B524RB(A) and B224RB(A) Plug-in

Relay Detector Bases

For use with the following models:
B524RB:     For use with any 500 Series detector
B224RB:     For use with any 200 Series detector

INSTALLATION AND MAINTENANCE INSTRUCTIONS

A Division of Pittway

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

Before Installing

Please thoroughly read the system wiring and installation
manuals, and manual I56-407, 

Guide for Proper Use of Sys-

tem Smoke Detectors,

 which provides detailed information

on detector spacing, placement, zoning, and special appli-
cations. Copies of these manuals are available at no charge
from System Sensor. (For installation in Canada, refer to
CAN/ULC-S524, Standard for the Installation for Fire Alarm
Systems and CEC Part 1, Sec. 32.)

NOTICE:

 This manual should be left with the owner/user

of this equipment.

IMPORTANT:

 The detector used with these bases must be

tested and maintained regularly following NFPA 72 require-
ments. The detectors should be cleaned at least once a year.

Specifications

Base Diameter:

6.2 inches (157 mm)

Base Height

B224RB:

1.2 inches (31 mm)

B524RB:

1.4 inches (36 mm)

Mounting:

4-inch square box with or without plaster ring, Min Depth - 1.5 inches (13 mm)
4-inch octagon box, Min. depth - 1.5 inches (13 mm)
3

1

/

2

-inch octagon box, Min. depth - 1.5 inches (13 mm)

Operating Temperature Range:

0

°

 to 49

°

C (32

°

 to 120

°

F)

Operating Humidity Range:

10% to 93% Relative Humidity (Non-condensing)

Electrical Ratings

Operating Voltage:

15 to 28 VDC

Time Averaged Standby Ratings:

<500 

µ

A @ 24 VDC

Relay Characteristics

Coil:

2 coil latching

Contact Type:

1 Form C

Contact Relay
Resistive:

2 A @ 30 VDC

Inductive:

0.3 A @ 110 VDC (with .35 PF or greater)
0.3 A @ 120 VAC (with .35 PF or greater)
1.0 A @ 30 VDC (with .6 PF or greater)

Set Time:

4 seconds minimum, 20 seconds maximum

Reset Time:

1 second minimum, 8 seconds maximum

General Information

Form C latching relay contacts are included for the control
of an auxiliary function. The relay operates 12 seconds
(nominally) after activation of the sensor head remote an-
nunciator output.

Mounting

The detector base mounts directly to 3

1

/

2

- and 4-inch oc-

tagon and 4-inch square boxes, with or without a plaster
ring.

To mount, remove the decorative ring by rotating it in ei-
ther direction to unhook the snaps. Then, separate the ring
from the base. Install the base on the box, using the screws
supplied with the junction box and the appropriate slots in
the base. Replace the decorative ring on the base and ro-
tate it in either direction until the ring snaps in place (see
Figure 1).

Содержание B224RB

Страница 1: ... or without plaster ring Min Depth 1 5 inches 13 mm 4 inch octagon box Min depth 1 5 inches 13 mm 31 2 inch octagon box Min depth 1 5 inches 13 mm Operating Temperature Range 0 to 49 C 32 to 120 F Operating Humidity Range 10 to 93 Relative Humidity Non condensing Electrical Ratings Operating Voltage 15 to 28 VDC Time Averaged Standby Ratings 500 µA 24 VDC Relay Characteristics Coil 2 coil latching...

Страница 2: ...n state when the base is shipped from the factory the contacts may have closed during shipment Connecting an auxiliary control circuit to closed relay con tacts can cause an unexpected and possibly dangerous ac tivation of that circuit Therefore do NOT connect an auxiliary control circuit to the relay contacts terminals 1 2 and 3 before ensuring that the relay contacts are in their open state Ensu...

Страница 3: ...the tamper resist feature if the removal tool is to be used This detector base includes a tamper resist feature that pre vents its removal from the base without the use of a tool To activate this feature break the tab from the detector base as shown in Figure 3A see page 4 Then install the detector To remove the detector from the base once the tamper re sist feature has been activated insert a sma...

Страница 4: ...detecting a smoldering fire with either an ionization type detector or a photoelectric type detector Either one of them may alarm only after flaming has initiated which will generate the heat needed to drive the smoke to the ceiling Smoke from fires in chimneys in walls on roofs or on the other side of a closed door s may not reach the smoke detector and alarm it A detector cannot detect a fire de...

Отзывы: