Main menu item
Sub-menu item 1
Sub-menu item 2
Explanations
→
Timer normal
speed
Set week schedule Monday to
Holiday for normal
speed. Possible to set 2 periods
per day.
00:00 24:00 for continuous
running. 00:00 00:00
inactivates the period.
Note the settings in the
commissioning record
→
Timer reduced
speed
Set week schedule Monday to
Holiday for reduced
speed. Possible to set 2 periods
per day.
00:00 24:00 for continuous
running. 00:00 00:00
inactivates the period.
Note the settings in the
commissioning record
→
Extended
running
Extended
running
60 min
Time in ext.
running
0 min
Set the time for extended
running. Digital inputs can be
used to force the unit to start
or increase to Normal running
although the timer says the
running mode should be
Off
or
Reduced
.
If the running time is set to 0
the unit only runs as long as the
digital input is closed.
The time the extended running
is active is monitored in "Time
in ext. Running".
It's also possible to set a time
here as well in order to shorten
the initial set period.
→
Holidays
Holidays
(mm:dd)
1:01–01 — 01–02
2:09–04 — 09–10
3:01–05 — 01–05
Set up to 24 separate possible
holiday periods for a full year.
A holiday period can be any
number of consecutive days
from one and upwards.
The dates are in the format:
MM:DD.
When the current date falls
within a holiday period, the
scheduler will use the settings
for the weekday “Holiday”.
Operation and Maintenance Instructions
132616
14
Systemair Sverige AB