NOTE:
If the outer aesthetic ring has been painted insure
that the paint is completely dry before proceeding
with this step.
Step 4. Final Verification
This step is required to insure the detector has been setup
correctly and will detect smoke at the proper sensitivity
level.
1. With the detector functioning (indicated by the green
LED blinking), completely block the reflector with an
opaque material. (Due to the high optical efficiency of
the reflector the selection of the opaque material used
to block the reflector is not critical. Acceptable materials
include, but aren’t limited to, this manual or the card-
board packaging inserts.) See Figure 14. The detector
should enter the trouble condition (indicated by the
fault relay and the yellow LED (see Appendix I). If the
detector does not enter the trouble condition there is a
problem with the installation refer to the troubleshoot-
ing section in Appendix I for further assistance.
2. Complete a sensitivity test of the detector. Refer to the
Sensitivity Testing section of this manual for the appro-
priate procedure.
3. If the orange sticky paper was used to aid in the loca-
tion of the reflector in the alignment mirror it should be
removed now. It is no longer necessary.
Congratulations. You have completed the final installation
and alignment procedure.
Figure 10. Switch Locations
ALIGNMENT
SENSITIVITY
TEST
RESET
C0274-00
Figure 11. Alignment Adjustment Locations
ALIGNMENT MIRROR
ALIGNMENT GUNSIGHT
DIGITAL SIGNAL
STRENGTH
READOUT
HORIZONTAL
ADJUSTMENT
VERTICAL
ADJUSTMENT
OPTICS
LOCK-DOWN
SCREWS
ALIGNMENT
POSITION
INDICATOR
C0264-00
Figure 12. Coarse Alignment Procedure
EYE
REFLECTOR
C0625-00
D400-73-00 10 I56-2294-03R