TURNING THE COIL

TESTING THE FANCOIL

CAUTION!

The fan may reach the speed of 1,000 rpm. Do not insert objects or hands into 

the electric fan. The motor becomes hot during operation; wait for it to cool 

before touching it. During the heating mode of operation the exchanger and the 

connecting pipes may become very hot (80°C).

Wait for the exchanger to cool before touching it or protect hands with 

suitable gloves. The heat exchange water coils are suitable for working up 

to ma maximum pressure of 8 bar.

1.  Remove the housing (if present).

2.  Disconnect the terminal block or the control panel (2), if present, from the 

side of the appliance.

3.  Remove the galvanised panels (4).

4.  Remove the coil fi xing screws (5).

5.  Take out the coil (1), being careful not to be cut by the fi ns and not to dama-

ge them.

6.  Remove the knockouts on the opposite side of the fan coil (using a screwdri-

ver), to allow the coil connections to pass through.

7.  Position the coil, turning it without tipping it upside down, so that the fi ttings 

are in line with the holes left by the knockouts.

8.  Fix the coil using the previously removed screws (5).

9.  Shift the control panel (2), if present, or the terminal block (fi xing it to the 

side opposite the water fi ttings), the motor and sensor cables (3), if present, 

fi xing them with their grips. Ensure that the cables pass through the hole in the 

side of the appliance, protecting them with the relative grommet. If it proves ea-

sier to carry  out this  operation  by separating the wires from the terminal blocks, 

mark the positions of the wires to avoid making mistakes when reconnecting.

10. Reconnect the wires to the relative terminal blocks or control panel (2), 

taking care that they are correctly positioned.

11.  Replace the galvanised panels.

12.  Remount the housing (if present).

Upon completion of installation, scrupulously check both the water and the elec-

trical connections before switching on the appliance. 

Before mounting the housing (if present)

, fi ll the system, bring it up to pres-

sure and bleed. Make the water circulate and check for leaks. 

Check correct operation of the fan coil at the 3 speeds, of the solenoid 

valves and of the minimum temperature thermostat (if installed). The ca-

binet is covered by a protective fi lm: remove it before fi xing the housing 

to the appliance.

Remount the housing (if present)

, otherwise the customer has the responsi-

bility of concealing the appliance.

CAUTION! Protect the appliance with a cardboard box if building works 

are still being carried out (Pic. 18).

To turn the coil, proceed as follows: 

Pic. 19

Pic. 18

Pic. 19

P=8

bar max

0
°

6
0
°

5

2

1

3

4

1

2

3

4

Содержание SYSCOIL MINI 21

Страница 1: ...INSTALLATION USE AND MAINTENANCE MANUAL LOW PROFILE CENTRIFUGAL FAN COIL UNIT SYSCOIL MINI 2012 0...

Страница 2: ......

Страница 3: ...COMMENDATIONS FOR INSTALLATION 6 FAN COIL INSTALLATION 6 WATER CONNECTIONS 7 Connection to the water mains 7 Condensate water drainage 7 ELECTRICAL CONNECTIONS 7 CONNECTION TO THE TERMINAL BLOCK 7 Wit...

Страница 4: ...he appliance works by electricity at mains voltage 230 Vac 50 Hz Always bear in mind that mains voltage is potentially dangerous and any appliance connected to it should be used with caution Before ca...

Страница 5: ...ng slots 9 Coil fixing screws 10 Load bearing structure 2 10 3 4 7 6 6 5 1 9 8 7 GENERAL TECHNICAL DATA MODEL 21 22 23 24 25 Power supply 230V 1 50Hz Tab 1 226 350 68 105 56 220 180 C D M L 110 350 22...

Страница 6: ...coil load bearing structure Gipping the rear of the housing remove it as shown in the Pic 5 NOTE be careful of the lugs on the front part of the load bearing structure as shown in Pic 10 Put the cabi...

Страница 7: ...ding not only the working current required by the appliance but also the necessary current for powering household and other electrical appliances already in use Any electrical and mechanical alteratio...

Страница 8: ...nt or the terminal block fixing it to the side opposite the water fittings the motor and sensor cables 3 if present fixing them with their grips Ensure that the cables pass through the hole in the sid...

Страница 9: ...ersion is the same USING THE CONTROL PANEL If the appliance has a built in control panel raise the flap and proceed as follows Heating mode Put the season selector switch from the off position to the...

Страница 10: ...ge position on the control panel Possible cause water in the system not hot enought Possible remedy check that the outlet temperature is above 40 C Little outflowing air Possible cause clogged filter...

Страница 11: ...NOTES...

Страница 12: ...With the perspective of improvement and against the continuous action of research and development the Manufacturer might modify even without any prior notice the given technical data systemair com...

Отзывы: