background image

POWER BOARD

EXHAUST TUBE

METAL SAMPLING TUBE

(sold separately)

POWER BOARD

MODULE COVER

SENSOR HEAD

SENSOR MODULE

COVER

MAGNET TEST

SMOKE TEST PORT

[3] GENERAL DESCRIPTION

Smoke introduced into an air duct system will be distributed throughout the 
entire building. Smoke detectors designed for use in air duct systems are used 
to sense the presence of smoke in the duct. 

Model DUCTSD240 Duct Smoke Detectors utilize 4-wire photoelectric technol-
ogy for the detection of smoke. This detection method, when combined with 
an efficient housing, samples air passing through the duct allowing detection 
of a developing hazardous condition. When sufficient smoke is sensed, an 
alarm signal is initiated and appropriate action can be taken to shut off fans, 
blowers, change over air handling systems, etc. These actions can facilitate 
the management of toxic smoke and fire gases throughout the areas served 
by the duct system.

The DUCTSD240 detector is designed to operate on 24 VDC/VAC or 120 VAC. 
Alarm and supervisory relay contacts are available for control panel interface 
(alarm initiation), HVAC control, and other auxiliary functions. The fire alarm 
control panel is NOT notified when sensor maintenance its required. Auxil-
iary relays are provided for fan shut down. Detector interconnection provides 
signaling of up to 30 other detectors in the loop for multiple fan shut down. 
These detectors are not designed for 2-wire applications.

[3.1] DETECTOR FEATURE SET

-Utilizes 2D51 plug-in head

-Cover missing signal

-Sampling tubes install from front or rear of detector

-Compatible with existing accessories

[4] CONTENTS OF THE DUCT SMOKE DETECTOR KIT

1.  Sensor/power board assembly and cover(s)
2.  Three #10 sheet metal screws for mounting
3.  Drilling template
4.  One sampling tube end cap
5.  One plastic exhaust tube
NOTE: A sampling tube must be ordered to complete the installation. It must 
be the correct length for the width of the duct where it will be installed. 
See Table 1 on page 3 to determine the inlet tube required for different duct 
widths. 

[5] DETECTOR INSTALLATION

[5.1] VERIFY AIR FLOW DIRECTION AND VELOCITY

Model DUCTSD240 detectors are designed to be used in air handling systems 
with air velocities of 100 to 4000 feet per minute. Duct widths from 6 inches to 
12 feet can be accommodated. Be sure to check engineering specifications to 
ensure that the air velocity in the duct falls within these parameters. If neces-
sary, use a velocity meter (anemometer) to check the air velocity in the duct.

[5.2] DETERMINE MOUNTING LOCATION AND CONFIGURATION

On ducts wider than 18 inches it is recommended that the detector be 
mounted downstream of a bend, obstruction in the duct, or the supply or 
return air inlet.

Exception:

 Installation of duct detectors can be on or within a commercial 

packaged rooftop heating and air-conditioning system, fire/smoke dampers 
and economizers. They may be mounted in either the supply and/or return air 
section as determined by local code.
Once a suitable location is selected, determine if the detector is to be mounted 
in a side-by-side “rectangular” configuration or a top-over-bottom “square” 
configuration as shown in 

Figure 2

. If mounting in the square configuration, 

remove the rear attachment pin, rotate the unit at the hinge, and replace the 
pin into the new attachment hole as shown in 

Figure 2

. Do NOT remove the 

hinge screw during this process. Final installation approval shall be based 
upon passing section 7.2.

FIGURE 2:

REMOVE PIN AND PIVOT

DETECTOR AS SHOWN BELOW.

REPLACE PIN TO

SECURE DETECTOR

IN PLACE.

H0638-00

[5.3] DRILL THE MOUNTING HOLES

Remove the paper backing from the mounting template supplied. Affix the 
template to the duct at the desired mounting location. Make sure the template 
lies flat and smooth on the duct. 

[5.3.1] FOR RECTANGULAR SIDE-BY-SIDE MOUNTING CONFIGURATION:

Center punch at (4) target centers: (2) “A” for sampling tubes and (2) “B” for 
the rectangular configuration mounting tabs as shown on mounting template. 
Drill pilot holes at target “A” centers and cut two 1.375 inch diameter holes 
using a 1

3

/

8

 inch hole saw or punch. Drill .156 inch diameter holes using a 

5

/

32

 

inch drill at target “B” centers.

[5.3.2] FOR SQUARE TOP-OVER-BOTTOM MOUNTING CONFIGURATION 

OR D4S SENSOR COMPONENT MOUNTING:

Center punch at (4) target centers: (2) “A” for sampling tubes and (2) “C” for 
the square configuration mounting tabs as shown on mounting template. Drill 
pilot holes at target “A” centers and cut two 1.375 inch diameter holes using 
a 1

3

/

8

 inch hole saw or punch. Drill .156 inch diameter holes using a 

5

/

32

 inch 

drill at target “C” centers. If desired, drill an additional .156 inch hole at the 
location of one of the mounting tabs on the lower housing.

[5.4] SECURE THE DUCT DETECTOR TO THE DUCT

Use two (rectangular configuration) or three (square configuration) of the pro-
vided sheet metal screws to screw the duct detector to the duct.

CAUTION:

 Do not overtighten the screws.

[2] FIGURE 1. EXPLODED VIEW OF DUCT SMOKE DETECTOR COMPONENTS:

H0637-00

  

I56-4260-002R 

 

 06-10

Содержание DUCTSD240

Страница 1: ...5 sec max Alarm response time 15 sec 15 sec 15 sec Sensitivity Test See detector label See detector label See detector label Current Requirements Using No Accessories Max standby current 21 mA 24 VDC 65 mA RMS 24VAC 60Hz 10 mA RMS 240 VAC 60 Hz Max alarm current 65 mA 24 VDC 135 mA RMS 24 VAC 60 Hz 18 mA RMS 240 VAC 60 Hz CONTACT RATINGS Alarm initiation contacts SPST 2 0A 30 VDC resistive Alarm a...

Страница 2: ...hese parameters If neces sary use a velocity meter anemometer to check the air velocity in the duct 5 2 DETERMINE MOUNTING LOCATION AND CONFIGURATION On ducts wider than 18 inches it is recommended that the detector be mounted downstream of a bend obstruction in the duct or the supply or return air inlet Exception Installation of duct detectors can be on or within a commercial packaged rooftop hea...

Страница 3: ...ct Plug the end with the end cap and tape closed any holes in the protrud ing section of tube Be sure to seal the duct where the tube protrudes FIGURE 4 DETECTOR 3 4 HOLE 12 1 4 2 H0215 00 NOTE Air currents inside the duct may cause excessive vibration especially when the longer sampling tubes are used In these cases a 3 inch floor flange available at most plumbing supply stores may be used to fas...

Страница 4: ... WIRE DUCT SMOKE DETECTORS CAUTION Do not loop wire under terminals when wiring detectors Break wire runs to provide system supervision of connections 24VAC DC 9 10 AUXILIARY CONTACTS FOR FAN SHUTDOWN ETC NOTE 2 16 6 17 8 18 7 N O C N C N O C N C 16 6 17 8 18 7 N O C N C N O C N C SUPERVISORY CONTACTS NOTE 3 24V 9 10 AUXILIARY CONTACTS FOR FAN SHUTDOWN ETC NOTE 2 SUPERVISORY CONTACTS NOTE 3 SUP N ...

Страница 5: ... REMEMBER TO REMOVE THE PLUGS AFTER THIS TEST OR THE DETECTOR WILL NOT FUNCTION PROPERLY FIGURE 8 MULTIPLE FAN SHUTDOWN INTERCONNECTION OF DUCTSD240 TO D4240 D4240 D4240 DUCTSD240 DUCTSD240 DUCTSD240 H0640 01 H0639 01 ALARM TEST OPTIONS TEST METHOD DETECTOR RESET Test Reset Button Press and hold test reset button for at least 7 seconds Press and release the test reset button Magnet Test M02 04 00 ...

Страница 6: ...If the smoke has cleared the unit will go into STANDBY otherwise the unit will remain in ALARM 12 DETECTOR CLEANING PROCEDURES Notify the proper authorities that the smoke detector system is undergoing maintenance and that the system will temporarily be out of service Disable the zone or system undergoing maintenance to prevent unwanted alarms and possible dispatch of the fire department 12 1 DETE...

Страница 7: ... green blink pattern exists until unit either enters Alarm or reverts to Standby within approximately 60 seconds Supervisory relay Terminals 3 and 14 are closed Alarm Relay Terminals 4 and 5 are open Aux Relay does not switch states Terminals 6 and 16 are closed Terminals 8 and 18 are closed Trouble Red Blink every 5 seconds Amber Solid Supervisory relay Terminals 3 and 14 are open Alarm Relay Ter...

Страница 8: ...tion number send defective units postage prepaid to Honeywell 12220 Rojas Drive Suite 700 El Paso TX 79936 USA Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to replace units which are found to be defective because of damage unreasonable use modifications or alterations occurring after the date of manufacture In no case shall the ...

Отзывы: