TABLE 3. DETECTOR STATUS INDICATION

NOTE: Power Board LED is not visible unless the power board cover is removed. If any other visual indication is noted contact System Sensor technical support 
at 1-800-SENSOR2.

DETECTOR 
STATE

SENSOR LED

POWER BOARD LED

COMMENTS

RELAY STATES

Power Up

Red Blink every 5 
seconds

Alternating Green/ 
Amber Blink every 1 
second 

Initialization completes in 

approximately 30 sec

Supervisory relay: Terminals 3 and 14 are closed. 

Alarm Relay: Terminals 4 and 5 are open

Aux Relay does not switch states: Terminals 6 and 16 
are closed; Terminals 8 and 18 are closed

Standby

Green Blink every 5 
seconds

Green Blink every 5 
seconds

Supervisory relay: Terminals 3 and 14 are closed. 

Alarm Relay: Terminals 4 and 5 are open

Aux Relay does not switch states: Terminals 6 and 16 
are closed; Terminals 8 and 18 are closed

Maintenance

Red Blink every 5 
seconds

Amber Blink every 5 
seconds

The 2D51 sensor is outside it’s 
UL approved sensitvity limits and 
needs to be cleaned or replaced.

Supervisory relay: Terminals 3 and 14 are closed. 

Alarm Relay: Terminals 4 and 5 are open

Aux Relay does not switch states: Terminals 6 and 16 
are closed; Terminals 8 and 18 are closed

Speed-Up

Alternating Red/
Green Blink every 
0.5 seconds

Green Blink every 
0.5 seconds

Alternating red /green blink 
pattern exists until unit either 
enters Alarm or reverts to 
Standby (within approximately 
60 seconds).

Supervisory relay: Terminals 3 and 14 are closed. 

Alarm Relay: Terminals 4 and 5 are open

Aux Relay does not switch states: Terminals 6 and 16 
are closed; Terminals 8 and 18 are closed

Trouble

Red Blink every 5 
seconds

Amber Solid 

Supervisory relay: Terminals 3 and 14 are open. 

Alarm Relay: Terminals 4 and 5 are open

Aux Relay does not switch states 

Cover Tamper 
Violation

Red Blink every 5 
seconds

Amber Solid

When in “Standby” mode, 
the product goes into “Cover 
Tamper Violation” if the cover 
has been removed or improperly 
replaced and remains so for at 
least 7 minutes.  As soon as the 
cover is properly reseated, the 
product reverts to “Standby” 
automatically.

Supervisory relay: Terminals 3 and 14 are open. 

Alarm Relay: Terminals 4 and 5 are open.  

Aux Relay does not switch states  

Communication 
Error

Off

Amber Solid

Sensor LED state cannot be 
guaranteed since there is a 
communication error.

Supervisory relay: Terminals 3 and 14 are open. 

Alarm Relay: Terminals 4 and 5 are open

Aux Relay does not switch states

Alarm

Red Solid

Red Solid

Supervisory relay: Terminals 3 and 14 are closed 

Alarm Relay: Terminals 4 and 5 are closed

Aux Relay switches states: Terminals 6 and 16 are 
open; Terminals 8 and 18 are open

Unit Loses 
Power

Off

Off

Supervisory relay: Terminals 3 and 14 are open. 

Alarm Relay: Terminals 4 and 5 are open

Aux Relay does not switch states

  

I56-4260-002R 

 

 06-10

Содержание DUCTSD240

Страница 1: ...5 sec max Alarm response time 15 sec 15 sec 15 sec Sensitivity Test See detector label See detector label See detector label Current Requirements Using No Accessories Max standby current 21 mA 24 VDC 65 mA RMS 24VAC 60Hz 10 mA RMS 240 VAC 60 Hz Max alarm current 65 mA 24 VDC 135 mA RMS 24 VAC 60 Hz 18 mA RMS 240 VAC 60 Hz CONTACT RATINGS Alarm initiation contacts SPST 2 0A 30 VDC resistive Alarm a...

Страница 2: ...hese parameters If neces sary use a velocity meter anemometer to check the air velocity in the duct 5 2 DETERMINE MOUNTING LOCATION AND CONFIGURATION On ducts wider than 18 inches it is recommended that the detector be mounted downstream of a bend obstruction in the duct or the supply or return air inlet Exception Installation of duct detectors can be on or within a commercial packaged rooftop hea...

Страница 3: ...ct Plug the end with the end cap and tape closed any holes in the protrud ing section of tube Be sure to seal the duct where the tube protrudes FIGURE 4 DETECTOR 3 4 HOLE 12 1 4 2 H0215 00 NOTE Air currents inside the duct may cause excessive vibration especially when the longer sampling tubes are used In these cases a 3 inch floor flange available at most plumbing supply stores may be used to fas...

Страница 4: ... WIRE DUCT SMOKE DETECTORS CAUTION Do not loop wire under terminals when wiring detectors Break wire runs to provide system supervision of connections 24VAC DC 9 10 AUXILIARY CONTACTS FOR FAN SHUTDOWN ETC NOTE 2 16 6 17 8 18 7 N O C N C N O C N C 16 6 17 8 18 7 N O C N C N O C N C SUPERVISORY CONTACTS NOTE 3 24V 9 10 AUXILIARY CONTACTS FOR FAN SHUTDOWN ETC NOTE 2 SUPERVISORY CONTACTS NOTE 3 SUP N ...

Страница 5: ... REMEMBER TO REMOVE THE PLUGS AFTER THIS TEST OR THE DETECTOR WILL NOT FUNCTION PROPERLY FIGURE 8 MULTIPLE FAN SHUTDOWN INTERCONNECTION OF DUCTSD240 TO D4240 D4240 D4240 DUCTSD240 DUCTSD240 DUCTSD240 H0640 01 H0639 01 ALARM TEST OPTIONS TEST METHOD DETECTOR RESET Test Reset Button Press and hold test reset button for at least 7 seconds Press and release the test reset button Magnet Test M02 04 00 ...

Страница 6: ...If the smoke has cleared the unit will go into STANDBY otherwise the unit will remain in ALARM 12 DETECTOR CLEANING PROCEDURES Notify the proper authorities that the smoke detector system is undergoing maintenance and that the system will temporarily be out of service Disable the zone or system undergoing maintenance to prevent unwanted alarms and possible dispatch of the fire department 12 1 DETE...

Страница 7: ... green blink pattern exists until unit either enters Alarm or reverts to Standby within approximately 60 seconds Supervisory relay Terminals 3 and 14 are closed Alarm Relay Terminals 4 and 5 are open Aux Relay does not switch states Terminals 6 and 16 are closed Terminals 8 and 18 are closed Trouble Red Blink every 5 seconds Amber Solid Supervisory relay Terminals 3 and 14 are open Alarm Relay Ter...

Страница 8: ...tion number send defective units postage prepaid to Honeywell 12220 Rojas Drive Suite 700 El Paso TX 79936 USA Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to replace units which are found to be defective because of damage unreasonable use modifications or alterations occurring after the date of manufacture In no case shall the ...

Отзывы: