INSTALLATION, OPERATION

AND MAINTENANCE MANUAL

Vers. 2012-0

low profi le
centrifugal fan coil unit

7

3 cm/m

WATER CONNECTIONS

ELECTRICAL CONNECTIONS

CONNECTIONS TO THE TERMINAL BLOCKS

CONNECTION TO THE WATER MAINS

CAUTION!   Always use a wrench and nose key for connection of the coil 

to the pipes (Pic. 12). If the solenoid valve is installed, suitably insulate the 

valve body with insulating material (Pic.  13).

Connect the water inlet and outlet pipes, observing the indications given on the 

side of the appliance. Correctly insulate the water supply pipes to prevent drip-

ping during the cooling mode of operation. An shutoff valve should be inserted 

on the water supply pipe and balancing valve on the outlet pipe. The valve body 

and balancing valve should also be properly insulated to prevent dripping. It is 

the installer’s responsibility to insulate properly and the manufacturer cannot be 

held liable for any insulation work.

NOTE: it is always advisable to install the solenoid valve.  In the heating 

mode of operation the solenoid valve reduces consumption because upon 

reaching the set temperature the circulation of water is stopped to avoid 

wasting energy (the fan coil would otherwise continue to heat like a radia-

tor, even with the motor at a standstill). In the cooling mode of operation 

the solenoid valve stops the circulation of water when the set temperature 

is reached, this stopiing the internal exchanger

from continuing to condense water with possible undersirable dripping 

into the fl oor. It also reduces chiller operation with consequent energy 

saving.

RECOMMENDATIONS!

Before carrying out electrical connections, ensure that the electricity supply to 

the supply line has been cut off, checking that the on-off switch is in the OFF 

position. Only qualifi ed electricians should carry out the electrical connections. 

Check that the mains supply is single-phase 230 Vac/1/50 Hz (± 10%).

Operating the appliance with voltages outside the above limits could cause mal-

function and renders the warranty null and void.

The fan coil power supply line should be fi tted with at least a switch isolator in 

conformity with European standard EN60947-3. Make sure that the electrical 

system is suitable for providing not only the working current required by the 

appliance, but also the necessary current for powering household and other 

electrical appliances already in use.

Any electrical and mechanical alterations or tampering render the warranty null 

and void. The motor and accessories power cables in channels or ducts should 

remain inside the same until they are inside the appliances.

The cables should be suffi ciently long so that they are not permanently taut or 

create throttling or pressure on metal parts  (see Pic. 15). The power cables 

should be suffi ciently long so that in the event of accidental tugging the active 

wires are subjected to stress before the earth wire. Connect the earth wire to the 

relative terminal marked with the symbol   .

Check the earth connection. Comply with the safety regulations in force in the 

country of installation.

WITHOUT CONTROL PANEL

The electrical connections should be made to the terminal block on the side of 

the appliance (Pic. 16).

Each terminal is identifi ed by the label to be found on the terminal block.

WITH CONTROL PANEL

The electrical connections should be made directly to the control panel, as shown 

by the relative wiring diagram. If the control panel has an electronic temperature 

sensor (NTC) this sensor will be powered by mains voltage (230Vac/1/50 Hz) 

and is therefore provided with double insulation.

CAUTION: FAILURE TO COMPLY WITH THE INDICATED CONNECTIONS 

MAY CAUSE MOTOR BURNOUT!

CONDENSATE WATER DRAINAGE

The condensate drain pipe should slope downwards by at least 3 cm/m and 

should not have ascending or throttled section in order to ensure a regular fl ow 

of water. It is advisable for a trap to be fi tted. The condensate drain pipe should 

be connected to a rainwater drainage system. Do not use sewage system to 

avoid possible odours in the event of evaporation of the water in the trap. Upon 

completion of work, check that the condensate fl ows out properly by pouring 

water into the tray (see Pic. 14). The condensate water drainage system should 

be fabricated

in a workmanlike manner and should be periodically checked. The manufacturer 

cannot be held liable for any damage caused by dripping in the absence of a 

solenoid valve or of periodic maintenance of the drainage system.

Pic. 15

Pic. 14

Pic. 12

Pic. 13

Pic. 16

Max (III)

Med (II)

Min (I)

Common

(Com)

230 Vac - 50 Hz

M

Fan motor

T1

Autotransformer
(not installed in all models)

XA1

Fan motor terminal board

XA1

Содержание SYSCOIL MINI 21

Страница 1: ...INSTALLATION USE AND MAINTENANCE MANUAL LOW PROFILE CENTRIFUGAL FAN COIL UNIT SYSCOIL MINI 2012 0...

Страница 2: ......

Страница 3: ...COMMENDATIONS FOR INSTALLATION 6 FAN COIL INSTALLATION 6 WATER CONNECTIONS 7 Connection to the water mains 7 Condensate water drainage 7 ELECTRICAL CONNECTIONS 7 CONNECTION TO THE TERMINAL BLOCK 7 Wit...

Страница 4: ...he appliance works by electricity at mains voltage 230 Vac 50 Hz Always bear in mind that mains voltage is potentially dangerous and any appliance connected to it should be used with caution Before ca...

Страница 5: ...ng slots 9 Coil fixing screws 10 Load bearing structure 2 10 3 4 7 6 6 5 1 9 8 7 GENERAL TECHNICAL DATA MODEL 21 22 23 24 25 Power supply 230V 1 50Hz Tab 1 226 350 68 105 56 220 180 C D M L 110 350 22...

Страница 6: ...coil load bearing structure Gipping the rear of the housing remove it as shown in the Pic 5 NOTE be careful of the lugs on the front part of the load bearing structure as shown in Pic 10 Put the cabi...

Страница 7: ...ding not only the working current required by the appliance but also the necessary current for powering household and other electrical appliances already in use Any electrical and mechanical alteratio...

Страница 8: ...nt or the terminal block fixing it to the side opposite the water fittings the motor and sensor cables 3 if present fixing them with their grips Ensure that the cables pass through the hole in the sid...

Страница 9: ...ersion is the same USING THE CONTROL PANEL If the appliance has a built in control panel raise the flap and proceed as follows Heating mode Put the season selector switch from the off position to the...

Страница 10: ...ge position on the control panel Possible cause water in the system not hot enought Possible remedy check that the outlet temperature is above 40 C Little outflowing air Possible cause clogged filter...

Страница 11: ...NOTES...

Страница 12: ...With the perspective of improvement and against the continuous action of research and development the Manufacturer might modify even without any prior notice the given technical data systemair com...

Отзывы: