Main menu item
Sub-menu item 1
Sub-menu item 2
Explanations
→
Manual/Auto
In this menu the running mode
of all the configured output
signals and a number of control
functions can be manually
controlled.
The supply air controller's
output signal can be manually
set (Manual/Auto) to any value
between 0 and 100%. The
temperature output signals will
change accordingly if they are
in Auto mode. It is also possible
to manually control each of
the temperature output signals
individually.
Since leaving any of the
outputs in manual control will
disrupt the normal control,
an alarm will be generated as
soon as any output is set to a
manual mode.
Supply
Temperature
contr.
Auto
Manual set:
0.0
Set the supply air temperature
to "Auto", "On" or "Off".
Set the output signal between
0-100%.
The outputs Y1, Y2 and Y3, if
in Auto-mode, will follow the
signal according to the set split
values.
SAF: Auto
Manual set:
0.0
EAF: Auto
Manual set:
0.0
Set the start signal for SAF
(supply air fan) & EAF (exhaust
air fan) to "
Auto
,
Manual
full speed
,
Manual half
speed
or
Manual
Heating
Auto
Manual set:
100.0
Set the heating to
Auto
,
Manual
or
Off
Set the manual output 0-100%
Cooling
Auto
Manual set:
0.0
Set the cooling to
Auto
,
Manual
or
Off
Set the manual output 0-100%
Note:
Needs to be activated in order
to be visible here
P1–Heating
Auto
Set the pump control for the
heating coil to
Auto
,
On
or
Off
Operation and Maintenance Instructions
132616
15
Systemair Sverige AB