- 15 -
User instructions
Pressure controller REP 6/10
3.3 Operation
P-band
0 % 100
0 % 100
Always close transparent
cover dust tight
0 % 100
SETPOINT
2
3
1
P4
5
P6
P7
P8
n-min
n-max
1
"Interference"
Comes on: TK triggered in motor
Flashes:
Break or short-circuited sensor input.
When upper or lower limit of sensor
measuring range is reached.
2
"Operation"
Comes on: Mains connection and
main switch in ON position (1 or 100%)
3
Main switch
Position "
0
": Controller off
Position "
I
" : Variable fan speed control
P4
Potentiometer
RPM "%"
Setting reference value 0-100%
P6
Potentiometer
"n-min"
Setting min. output voltage (min rpm)
P7
Potentiometer
"n-max"
Setting max. output voltage (max rpm)
P8
Potentiometer
P-band
Setting control inertia