background image

10

9

19
20

1

12

15

3

2

1

DUCTSD240

APA151

(GREEN LED) POWER

FIELD 
INSTALLED 
JUMPER

11

2

+

AUX OUT +

AUX OUT –

ALARM

R TEST

ACC +

ACC –

R RESET

7

18

8

17

6

16

14

3

13

5
4

SUP, NO
SUP, C

NOTE:

 WIRING DIAGRAM SHOWN IS FOR DUCTSD 4-WIRE DUCT 

SMOKE DETECTOR SYSTEM EQUIPPED WITHOUT A CONTROL PANEL.

NOTE:

 A TROUBLE CONDITION IS INDICATED 

BY LOSS OF GREEN LED

COMMON

(RED LED) ALARM

FIGURE 9. DETECTOR SENSOR EXPLODED VIEW:

SENSOR 

COVER

SENSING 

CHAMBER 

COVER AND 

SCREEN

SENSOR 

CHAMBER

COVER 

REMOVAL 

TABS

H0642-01

C1009-00

10

9

19
20

1

12

15

2

6

1
5

4

3

DUCTSD240

RTS151/RTS151KEY

(GREEN LED) 

POWER

(RED LED) 

ALARM

FIELD 

INSTALLED 

JUMPER

11

2

+

AUX OUT +

AUX OUT –

ALARM

R TEST

ACC +

ACC –

R RESET

7

18

8

17

6

16

14

3

13

5
4

SUP, NO
SUP, C

FOR RTS151KEY ONLY WITHOUT A CONTROL PANEL

FIELD 

INSTALLED 

JUMPERS

4.   Notify the proper authorities testing has been completed and the smoke 

detector system is back in operation.

NOTICE: If any unitary packaged air conditioning units are run during the 
drywall installation phase of any building under construction to accelerate 
the drying of joint compound, the subsequent sanding of those drywall joints 
and resulting dust may compromise the sensor heads in duct smoke detectors. 
To avoid this condition it is recommended that the sensor heads be removed 
during the construction phase. 
For additional information visit www.systemsensor.com for a detailed techni-
cal bulletin.

[13] SENSOR REPLACEMENT (PART NO. 2D51)

1.  Remove the sensor head by rotating counterclockwise.
2.  Pull gently to remove it. 
3.   To replace the sensor head, align the mounting features and rotate clock-

wise into place.

H0643-01

FIGURE 10. WIRING DIAGRAMS FOR OPTIONAL ACCESSORIES:

[11.6] DUCT CLEARING 

After an ALARM event occurs, the unit may be reset by pressing the RESET 
pushbutton. If the duct is not clear of smoke, the AUX relay will open for 20 
seconds, to allow the fans to run and clear the duct of smoke. If the smoke 
has cleared the unit will go into STANDBY, otherwise the unit will remain in 
ALARM.

[12] DETECTOR CLEANING PROCEDURES

Notify the proper authorities that the smoke detector system is undergoing 
maintenance, and that the system will temporarily be out of service. Disable 
the zone or system undergoing maintenance to prevent unwanted alarms and 
possible dispatch of the fire department.

[12.1] DETECTOR SENSOR

1.  Remove the sensor to be cleaned from the system.
2.   Remove the sensor cover by pulling outward on each of the four removal 

tabs that hold the cover in place. See 

Figure 9

.

3.   Vacuum the screen carefully without removing it. If further cleaning is 

required continue with Step 4, otherwise skip to Step 7.

4.  Remove the chamber cover/screen assembly by pulling it straight out.
5.   Use a vacuum cleaner or compressed air to remove dust and debris from 

the sensing chamber.

6.   Reinstall the chamber cover/screen assembly by sliding the edge over the 

sensing chamber. Turn until it is firmly in place.

7.   Replace the cover using the holes for the LEDs for alignment and then 

gently pushing it until it locks into place.

8.  Reinstall the detector.

[12.2] REINSTALLATION

1.  Reinstall the detector in its housing.
2.  Restore system power. 
3.  Perform Detector Check, Section 11.2.

ALARM

AUX OUT –

15

20

(+)

(–)

ALARM 

AUX OUT – 

15

20

(+)

(–)

RED

MHR/MHW 

(OPTIONAL) AUDIO 

ALERT

DUCTSD240

DUCT DETECTOR 

DUCTSD240

DUCT DETECTOR 

RA100Z(OPTION-

AL)REMOTE (LED) 

ANNUNCIATOR

H0641-01

FIGURE 11. WIRING DIAGRAM FOR DUCTSD240 TO APA151:

FIGURE 12. WIRING DIAGRAM FOR DUCTSD240 TO RTS151/RTS151KEY:

[14] OPTIONAL ACCESSORIES

[14.1] RTS151/RTS151KEY REMOTE TEST STATION

The RTS151/RTS151KEY Remote Test Station facilitates test of the alarm ca-
pability of the duct smoke detector as indicated in the RTS151/RTS151KEY 
manual. The DUCTSD240 duct smoke detector can be reset by the RTS151/
RTS151KEY. To install the RTS151/RTS151KEY, connect the device as shown in 

Figure 12

; wire runs must be limited to 25 ohms or less per interconnecting 

wire. If a system control panel is used, the panel itself may require testing.

  

I56-4260-002R 

 

 06-10

Содержание DUCTSD240

Страница 1: ...5 sec max Alarm response time 15 sec 15 sec 15 sec Sensitivity Test See detector label See detector label See detector label Current Requirements Using No Accessories Max standby current 21 mA 24 VDC 65 mA RMS 24VAC 60Hz 10 mA RMS 240 VAC 60 Hz Max alarm current 65 mA 24 VDC 135 mA RMS 24 VAC 60 Hz 18 mA RMS 240 VAC 60 Hz CONTACT RATINGS Alarm initiation contacts SPST 2 0A 30 VDC resistive Alarm a...

Страница 2: ...hese parameters If neces sary use a velocity meter anemometer to check the air velocity in the duct 5 2 DETERMINE MOUNTING LOCATION AND CONFIGURATION On ducts wider than 18 inches it is recommended that the detector be mounted downstream of a bend obstruction in the duct or the supply or return air inlet Exception Installation of duct detectors can be on or within a commercial packaged rooftop hea...

Страница 3: ...ct Plug the end with the end cap and tape closed any holes in the protrud ing section of tube Be sure to seal the duct where the tube protrudes FIGURE 4 DETECTOR 3 4 HOLE 12 1 4 2 H0215 00 NOTE Air currents inside the duct may cause excessive vibration especially when the longer sampling tubes are used In these cases a 3 inch floor flange available at most plumbing supply stores may be used to fas...

Страница 4: ... WIRE DUCT SMOKE DETECTORS CAUTION Do not loop wire under terminals when wiring detectors Break wire runs to provide system supervision of connections 24VAC DC 9 10 AUXILIARY CONTACTS FOR FAN SHUTDOWN ETC NOTE 2 16 6 17 8 18 7 N O C N C N O C N C 16 6 17 8 18 7 N O C N C N O C N C SUPERVISORY CONTACTS NOTE 3 24V 9 10 AUXILIARY CONTACTS FOR FAN SHUTDOWN ETC NOTE 2 SUPERVISORY CONTACTS NOTE 3 SUP N ...

Страница 5: ... REMEMBER TO REMOVE THE PLUGS AFTER THIS TEST OR THE DETECTOR WILL NOT FUNCTION PROPERLY FIGURE 8 MULTIPLE FAN SHUTDOWN INTERCONNECTION OF DUCTSD240 TO D4240 D4240 D4240 DUCTSD240 DUCTSD240 DUCTSD240 H0640 01 H0639 01 ALARM TEST OPTIONS TEST METHOD DETECTOR RESET Test Reset Button Press and hold test reset button for at least 7 seconds Press and release the test reset button Magnet Test M02 04 00 ...

Страница 6: ...If the smoke has cleared the unit will go into STANDBY otherwise the unit will remain in ALARM 12 DETECTOR CLEANING PROCEDURES Notify the proper authorities that the smoke detector system is undergoing maintenance and that the system will temporarily be out of service Disable the zone or system undergoing maintenance to prevent unwanted alarms and possible dispatch of the fire department 12 1 DETE...

Страница 7: ... green blink pattern exists until unit either enters Alarm or reverts to Standby within approximately 60 seconds Supervisory relay Terminals 3 and 14 are closed Alarm Relay Terminals 4 and 5 are open Aux Relay does not switch states Terminals 6 and 16 are closed Terminals 8 and 18 are closed Trouble Red Blink every 5 seconds Amber Solid Supervisory relay Terminals 3 and 14 are open Alarm Relay Ter...

Страница 8: ...tion number send defective units postage prepaid to Honeywell 12220 Rojas Drive Suite 700 El Paso TX 79936 USA Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to replace units which are found to be defective because of damage unreasonable use modifications or alterations occurring after the date of manufacture In no case shall the ...

Отзывы: