Operating Instructions
29
Setup / Vessel height, measuring range
This selection will adjust the sensor's operating range to the vessel height and significantly increase
measurement accuracy in various outline conditions.
Regardless of this the minimum adjustment described below must be completed.
Enter the required parameters using the appropriate keys, save them by pressing [OK] and then go to the
next menu point by pressing [ESC] and [->].
Setup / Vessel form
In addition to the medium and the application, the vessel form can also affect the measurement. This menu
point provides a range of options for the vessel floor and roof for certain applications to adjust the sensor to
these different measurement conditions.
Enter the required parameters using the appropriate keys, save them by pressing [OK] and then go to the
next menu point by pressing [ESC] and [->].
Setup / Adjustment
Since the radar sensor is a distance measuring instrument, it measures the distance from the sensor to the
surface of the solids. To display the actual fill level the measured distance must be assigned to the percentage
height.
To complete this adjustment the distance must be entered for the minimum and maximum fill level, see
example below: