background image

flexibility of mounting locations and large coverage area of 
projected type beam detectors often the conditions above 
can be addressed or minimized.

Some  examples  of  applications  for  beam  detectors  might 
include freezers, aircraft hangars, cold storage warehouses, 
shipping  warehouses,  enclosed  parking  facilities,  sporting 
arenas and stadiums, concert halls, barns, or stables. Some 
of  these  environments  might  be  considered  to  hostile  for 
spot-type  smoke  detectors.  If  the  environment  is  consid-
ered to be hostile then the colder alarm threshold settings 
should be used.

Before  installing  the  transmitter/receiver  unit  or  reflector 
in these types of applications special consideration should 
be given to insure proper operation of the beam detector. 
The beam detector should not be installed in environments 
where there is no temperature control and condensation or 
icing is likely. Condensation or icing of the reflector surface 
or  the  outer  surface  of  the  transmitter/receiver  unit  will 
obscure the light beam resulting in a false alarm. If elevated 
humidity levels and rapidly changing temperatures can be 
expected then condensation will likely form and the appli-
cation  should  not  be  considered  acceptable  for  the  beam 
detector.  The  beam  detector  should  not  be  installed  in 
locations where the transmitter/receiver unit, the reflector, 
or the optical pathway between them may be exposed to 
outdoor conditions such as rain, snow, sleet, or fog. These 
conditions will impair the proper operation of the detector 
and must be avoided.

Approved Accessories

The following accessories can be purchased separately for 
use with this beam detector.

BEAMLRK

The BEAMLRK allows System Sensor reflected beam detec-
tors to be installed at separations between 230 and 328 feet 
(70 to 100 meters). At these distances, four 8

″×

8

 reflectors 

must  be  used  to  provide  enough  reflected  infrared  light. 
This  kit  includes  3  additional  reflectors  with  new  test 
scale legends. The reflector included with the transmitter/
receiver unit is the fourth reflector to be used. This kit is 
not compatible with the multi-mount kit (BEAMMMK).

BEAMMMK

The BEAMMMK allows System Sensor reflected beam detec-
tors and reflectors to be mounted to either a vertical wall or 
the ceiling. The kit allows for additional alignment range in 
cases where the detector and reflector cannot be mounted 
within  10°  of  each  other.  The  kit  includes  the  hardware 
necessary to mount either a single transmitter/receiver unit 
or a single reflector. (To mount the transmitter/receiver the 
surface mount kit, BEAMSMK, must also be used). If the 
transmitter/receiver  and  the  reflector  require  additional 

alignment range two kits are required. The kit is not com-
patible with the long-range reflector kit (BEAMLRK). 

BEAMSMK

The BEAMSMK allows System Sensor reflected beam detec-
tors to be mounted when surface wiring is used. This kit 
must be used when mounting the transmitter/receiver unit 
with the multi-mount kit (BEAMMMK).

BEAMHK

The BEAMHK allows the transmitter/receiver unit to oper-
ate  in  environments  prone  to  the  formation  of  condensa-
tion.  Condensation  forming  on  the  beam  detector  unit 
may result in trouble or false alarm conditions. BEAMHK 
will lessen the likelihood of condensation by maintaining 
the  unit  at  a  temperature  that  is  slightly  higher  than  the 
surrounding  air.  Please  refer  to  the  BEAMHK  installation 
manual for operation instructions.

BEAMHKR

The BEAMHKR allows the reflector to operate in environ-
ments prone to the formation of condensation. Condensation 
forming on the reflector may result in trouble or false alarm 
conditions. BEAMHKR will lessen the likelihood of conden-
sation by maintaining the reflector at a temperature that is 
slightly higher than surrounding air. The kit requires a 24V 
power supply. When used with the long-range reflector kit 
(BEAMLKR),  it  is  necessary  to  purchase  and  install  four 
BEAMHKR kits. Please refer to the BEAMHKR installation 
manual for operation instructions.

RTS451/KEY

The  remote  test  accessory,  RTS451/KEY  allows  for  the 
beam  detector  to  be  tested  remotely.  The  test  accessory 
provides test and reset functions and green and red LED’s 
that mimic the LED’s on the detector.

Parts List

Description 

Quantity

Transmitter/Receiver Unit . . . . . . . . . . . . . . . . . . .  1
Paintable Trim Ring . . . . . . . . . . . . . . . . . . . . . . . .  1
Reflector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  1
Plug-in Terminal Blocks . . . . . . . . . . . . . . . . . . . . .  4
Instruction Manual . . . . . . . . . . . . . . . . . . . . . . . .  1
Orange Sticky Paper. . . . . . . . . . . . . . . . . . . . . . . .  1

Parts Diagram (not to scale)

D400-73-00                                                                                              3                                                                                            I56-2294-03R

Terminal Block

Paintable
Trim Ring

C0306-00

Содержание BEAM1224

Страница 1: ...only Sensitivity Filter Incremental scale on reflector Local Alarm Test Switch Local Alarm Reset Switch Remote Test and Reset Switch Capability compatible with RTS451 RTS451KEY Indicators Alarm Remote Output Local LED red Trouble Remote Output Local LED yellow Blink Pattern Indicates Trouble Diagnostics Normal Operation Local LED flashing green once every 5 sec Alignment Aids Optical Gunsight coar...

Страница 2: ...ion The alarm signal latches and can be reset by a momentary power interruption by using the remote reset input to the detector if using the remote test reset station model RTS451 or with the local reset button located on the detector The local reset button is accessible by removing the outer paintable trim ring The yellow LED will blink in specific patterns to provide a diag nostic aid when diagn...

Страница 3: ...BEAMMMK allows System Sensor reflected beam detec tors and reflectors to be mounted to either a vertical wall or the ceiling The kit allows for additional alignment range in cases where the detector and reflector cannot be mounted within 10 of each other The kit includes the hardware necessary to mount either a single transmitter receiver unit or a single reflector To mount the transmitter receive...

Страница 4: ...nature of the contents of the room being protected do not warrant greater protection or closer spacing In a room with a smooth ceiling detectors should be spaced between 30 and 60 feet 9 1 to 18 3m One half that spacing between the beam and the sidewall may be used as a guide See Figure 1 The beam detector can be mounted with the transmitter receiver on one wall and the reflector on the opposite w...

Страница 5: ...ons for surface mounting instructions The transmitter receiver unit can be mounted to the wall using the supplied drilling template see Appendix II The detector base has 4 primary mounting keyholes one in each corner of the base All four hole locations should be used to provide a secure mounting The outer housing of the beam detector is held to the base using four screws In order to mount the dete...

Страница 6: ...s cannot be avoided some specific installation practices can help to mini mize the effects of the glass These practices include avoid penetration of multiple panes of glass position the glass so that it is not perpendicular to the line of sight between the detector and the reflector A minimum of 10 off perpen dicular should be considered and make certain that the glass is smooth clear and mounted ...

Страница 7: ...stallation Instructions for electrical ratings of RTS451 KEY Pin 2 Pin 4 Pin 3 Pin 5 C0273 00 Figure 9 Wiring Diagram Remote LEDs BEAM1224 S Alarm Signal Circuit Note 1 T2 1 T3 3 T2 2 Yellow Note 1 See electrical ratings section of this manual for circuit output ratings Red Trouble Signal Circuit Note 1 C0319 01 box be sure to leave enough wire in the box to connect to the terminal blocks Approxim...

Страница 8: ...r more details Insure that both the detector and reflector are mounted within their operational parameters for off axis angles See Mounting Instructions for more details Disable the zone or system to prevent unwanted alarms before applying power Insure power to the detector is ON You are now ready to begin the alignment procedure Step 1 Coarse Alignment Refer to Figures 11 and 12 for this step 1 I...

Страница 9: ...e alignment switch to complete the fine adjustment step The digital display readout will turn OFF and the yellow LED will remain ON NOTE It may not be possible to achieve a value near 90 on the display during the last adjustment iteration The final value of the display will not likely be near 90 This is normal It is due to the detector reduc ing its electronic gain each time a value of 90 is achie...

Страница 10: ...llow LED see Appendix I If the detector does not enter the trouble condition there is a problem with the installation refer to the troubleshoot ing section in Appendix I for further assistance 2 Complete a sensitivity test of the detector Refer to the Sensitivity Testing section of this manual for the appro priate procedure 3 If the orange sticky paper was used to aid in the loca tion of the refle...

Страница 11: ...cally adjust its sensitivity using advanced software algorithms to select the optimum sensitivity for the environment The sensitivity will be continuously adjusted within the ranges specified in the chart above Sensitivity Total obscuration can be converted to percent per foot assuming uniform smoke density for the entire length of the beam The chart below converts total obscuration to percent per...

Страница 12: ... procedure is successful repeat the test pro cedure If the detector still fails the test it should be returned B Test Switch The detector can be tested using the local test switch on the transmitter receiver unit or remotely using the remote test station The remote test station RTS451 or RTS451KEY can be used with the BEAM1224 BEAM1224S beam smoke detec tor Follow instructions included with the te...

Страница 13: ...tector notify the proper authorities that the smoke detector system is undergoing maintenance and therefore the sys tem will be temporarily out of service Disable the zone or system undergoing maintenance to prevent unwanted alarms 1 Carefully clean the outer housing lens face A damp soft cloth with a mild soap may be used Avoid products with solvents or ammonia 2 Carefully clean the reflector A d...

Страница 14: ... in the pathway Trouble Beam Blockage Initial Response Off 4 Quick Blinks Off Off Beam Blockage Open OFF Open Remove blockage Faulty unit Trouble Beam Blockage Long Term Response On 4 Quick Blinks Off Off Beam Blockage Close OFF Open Remove blockage Faulty unit Initialization Power on Off Blink until complete Blink Off Apply Power from discharged state Open OFF Close Initialization alignment exit ...

Страница 15: ...Appendix II Detector Drilling Template 4 345 6 190 Scale 1 1 D400 73 00 15 I56 2294 03R ...

Страница 16: ...D400 73 00 16 I56 2294 03R ...

Страница 17: ...Appendix III Reflector Drilling Template Scale 1 1 5 512 140mm 8 465 215mm D400 73 00 17 I56 2294 03R ...

Страница 18: ...age is caused by the Company s neg ligence or fault Some states do not allow the exclusion or limitation of incidental or consequential damages so the above limitation or exclusion may not apply to you This Warranty gives you specific legal rights and you may also have other rights which vary from state to state Three Year Limited Warranty FCC Statement This device complies with part 15 of the FCC...

Отзывы: