11.5 annual inspection
Annual inspection by an accredited inspectorate is re-
quired if refrigerant volume in a one-piece unit exceeds 3
kg per circuit.
This is thus not required the for size 14 and 18 units, but
on the other hand it is for the size 4, 34, 48 and 60 units.
obligation to file reports
Obligation to report to a local supervisory authority is only
required if the total volume of refrigerant in the company
exceeds 10 kg.
11.6 service
Only service personnel trained by Swegon shall be permit-
ted to do any work on the cooling unit.
If any repair work is needed, get in touch with your near-
est Swegon service representative, see the backside of
these user instructions.
12 CoolinG Coil anD CoolinG
aGent Cooler
Cooling coil and cooling agent cooler are sized to match
the size 08-60 Gold and the size 004-014 Basic units.
The coils consist of copper tubes and profiled aluminium
fins. The casing is made of hot galvanized sheet steel. The
headers are made of steel.
12.1 instructions for the BasiC unit
12.1.1 BCKo, 006-014 Cooling agent cooler
The BCKO cooling agent cooler is finned tube coil. Water
is used as the heat carrier, usually mixed with glycol.
The BCKO is made of copper tubes with aluminium fins.
The headers and connections are made of steel.
Specification
The design, size, etc. of the cooler are specified in the
delivery documents.
BCKO
BASIC
COOLER
R dia.
VOLUME/L
004
14
006
18
006
4
5
0.1
009
4
3
3
009
34
3
3
014
34
3
30
014
48
3
37
installation
The coil must be vented before the system is commis-
sioned, thus a venting valve should be fitted to the venting
nipple.
The BCKO Cooling agent cooler should be connected for
cross-flow mode as indicated by the arrows on the con-
nection branches. If a shunt unit is fitted, make sure that it
is installed so as not to block inspection of the other func-
tional sections.
Care
Check whether cleaning is required at least twice a year.
The unit should be cleaned in the following way only:
Blow with compressed air towards the ordinary direction
of airflow and then vacuum clean the side facing the ordi-
nary direction of airflow using a soft nozzle.
Wet cleaning can be carried out by flushing with water.
If a solvent is used, it must be of a quality that doesn’t
corrode aluminium or copper. Cover adjacent functional
sections to protect them before you begin cleaning. After
you’ve finished cleaning, blow the surfaces with com-
pressed air to remove all traces of detergent. Swegon
detergent, sold by Swegon Service is recommended.
While cleaning, check for trapped air in circuits, the glycol
content and density, if necessary.
BCKo Dimensions
L
K
P
Fig. 18
BCKO 004-014
B
H
L
004
1039
546
453
006
159
656
453
009
1459
756
453
014
1759
906
453
gB.Cooler.inSt.060501