9.4
test menus
Whenever any of the menus under TEST is selected, the
control system will leave the normal in-operation status
and go over to manual test run status.
warning!
The various ouputs are now controlled by the operator
in fully manual mode. The safety functions are switched
off and the operator assumes all responsibility.
The only provision is that the pumps must be in operation
before any compressor can be started.
INFO : INST : : TEST : LARM
*COOLER* TUES 1:49
SHUT OFF
▼
Main menu
The TEST button must be held in for 5 s. before the
image will change.
: : :RET : PROG
OPER LEVEL
00%
BRINE PUMP
1
COOLING AGENT PUMP
1
▼
OPER LEVEL indicates the current percentage, the same as
in the main menu.
BRINE PUMP and COOLING AGENT PUMP shows the sta-
tus for each pump in the manual mode.
Pressing PROG alters the image to the settings menu.
(Cooler 14 and 18: Line 3 is empty.
: : :RET : PROG
COMPRESSOR.1
1
COMPRESSOR.
1
▼
COMPRESSOR 1 and COMPRESSOR show the status of
each compressor in the manual mode.
Pressing PROG alters the image to the settings menu.
important!
The pumps must be in operation before the compressors
can be started.
: : :RET : PROG
GROUP ALARM A 1 B 0
OPER INDICATION
1
OPER INDICATION 10V
▼
GROUP ALARM A, B and OPER INDICATION show the
status of each relay output in the manual mode.
Pressing PROG alters the image to the settings menu.
: : : RET :
BRINE TEMP -,6˚C
COOLING AGENT TEMP 34,6˚C
BRINE TEMP and COOLING AGENT TEMP show present
temperatures. (For the size 14 and 18 Coolers: BRINE
TEMP and CONDENSER TEMP is shown).
gB.Cooler.inSt.060501