D200-304-00
I56-3893-001
Pittway Tecnologica S.r.l. Via Caboto 19/3, 34147 TRIESTE, Italy
PROGRAMMING
To load network parameters into the RF repeater, it is necessary
to link the RF gateway and the RF repeater in a configuration
operation. At commissioning time, with the RF network devices
powered on, the RF gateway will connect and programme them
with network information as necessary. The radio repeater then
synchronises with its other associated devices as the RF mesh
network is created by the gateway. (For further information, see the
Radio Programming and Commissioning Manual
- ref. D200-
306-00.)
NOTE:
Do not run more than one interface at a time to
commission devices in an area.
LED INDICATORS AND FAULT DESCRIPTION
The radio gateway has two LED indicators that show the status of
the device (see table below).
Figure 4: Battery Installation and Rotary Address Switches
NOTE POLARITY
4 x Duracell
Ultra 123
4c
4a
4d
4b
+
+
+
+
1
2
3
4
EN54-25: 2008 / AC: 2010 / AC: 2012
Components Using Radio Links
EN54-18: 2005 / AC: 2007 Input/Output Devices
for use in fire detection and fire alarm systems for buildings
0333 16
DOP-IRF006
Pittway Tecnologica S.r.l.
Via Caboto 19/3, 34147 Trieste, Italy
+
ROTARY ADDRESS SWITCHES
Repeater Status LEDs
Repeater Status
LED State
Meaning
Power-on initialisation
(no fault)
Long Green pulse
Device is un-commissioned
(factory default)
3 Green blinks
Device is commissioned
Fault
Blink Amber every 1s.
Device has an internal trouble
Un-commissioned
Red/Green double-blink every 14s
(or just Green when communicating).
Device is powered and is waiting to be
programmed.
Sync
Green/Amber double-blink every 14s
(or just Green when communicating).
Device is powered, programmed and
trying to find/join the RF network.
Normal
Controlled by panel; can be set to Red
ON, periodic blink Green or OFF.
RF communications is established;
device is working properly.
Idle (low power mode) Amber/Green double-blink every 14s
Commissioned RF network is in standby;
used when the gateway is powered off.
EC Declaration of Conformity
In accordance with EN60950 and 1999/5/EC R&TTE Directive
This product complies with the following Directive(s):
2006/95/EC Low Voltage
2004/108/EC Electromagnetic Compatibility
The full DoC can be obtained from System Sensor Europe
Patents Pending