background image

[8] FIELD WIRING INSTALLATION GUIDELINES

All wiring must be installed in compliance with the National Electrical Code 
and the local codes having jurisdiction. Proper wire gauges should be used. 
The conductors used to connect smoke detectors to control panels and acces-
sory devices should be color-coded to prevent wiring mistakes. Improper con-
nections can prevent a system from responding properly in the event of a fire.

For signal wiring, (wiring between interconnected detectors or from detectors 
to auxiliary devices), it is recommended that single conductor wire be no 
smaller than 18 gauge.

Smoke detectors and alarm system control panels have specifications for al-
lowable loop resistance. Consult the control panel manufacturer’s specifica-
tions for the total loop resistance allowed for the particular control panel being 
used before wiring the detector loop.

[8.1] WIRING INSTRUCTIONS

The DUCTSD240 detector is designed for easy wiring. The housing provides a 
terminal strip with clamping plates. See 

Figure 6

 on page 4 for system wiring.

*Trouble is indicated when the Supervisory Relay, switches state-Termi-
nals 3 and 14 are open in a Trouble Condition
Causes of a Trouble Condition may be:

•  Unit loses Power
•  Cover Tamper Feature times out
•  When in “Standby” mode, the product goes into “Cover Tamper 

Violation” if the cover has been removed or improperly replaced and 
remains so for at least 7 minutes.  As soon as the cover is properly re-
seated, the product reverts to “Standby” automatically

HIGH

LOW

9 VOLT

BATTERY

9 VOLT

BATTERY

9 VOLT

BATTERY

TO SAMPLING TUBE
TO EXHAUST TUBE

DIFFERENTIAL 

PRESSURE 

TRANSMITTER 

MODEL #607-01

15 TO 36 

VDC SUPPLY

1000 OHM 5%

1 WATT RESISTOR

VOLT METER FLUKE 

MODEL 87 OR 

EQUIVALENT

+

FIGURE 5. PROCEDURE FOR VERIFYING AIR FLOW LESS THAN 500 FPM:

H0163-01

FIGURE 6. SYSTEM WIRING DIAGRAM FOR 4-WIRE DUCT SMOKE DETECTORS:

CAUTION

Do not loop wire under terminals when wiring detectors. Break wire runs to provide system supervision of connections.

24VAC/DC

9

10

AUXILIARY CONTACTS

FOR FAN SHUTDOWN, ETC. (NOTE 2)

16

6

17

8

18

7

N.O.

C.

N.C.

N.O.

C.

N.C.

16

6

17

8

18

7

N.O.

C.

N.C.

N.O.

C.

N.C.

SUPERVISORY CONTACTS

(NOTE 3)

24V

9

10

AUXILIARY CONTACTS

FOR FAN SHUTDOWN, ETC. (NOTE 2)

SUPERVISORY CONTACTS

(NOTE 3)

SUP N.O.

SUP C

SUP C

SUP N.O.

4

5

ALARM

INITIATION

CONTACTS

(NOTE 4)

4

5

ALARM

INITIATION

CONTACTS

(NOTE 4)

ALARM

INITIATION

LOOP

UL/FM LISTED

4-WIRE

CONTROL PANEL

+

240

VAC

240

VAC

OR

OR

AUX A

AUX B

AUX A

AUX B

ALARM N.O.

ALARM N.O.

ALARM C

ALARM C

3

3

14

14

FIRST DETECTOR IN THE LOOP

POWER INPUTS (NOTE 1)

POWER INPUTS (NOTE 1)

LAST DETECTOR IN THE LOOP

EOL RESISTOR 

SPECIFIED BY 

PANEL 

MANUFACTURER

NOTE 1:

 24V Power Inputs accept 24VDC of either polarity or 24VAC 50-60Hz. 

120VAC Power Inputs accept only 120VAC 50-60Hz. Connect power source to 
appropriate terminals of each detector. See specifications for additional power 
supply information.

NOTE 2:

 Auxiliary contacts shown in standby position. Contacts switch dur-

ing alarm as indicated by arrows. Auxiliary contacts are not to be used for 
connection to the control panel. See specifications for contact ratings.

NOTE 3:

 Supervisory contacts shown in standby position. Open contacts indi-

cate a trouble condition to the panel. See specifications for contact ratings.

H0558-12

[9] DETECTOR STATUS INDICATION

Detector Status is indicated by the sensor LEDs. Refer to Table 3 on page 7 for 
more details.

Note: The power board contains a diagnostic status indicator LED. However, 
this LED is not visible under normal operating circumstances.

[10] INTERCONNECTION (MULTIPLE FAN SHUT DOWN)

When using the interconnect feature, an alarm from an initiating device will 
switch the Aux Relays on the other devices interconnected.

NOTE 4:

 Alarm Initiation contacts shown in standby position. Closed contacts 

indicate an alarm condition to the panel. See specifications for contact ratings.

  

I56-4260-002R 

 

 06-10

Содержание DUCTSD240

Страница 1: ...5 sec max Alarm response time 15 sec 15 sec 15 sec Sensitivity Test See detector label See detector label See detector label Current Requirements Using No Accessories Max standby current 21 mA 24 VDC 65 mA RMS 24VAC 60Hz 10 mA RMS 240 VAC 60 Hz Max alarm current 65 mA 24 VDC 135 mA RMS 24 VAC 60 Hz 18 mA RMS 240 VAC 60 Hz CONTACT RATINGS Alarm initiation contacts SPST 2 0A 30 VDC resistive Alarm a...

Страница 2: ...hese parameters If neces sary use a velocity meter anemometer to check the air velocity in the duct 5 2 DETERMINE MOUNTING LOCATION AND CONFIGURATION On ducts wider than 18 inches it is recommended that the detector be mounted downstream of a bend obstruction in the duct or the supply or return air inlet Exception Installation of duct detectors can be on or within a commercial packaged rooftop hea...

Страница 3: ...ct Plug the end with the end cap and tape closed any holes in the protrud ing section of tube Be sure to seal the duct where the tube protrudes FIGURE 4 DETECTOR 3 4 HOLE 12 1 4 2 H0215 00 NOTE Air currents inside the duct may cause excessive vibration especially when the longer sampling tubes are used In these cases a 3 inch floor flange available at most plumbing supply stores may be used to fas...

Страница 4: ... WIRE DUCT SMOKE DETECTORS CAUTION Do not loop wire under terminals when wiring detectors Break wire runs to provide system supervision of connections 24VAC DC 9 10 AUXILIARY CONTACTS FOR FAN SHUTDOWN ETC NOTE 2 16 6 17 8 18 7 N O C N C N O C N C 16 6 17 8 18 7 N O C N C N O C N C SUPERVISORY CONTACTS NOTE 3 24V 9 10 AUXILIARY CONTACTS FOR FAN SHUTDOWN ETC NOTE 2 SUPERVISORY CONTACTS NOTE 3 SUP N ...

Страница 5: ... REMEMBER TO REMOVE THE PLUGS AFTER THIS TEST OR THE DETECTOR WILL NOT FUNCTION PROPERLY FIGURE 8 MULTIPLE FAN SHUTDOWN INTERCONNECTION OF DUCTSD240 TO D4240 D4240 D4240 DUCTSD240 DUCTSD240 DUCTSD240 H0640 01 H0639 01 ALARM TEST OPTIONS TEST METHOD DETECTOR RESET Test Reset Button Press and hold test reset button for at least 7 seconds Press and release the test reset button Magnet Test M02 04 00 ...

Страница 6: ...If the smoke has cleared the unit will go into STANDBY otherwise the unit will remain in ALARM 12 DETECTOR CLEANING PROCEDURES Notify the proper authorities that the smoke detector system is undergoing maintenance and that the system will temporarily be out of service Disable the zone or system undergoing maintenance to prevent unwanted alarms and possible dispatch of the fire department 12 1 DETE...

Страница 7: ... green blink pattern exists until unit either enters Alarm or reverts to Standby within approximately 60 seconds Supervisory relay Terminals 3 and 14 are closed Alarm Relay Terminals 4 and 5 are open Aux Relay does not switch states Terminals 6 and 16 are closed Terminals 8 and 18 are closed Trouble Red Blink every 5 seconds Amber Solid Supervisory relay Terminals 3 and 14 are open Alarm Relay Ter...

Страница 8: ...tion number send defective units postage prepaid to Honeywell 12220 Rojas Drive Suite 700 El Paso TX 79936 USA Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to replace units which are found to be defective because of damage unreasonable use modifications or alterations occurring after the date of manufacture In no case shall the ...

Отзывы: