do  not  apply  power  to  these  terminals  as  this  will  damage  the
control.

Outdoor Sensor 

Connect the two wires from the Outdoor Sensor to the Outdoor
Sensor terminals. The Outdoor Sensor measures the outdoor air
temperature. 

Boiler Sensor 

Connect  the  two  wires  from  the  Boiler  Sensor  to  the  Supply
Sensor  terminals  and  insulate.  The  Boiler  Sensor  measures  the
supply water temperature going from the boiler to the system.

SETTINGS:

Before adjusting the settings, read through the sequence of operation
to ensure that you understand how the control operates. The follow-
ing  page  describes  how  to  program  these  settings  into  the  control
once it has been powered up.

Step Four:

Outdoor Design Temperature:

The  Outdoor  Design  setting  is  the  outdoor
temperature used in the heat loss calculation.
It is set to the typical coldest outdoor temper-
ature.  Using  a  small  screwdriver  adjust  the
reset ratio knob to appropriate Outdoor Design
Temperature. When set to OFF, the boiler tem-
perature will not be reset and boiler will fire to
high limit when there is a call for heat.

Boiler Minimum Supply Temperature (Dip Switch #1):

Most  boilers  require  a  minimum  operating  temperature  to  prevent
corrosion from flue gas condensation. The minimum boiler dip switch
should be set to ON (140°F) supply water temperature so boiler can
operate without causing the boiler flue gases to condense. Consult

the  boiler  manufacturer  for  recommended  minimum  boiler  supply
temperatures.  The  dip  switch  can  also  be  set  to  OFF  (70°F)  when
condensation is not a concern.

Differential (Dip Switch #2):

The differential adjustment sets how far the actual boiler supply water
temperature  may  deviate  from  the  desired  temperature  before  the
boiler is turned on or off. This is a function of the water content of the
boiler and the flow rate through the system pump relative to the heat
output of the boiler. The differential can be set by dip switch #2,  set to
OFF for 10°F (6°C) or set to ON for 20°F (12°C). 

Pump Operation (Dip Switch #3):

The  pump  operation  is  controlled  by  dip  switch  #3.    When  the  dip
switch is set to ON, the pump output will energize when thermostat
or DHW calls for heat. When set to OFF, the pump will only come on
when the thermostat calls for heat not the DHW.

Warm Weather Shut Down: 

When the outdoor temperature rises above 70°F (21°C), the control
turns off the boiler and blinks the Thermostat LED light. This function
only applies for space heating and does not affect DHW operation.

TROUBLESHOOTING:

Step Five:

As in any troubleshooting procedure, it is important to isolate a prob-
lem as much as possible before proceeding. The blinking error LED
light greatly simplifies troubleshooting of the SR501-OR. If you sus-
pect a wiring fault, return to step three and carefully check all exter-
nal wiring and wiring connections. 

Sensor Errors:

• If an outdoor sensor fault occurs, the SR501-OR will assume a

fixed  outdoor  temperature  of  32°F  (0°C)  and  will  target  the
appropriate supply water temperature. The Boiler light will blink
twice every 5 seconds to indicate the outdoor sensor error. 

• If a boiler sensor fault occurs, the SR501-OR turns the boiler off

and the Boiler light will blink once every 5 seconds to indicate
the boiler supply sensor error. 

Adjustment of Settings: 

• If  the  outdoor  temperature  is  cold  and  the  rooms  are  cold,

increase the Outdoor Design setting by 5°F (3°C) per day. 

• If the boiler is cycling too often, increase the Differential setting.

Testing the Sensors:

A good quality test meter capable of measuring up to 5,000 k

(1 k =

1000 

)  is  required  to  measure  the  sensor  resistance.  In  addition  to

this,  the  actual  temperature  must  be  measured  with  either  a  good
quality digital thermometer, or, if a thermometer is not available, a sec-

Do not apply voltage to a sensor at any time
as damage to the sensor may result.

Note: When the outdoor temperature rises above 70°F (21°C), the
control turns off the boiler and blinks the Thermostat LED light.
DHW will still operate.

OFF

-30

-20

-10

0

10

20

30

40

Содержание FuelMizer SR501-OR-4

Страница 1: ...all surface area such as baseboard radiators requires a higher water temperature than a larger surface area such as radiant floors The heat lost from a building is dependent on the outdoor tem perature as well as other factors As the outdoor temperature drops the building heat loss increases Reset Ratio Operation of a hot water heating system can generally be improved by modulating the supply wate...

Страница 2: ...r Shut Down WWSD When the outdoor temperature rises above 70 F 21 C the control turns off the boiler and blinks the Thermostat LED light This function only applies for space heating and does not affect DHW operation Boiler Operation When the SR501 OR has a reset demand the system supply water temperature is controlled by turning the boiler on and off The control calculates the target supply water ...

Страница 3: ...gh limit when there is a call for heat Boiler Minimum Supply Temperature Dip Switch 1 Most boilers require a minimum operating temperature to prevent corrosion from flue gas condensation The minimum boiler dip switch should be set to ON 140 F supply water temperature so boiler can operate without causing the boiler flue gases to condense Consult the boiler manufacturer for recommended minimum boil...

Страница 4: ...64 9422 FAX 905 564 9436 Visit our web site at http www taco hvac com Printed in USA Copyright 2013 TACO Inc ond sensor can be placed alongside the one to be tested and the read ings compared First measure the temperature using the thermometer and then measure the resistance of the sensor at the control The wires from the sensor must not be connected to the control while the test is performed Usin...

Отзывы: