background image

D400-73-00                                                                                             13                                                                                           I56-2294-03R

If the detector fails this test several steps should be taken 
to determine if the detector is faulty or simply needs to be 
re-adjusted before returning the unit for repair. These steps 
include:

1.  Verify  all  wiring  connections  and  appropriate  power  is 

applied to the detector.

2.  Verify that the optical line of sight is free from obstruc-

tions and reflective objects.

3.  Apply  the  maintenance  procedure  in  this  manual. 

Repeat  the  test  procedure.  If  the  detector  still  fails  the 
test procedure proceed with step 4.

4.  Repeat  the  alignment  procedure  in  this  manual.  If  the 

alignment  procedure  is  successful  repeat  the  test  pro-
cedure.  If  the  detector  still  fails  the  test  it  should  be 
returned.

Maintenance

NOTE:

   Before  cleaning  the  detector,  notify  the  proper 

authorities  that  the  smoke  detector  system  is 
undergoing  maintenance,  and  therefore  the  sys-
tem will be temporarily out of service. Disable the 
zone or system undergoing maintenance to prevent 
unwanted alarms.

1.  Carefully clean the outer housing lens face. A damp soft 

cloth  with  a  mild  soap  may  be  used.  Avoid  products 
with solvents or ammonia.

2.  Carefully  clean  the  reflector.  A  damp  soft  cloth  with  a 

mild soap may be used. Avoid products with solvents or 
ammonia.

3.  Notify the proper authorities that the system is back on 

line.

Painting

The outer aesthetic ring may be painted using a spray or 
brush type paint of appropriate type. See specification sec-
tion of this manual for paint types.

NOTE:

  Never paint the flat lens surface of the outer housing.

Special Note Regarding Smoke Detector Guards

Smoke  detectors  are  not  to  be  used  with  detector  guards 
unless the combination has been evaluated and found suit-
able for that purpose.

Содержание BEAM1224

Страница 1: ...only Sensitivity Filter Incremental scale on reflector Local Alarm Test Switch Local Alarm Reset Switch Remote Test and Reset Switch Capability compatible with RTS451 RTS451KEY Indicators Alarm Remote Output Local LED red Trouble Remote Output Local LED yellow Blink Pattern Indicates Trouble Diagnostics Normal Operation Local LED flashing green once every 5 sec Alignment Aids Optical Gunsight coar...

Страница 2: ...ion The alarm signal latches and can be reset by a momentary power interruption by using the remote reset input to the detector if using the remote test reset station model RTS451 or with the local reset button located on the detector The local reset button is accessible by removing the outer paintable trim ring The yellow LED will blink in specific patterns to provide a diag nostic aid when diagn...

Страница 3: ...BEAMMMK allows System Sensor reflected beam detec tors and reflectors to be mounted to either a vertical wall or the ceiling The kit allows for additional alignment range in cases where the detector and reflector cannot be mounted within 10 of each other The kit includes the hardware necessary to mount either a single transmitter receiver unit or a single reflector To mount the transmitter receive...

Страница 4: ...nature of the contents of the room being protected do not warrant greater protection or closer spacing In a room with a smooth ceiling detectors should be spaced between 30 and 60 feet 9 1 to 18 3m One half that spacing between the beam and the sidewall may be used as a guide See Figure 1 The beam detector can be mounted with the transmitter receiver on one wall and the reflector on the opposite w...

Страница 5: ...ons for surface mounting instructions The transmitter receiver unit can be mounted to the wall using the supplied drilling template see Appendix II The detector base has 4 primary mounting keyholes one in each corner of the base All four hole locations should be used to provide a secure mounting The outer housing of the beam detector is held to the base using four screws In order to mount the dete...

Страница 6: ...s cannot be avoided some specific installation practices can help to mini mize the effects of the glass These practices include avoid penetration of multiple panes of glass position the glass so that it is not perpendicular to the line of sight between the detector and the reflector A minimum of 10 off perpen dicular should be considered and make certain that the glass is smooth clear and mounted ...

Страница 7: ...stallation Instructions for electrical ratings of RTS451 KEY Pin 2 Pin 4 Pin 3 Pin 5 C0273 00 Figure 9 Wiring Diagram Remote LEDs BEAM1224 S Alarm Signal Circuit Note 1 T2 1 T3 3 T2 2 Yellow Note 1 See electrical ratings section of this manual for circuit output ratings Red Trouble Signal Circuit Note 1 C0319 01 box be sure to leave enough wire in the box to connect to the terminal blocks Approxim...

Страница 8: ...r more details Insure that both the detector and reflector are mounted within their operational parameters for off axis angles See Mounting Instructions for more details Disable the zone or system to prevent unwanted alarms before applying power Insure power to the detector is ON You are now ready to begin the alignment procedure Step 1 Coarse Alignment Refer to Figures 11 and 12 for this step 1 I...

Страница 9: ...e alignment switch to complete the fine adjustment step The digital display readout will turn OFF and the yellow LED will remain ON NOTE It may not be possible to achieve a value near 90 on the display during the last adjustment iteration The final value of the display will not likely be near 90 This is normal It is due to the detector reduc ing its electronic gain each time a value of 90 is achie...

Страница 10: ...llow LED see Appendix I If the detector does not enter the trouble condition there is a problem with the installation refer to the troubleshoot ing section in Appendix I for further assistance 2 Complete a sensitivity test of the detector Refer to the Sensitivity Testing section of this manual for the appro priate procedure 3 If the orange sticky paper was used to aid in the loca tion of the refle...

Страница 11: ...cally adjust its sensitivity using advanced software algorithms to select the optimum sensitivity for the environment The sensitivity will be continuously adjusted within the ranges specified in the chart above Sensitivity Total obscuration can be converted to percent per foot assuming uniform smoke density for the entire length of the beam The chart below converts total obscuration to percent per...

Страница 12: ... procedure is successful repeat the test pro cedure If the detector still fails the test it should be returned B Test Switch The detector can be tested using the local test switch on the transmitter receiver unit or remotely using the remote test station The remote test station RTS451 or RTS451KEY can be used with the BEAM1224 BEAM1224S beam smoke detec tor Follow instructions included with the te...

Страница 13: ...tector notify the proper authorities that the smoke detector system is undergoing maintenance and therefore the sys tem will be temporarily out of service Disable the zone or system undergoing maintenance to prevent unwanted alarms 1 Carefully clean the outer housing lens face A damp soft cloth with a mild soap may be used Avoid products with solvents or ammonia 2 Carefully clean the reflector A d...

Страница 14: ... in the pathway Trouble Beam Blockage Initial Response Off 4 Quick Blinks Off Off Beam Blockage Open OFF Open Remove blockage Faulty unit Trouble Beam Blockage Long Term Response On 4 Quick Blinks Off Off Beam Blockage Close OFF Open Remove blockage Faulty unit Initialization Power on Off Blink until complete Blink Off Apply Power from discharged state Open OFF Close Initialization alignment exit ...

Страница 15: ...Appendix II Detector Drilling Template 4 345 6 190 Scale 1 1 D400 73 00 15 I56 2294 03R ...

Страница 16: ...D400 73 00 16 I56 2294 03R ...

Страница 17: ...Appendix III Reflector Drilling Template Scale 1 1 5 512 140mm 8 465 215mm D400 73 00 17 I56 2294 03R ...

Страница 18: ...age is caused by the Company s neg ligence or fault Some states do not allow the exclusion or limitation of incidental or consequential damages so the above limitation or exclusion may not apply to you This Warranty gives you specific legal rights and you may also have other rights which vary from state to state Three Year Limited Warranty FCC Statement This device complies with part 15 of the FCC...

Отзывы: