background image

D400-73-00                                                                                              7                                                                                            I56-2294-03R

Figure 7. Wiring Diagram

BEAM1224

LISTED PANEL

EOL

RESISTOR

Class

A

Return

Loop

T1-1

Power+

Ini

Initiating–

Power–

Power IN+

Power IN–

Alarm COM

Trouble COM

Alarm NO

Power OUT+

Power OUT–

Alarm COM

Trouble NC

Alarm NO

T1-2

T4-2

T4-1

T3-2

T1-3

T1-4

T4-4

T4-3

T3-1

T2-2
T2-1
T3-3
T2-3
T2-4

AUX (–)
Remote Alarm Output
Remote Trouble Output
Test Input
Reset Input

BEAM1224

T1-1

Power IN+

Power IN–

Alarm COM

Trouble COM

Alarm NO

Power OUT+

Power OUT–

Alarm COM

Trouble NC

Alarm NO

T1-2

T4-2

T4-1

T3-2

T1-3

T1-4

T4-4

T4-3

T3-1

T2-2
T2-1
T3-3
T2-3
T2-4

AUX (–)
Remote Alarm Output
Remote Trouble Output
Test Input
Reset Input

Listed EOL Power
Supervision Module
(Only required if other
sensors are on the
same loop)

C0272-00

Figure 8. Wiring Diagram (RTS451)

RTS451/KEY

BEAM1224

Pin 1

Remote Alarm Out

T2-1

T2-2

T2-4
T2-3

AUX (–)
Reset Input

Test Input

See RTS451/KEY Installation Instructions
for electrical ratings of RTS451/KEY.

Pin 2

Pin 4

Pin 3

Pin 5

C0273-00

Figure 9. Wiring Diagram (Remote LEDs)

BEAM1224/S

Alarm

Signal
Circuit

(Note 1)

T2-1

T3-3

T2-2

Yellow

Note 1:  See electrical ratings section of this

manual for circuit output ratings.

Red

Trouble

Signal
Circuit

(Note 1)

C0319-01

box be sure to leave enough wire in the box to connect to the 
terminal blocks. (Approximately 9

 [23cm) of wire outside of 

the junction box will be required for proper installation). All 
wiring to the detector is done via pluggable terminal blocks. 
In order to properly make electrical connections strip approxi-
mately 

1

/

4

 (6mm) of insulation from the end of the wire, slid-

ing the bare end of the wire under the clamping plate screw. 

Figure 6 shows all the wiring connections to the transmitter/
receiver unit. Figure 7 shows the proper wiring diagram for 
either class A or class B operation. Figure 8 shows the con-
nections that are necessary when using one of the optional 
remote test stations (RTS451 or RTS451KEY). Figure 9 shows 
the remote outputs for trouble and alarm.

Содержание BEAM1224

Страница 1: ...only Sensitivity Filter Incremental scale on reflector Local Alarm Test Switch Local Alarm Reset Switch Remote Test and Reset Switch Capability compatible with RTS451 RTS451KEY Indicators Alarm Remote Output Local LED red Trouble Remote Output Local LED yellow Blink Pattern Indicates Trouble Diagnostics Normal Operation Local LED flashing green once every 5 sec Alignment Aids Optical Gunsight coar...

Страница 2: ...ion The alarm signal latches and can be reset by a momentary power interruption by using the remote reset input to the detector if using the remote test reset station model RTS451 or with the local reset button located on the detector The local reset button is accessible by removing the outer paintable trim ring The yellow LED will blink in specific patterns to provide a diag nostic aid when diagn...

Страница 3: ...BEAMMMK allows System Sensor reflected beam detec tors and reflectors to be mounted to either a vertical wall or the ceiling The kit allows for additional alignment range in cases where the detector and reflector cannot be mounted within 10 of each other The kit includes the hardware necessary to mount either a single transmitter receiver unit or a single reflector To mount the transmitter receive...

Страница 4: ...nature of the contents of the room being protected do not warrant greater protection or closer spacing In a room with a smooth ceiling detectors should be spaced between 30 and 60 feet 9 1 to 18 3m One half that spacing between the beam and the sidewall may be used as a guide See Figure 1 The beam detector can be mounted with the transmitter receiver on one wall and the reflector on the opposite w...

Страница 5: ...ons for surface mounting instructions The transmitter receiver unit can be mounted to the wall using the supplied drilling template see Appendix II The detector base has 4 primary mounting keyholes one in each corner of the base All four hole locations should be used to provide a secure mounting The outer housing of the beam detector is held to the base using four screws In order to mount the dete...

Страница 6: ...s cannot be avoided some specific installation practices can help to mini mize the effects of the glass These practices include avoid penetration of multiple panes of glass position the glass so that it is not perpendicular to the line of sight between the detector and the reflector A minimum of 10 off perpen dicular should be considered and make certain that the glass is smooth clear and mounted ...

Страница 7: ...stallation Instructions for electrical ratings of RTS451 KEY Pin 2 Pin 4 Pin 3 Pin 5 C0273 00 Figure 9 Wiring Diagram Remote LEDs BEAM1224 S Alarm Signal Circuit Note 1 T2 1 T3 3 T2 2 Yellow Note 1 See electrical ratings section of this manual for circuit output ratings Red Trouble Signal Circuit Note 1 C0319 01 box be sure to leave enough wire in the box to connect to the terminal blocks Approxim...

Страница 8: ...r more details Insure that both the detector and reflector are mounted within their operational parameters for off axis angles See Mounting Instructions for more details Disable the zone or system to prevent unwanted alarms before applying power Insure power to the detector is ON You are now ready to begin the alignment procedure Step 1 Coarse Alignment Refer to Figures 11 and 12 for this step 1 I...

Страница 9: ...e alignment switch to complete the fine adjustment step The digital display readout will turn OFF and the yellow LED will remain ON NOTE It may not be possible to achieve a value near 90 on the display during the last adjustment iteration The final value of the display will not likely be near 90 This is normal It is due to the detector reduc ing its electronic gain each time a value of 90 is achie...

Страница 10: ...llow LED see Appendix I If the detector does not enter the trouble condition there is a problem with the installation refer to the troubleshoot ing section in Appendix I for further assistance 2 Complete a sensitivity test of the detector Refer to the Sensitivity Testing section of this manual for the appro priate procedure 3 If the orange sticky paper was used to aid in the loca tion of the refle...

Страница 11: ...cally adjust its sensitivity using advanced software algorithms to select the optimum sensitivity for the environment The sensitivity will be continuously adjusted within the ranges specified in the chart above Sensitivity Total obscuration can be converted to percent per foot assuming uniform smoke density for the entire length of the beam The chart below converts total obscuration to percent per...

Страница 12: ... procedure is successful repeat the test pro cedure If the detector still fails the test it should be returned B Test Switch The detector can be tested using the local test switch on the transmitter receiver unit or remotely using the remote test station The remote test station RTS451 or RTS451KEY can be used with the BEAM1224 BEAM1224S beam smoke detec tor Follow instructions included with the te...

Страница 13: ...tector notify the proper authorities that the smoke detector system is undergoing maintenance and therefore the sys tem will be temporarily out of service Disable the zone or system undergoing maintenance to prevent unwanted alarms 1 Carefully clean the outer housing lens face A damp soft cloth with a mild soap may be used Avoid products with solvents or ammonia 2 Carefully clean the reflector A d...

Страница 14: ... in the pathway Trouble Beam Blockage Initial Response Off 4 Quick Blinks Off Off Beam Blockage Open OFF Open Remove blockage Faulty unit Trouble Beam Blockage Long Term Response On 4 Quick Blinks Off Off Beam Blockage Close OFF Open Remove blockage Faulty unit Initialization Power on Off Blink until complete Blink Off Apply Power from discharged state Open OFF Close Initialization alignment exit ...

Страница 15: ...Appendix II Detector Drilling Template 4 345 6 190 Scale 1 1 D400 73 00 15 I56 2294 03R ...

Страница 16: ...D400 73 00 16 I56 2294 03R ...

Страница 17: ...Appendix III Reflector Drilling Template Scale 1 1 5 512 140mm 8 465 215mm D400 73 00 17 I56 2294 03R ...

Страница 18: ...age is caused by the Company s neg ligence or fault Some states do not allow the exclusion or limitation of incidental or consequential damages so the above limitation or exclusion may not apply to you This Warranty gives you specific legal rights and you may also have other rights which vary from state to state Three Year Limited Warranty FCC Statement This device complies with part 15 of the FCC...

Отзывы: