Main menu item
Sub-menu item 1
Sub-menu item 2
Explanations
→
Frost
protection
Active
Setp shutdown:
25.0°C
P-band active:
5.0°C
P-band active 5° C means that
the frost protection controller
will start overriding the heating
output when the frost protection
temperature is less than 5
degrees above the set frost
alarm default alarm limit is 7° C
Fast stop
at frost
protection
alarm
Yes
Set
the fast stop of the unit in
case of frost protection alarm to
Yes
or
No
.
→
Alarm
settings
→
Alarm limits
Set
the alarm limits and allowed
deviations for the different
functions
→
Alarm delays
Set
the alarm delays and
allowed deviation delays for the
different functions
→
Restore alarm
Reset the service alarm (filter
alarm).
Restore factory
settings:
No
Restore user
settings:
No
In this menu, it is possible to
restore all parameters to their
factory settings or to the user
settings they were
saved as
earlier.
Select
Yes
or
No
Save user
settings
No
The current configuration can
be saved in a separate memory
area and can later be restored
using the previous menu,
Restore user settings.
Select
Yes
or
No
→
Configuration
→
Inputs/Out-
puts
AI
DI
UI
AO
DO
Set
compensations for
analogue inputs and assign
extra sensors and in/outputs.
Set
if digital inputs is normally
open or normally closed.
→
Control
function
Control
function
Mode:
Supply air
control
Set
type of temperature control
function you want the unit
to operate under. Choose
between
Extract air control,
"Room control, Outdoor
comp.
Supply, Supply
air control,
Extract/supply air
→(possible to switch between
the two depending on outdoor
temp.),