11.5  annual inspection

Annual inspection by an accredited inspectorate is re-
quired if refrigerant volume in a one-piece unit exceeds 3 
kg per circuit. 
This is thus not required the for size 14 and 18 units, but 
on the other hand it is for the size 4, 34, 48 and 60 units.

obligation to file reports

Obligation to report to a local supervisory authority is only 
required if the total volume of refrigerant in the company 
exceeds 10 kg.

11.6  service

Only service personnel trained by Swegon shall be permit-
ted to do any work on the cooling unit.
If any repair work is needed, get in touch with your near-
est Swegon service representative, see the backside of 
these user instructions.

12  CoolinG Coil anD CoolinG  

 

aGent Cooler

Cooling coil and cooling agent cooler are sized to match 
the size 08-60 Gold and the size 004-014 Basic units. 
The coils consist of copper tubes and profiled aluminium 
fins. The casing is made of hot galvanized sheet steel. The 
headers are made of steel.

12.1  instructions for the BasiC unit

12.1.1  BCKo, 006-014 Cooling agent cooler

The BCKO cooling agent cooler is finned tube coil. Water 
is used as the heat carrier, usually mixed with glycol.
The BCKO is made of copper tubes with aluminium fins. 
The headers and connections are made of steel.

Specification

The design, size, etc. of the cooler are specified in the 
delivery documents.

BCKO

BASIC

COOLER

R dia.

VOLUME/L

004

14

006

18

006

4

5

0.1

009

4

3

3

009

34

3

3

014

34

3

30

014

48

3

37

installation

The coil must be vented before the system is commis-
sioned, thus a venting valve should be fitted to the venting 
nipple.
The BCKO Cooling agent cooler should be connected for 
cross-flow mode as indicated by the arrows on the con-
nection branches. If a shunt unit is fitted, make sure that it 
is installed so as not to block inspection of the other func-
tional sections.

Care

Check whether cleaning is required at least twice a year. 
The unit should be cleaned in the following way only:
Blow with compressed air towards the ordinary direction 
of airflow and then vacuum clean the side facing the ordi-
nary direction of airflow using a soft nozzle.
Wet cleaning can be carried out by flushing with water. 
If a solvent is used, it must be of a quality that doesn’t 
corrode aluminium or copper. Cover adjacent functional 
sections to protect them before you begin cleaning. After 
you’ve finished cleaning, blow the surfaces with com-
pressed air to remove all traces of detergent. Swegon 
detergent, sold by Swegon Service is recommended.
While cleaning, check for trapped air in circuits, the glycol 
content and density, if necessary.

BCKo Dimensions

L

K

P

Fig. 18

BCKO 004-014

B

H

L

004

1039

546

453

006

159

656

453

009

1459

756

453

014

1759

906

453

gB.Cooler.inSt.060501

Содержание Cooler 14

Страница 1: ...Cooling Unit Cooler Installation and Maintenance Instructions Sizes 14 60 Sizes 14 18 Sizes 24 60 GB COOLER INST 060501...

Страница 2: ...ixture 13 6 8 1 Filling 14 6 8 2 Venting the system 14 7 Commissioning 15 7 1 Preparations 15 7 1 1 Before starting for first time 15 7 1 2 Starting up 15 7 1 3 To correct the phase sequence 15 8 Prog...

Страница 3: ...documented and certificated Quality Management and Environmental Management Systems that meet the provisions of ISO 9001 and ISO 14001 respectively 1 Overview 1 1 General Cooling Unit Cooler The Cool...

Страница 4: ...form A reduction in pressure occurs in expansion valve EV From the expansion valve the refrigerant advances to evapora tor VVX where the refrigerant vaporises and absorbs heat from the adjacent medium...

Страница 5: ...medium i e the brine water ethylene glycol Gas leaves the evaporator and flows back to the cooling compressor Water pump G1 pumps the brine water ethylene glycol in one circuit from condensers VVX3 a...

Страница 6: ...nit is in principle a hazardous area due to the presence of refrigerant For particulars of how to deal with leakage see Section 10 3 The circuits contain type R 407C and R134A refrigerant Caution Sinc...

Страница 7: ...n the underside of the pallet or under the unit Then lift in the pallet or the unit if the pallet is not to be attached See fig 6 Fig 6 3 2 Mounting The Cooler cooling unit should be located at a suit...

Страница 8: ...it and their ca pacities that correspond to each size of air handling unit see Section 14 General Technical Data Cooler sizes 14 18 Power supply Start and control signal Brine Extract air Outdoor air...

Страница 9: ...it is connected without any end panel to the exhaust air side downstream of the fan in the Basic A cover plate must be fitted to the air handling unit since the refrigerating machine is somewhat small...

Страница 10: ...2 35 A T for the size 24 Coolers and 35 A T for the size 34 Coolers When sizing the cable take into account the ambient temperature and how the cable will be arranged See Fig 10 4 1 4 Cooler sizes 48...

Страница 11: ...the connector in any of the connections for ABC Bus communication on the control circuit card ABC Bus ABC Bus Fig 11 Fig 11b Hand held Micro Terminal Connect the quick connector of the hand held micro...

Страница 12: ...p alarm B Connect alarms from the Cooler to the External Alarm 1 or the External Alarm 2 terminals The alarm in the Cooler is factory preset with priority A which means that only group alarm A normall...

Страница 13: ...the GOLD Fig 14 6 Cooling Connections Connection of the cooling coil and the cooling agent cooler to cooling unit 6 1 Location The cooling coil shall be located in the supply air ductwork Sizes 14 an...

Страница 14: ...safety valve opens See Fig 15 1 Shut off the tap Important The system must be vented see Section 6 8 2 It is essential to evacuate all the air out of the system It is advisable to run the pumps with...

Страница 15: ...r about 5 seconds Start the pump pumps to run for a few minutes to check that the liquid control systems are free from air Start the pumps by pressing the PROG button to advance to the control positio...

Страница 16: ...unction of the buttons is explained by the caption or symbol shown in the display right above each button For explanation see Section 8 2 8 2 Menu button captions and symbols The most common button fu...

Страница 17: ...ER TUES 12 49 100 AUTO OPER Main menu RET OPER LEVEL 100 BRINE PUMP 1 COOLING AGENT PUMP 1 OPER LEVEL indicates the present cooling load as in the main menu BRINE PUMP shows the pump status 1 On and 0...

Страница 18: ...mage to the settings menu The sizes 14 18 24 34 48 and 60 can be set RET PROG ACTTUAL TIME WED TIME 07 30 DATE 17 03 2003 Shows preset ACTUAL TIME The second line shows the current day of the week and...

Страница 19: ...icates the current percentage the same as in the main menu BRINE PUMP and COOLING AGENT PUMP shows the sta tus for each pump in the manual mode Pressing PROG alters the image to the settings menu Cool...

Страница 20: ...From here you can advance to the desired alarm number By pressing SET the image changes over to the level for setting of the current priority and condition of the alarm PRIORITY can be selected for 1...

Страница 21: ...rm 51 HIGH PRESSURE SWITCH COMPRESSOR 2 TRIPPED The alarm is initiated if input 29 30 is interrupted and if BT4 45 C The alarm has factory settings Priority 1 Indication 1 Stop 1 Time delay 1 s The al...

Страница 22: ...ue to regulations in cooling standards Alarm 59 BRINE TEMP EXCEEDS ALARM LIMIT The alarm is initiated if BT3 the brine temperature 15 C for more than one hour while one or more compressors are operati...

Страница 23: ...ontains gas under high pressure The refrigerant circuit may only be modified or repaired by qualified personnel from an accredited refrigeration company Important If you detect any refrigerant leakage...

Страница 24: ...d connections are made of steel Specification The design size etc of the cooler are specified in the delivery documents BCKO BASIC COOLER R dia VOLUME L 004 14 006 18 006 24 25 20 1 009 24 32 23 009 3...

Страница 25: ...r expansion forces of the piping system will not be applied to the connections Use appropriate sealant for sealing the thread of the coil connections Installing the water trap The water trap must be f...

Страница 26: ...size Type A B C E G H R Wgt in kg excl liquid Filling volume L 14 TBKA 2 100 040 3 400 1295 1000 148 113 625 25 89 9 18 TBKA 2 100 040 4 400 1295 1000 148 113 625 32 95 12 24 TBKA 2 100 040 5 400 1295...

Страница 27: ...l liquid Filling volume L 48 TBKA 2 160 080 3 0 1 2311 1141 510 215 39 60 TBKA 2 160 080 4 0 1 2311 1141 510 230 46 Cooling agent cooler For Cooler size Type B H L R Wgt in kg excl liquid Filling volu...

Страница 28: ...led E The cooling coil shall be insulated in accordance with local regulations for ventilation ducts and connected pipe work in accordance with local trade standards F On coils with round duct connect...

Страница 29: ...BCEA BASIC 006 Supplied without end Supplied without end Connection frame with connection wall connection wall slip clamp joint 1100x500 mm TBXZ 111005022 1 This end connection wall does not have a c...

Страница 30: ...R407c R407c Number of circuits 2 2 2 2 2 2 Volume R134a Kg 2 3 2 9 2 3 4 5 5 4 8 2 Volume R407c Kg 2 1 3 0 4 0 4 9 8 0 8 0 Electrical connections Power supply Volt 400 400 400 400 400 400 Frequency H...

Страница 31: ...nit by means of slip clamps The larger units stand alone and alongside the air handling unit Cooler 14 B L H R2 Fig 25 Cooler 18 B L H R2 Fig 26 Cooler 24 34 48 60 H B L R1 R2 Fig 27 16 1 1 Dimensions...

Страница 32: ...is designed for installation in electical environments where the Low Voltage Directive specifies interference levels in accordance with the standards for electromagnetic radiation in dwellings offices...

Страница 33: ...fitted with control system TA fitted with control system VVVA VVRV covered by this declaration comforms to the following Standards EN 292 1 2 EN 294 EN 60204 1 EN 61000 6 2 and EN 61000 6 3 according...

Страница 34: ...Swegon AB Box 300 SE 535 23 Kv num 46 512 32200 www swegon com www swegon com GB COOLER INST 060501...

Отзывы: