Operating Instructions
35
Caution
If you select a linearization curve the measurement signal will no longer necessarily be proportional to the fill
level. The must be taken into account by the user, particularly when setting the switch point at the limit signal
transducer.
Additional adjustments / Reset
This function resets various parameter settings made by the user.
The following reset functions are available:
Factory settings
Restore the parameter settings on the date of delivery from the factory including the
settings specific to the order. Any created false signal suppression, freely programmed linearization curve or
measurement value memory will be deleted.
Basic settings
Reset the parameter settings including special and laboratory parameters to the default
values for the specific device. Any created false signal suppression, freely programmed linearization curve or
measurement value memory will be deleted.
Setup
Reset the parameter settings made in the Commissioning menu point to the default values for the
specific device. Any created false signal suppression, freely programmed linearization curve, measurement
value memory or even memory will be retained. The linearization will be set to linear.
False signal suppression
Delete any previously created false signal suppression. The false signal
suppression created at the factory will be retained.
Peak val. measurement
Reset the measured min. and max. distances to the current measurement value.
The following table shows the default values for the device. Depending on the device version, not all menu
points may be available or may have different settings.
r
!