9
Menus
9.1
Main Menu
INFO : INST : : TEST : LARM
*COOLER* TUES 1:49
. . : 100%
AUTO OPER
▼
Fig. 16
The COOLER image indicates type of unit, the present day
of the week and the time.
The second and third lines indicate the in-operation status
of the cooling unit.
SWITCHED OFF is shown when the control circuit card has
not received an operation command. STOP is shown when
operation command has been given, but the cooling load
signal is 0. A percentage figure that may vary between
0–100% together with the text AUTO OPER indicates the
cooling capacity at which the unit is operating.
The text DELAYED START and the percentage figure are
alternately displayed when any of the cooling compressors
are unable to start, because the restart delay time has not
run out.
9.2
information Menus
INFO : INST : : TEST : LARM
▼
*COOLER* TUES 1:49
. . : 100%
AUTO OPER
Main menu.
: : : RET :
▼
OPER LEVEL
100%
BRINE PUMP
1
COOLING AGENT PUMP
1
OPER LEVEL indicates the present cooling load, as in the
main menu.
BRINE PUMP shows the pump status.
1 = On and 0 = Off.
COOLING AGENT PUMP shows the status of the pump.
1 = On and 0 = Off. (Size 14 and 18 Coolers: this line is
empty).
: : : RET :
▼
COMPRESSOR.1
1
COMPRESSOR.
1
COMPRESSOR.1 shows the status of compressor 1.
1 = On and 0 = Off.
COMPRESSOR. shows status of the compressor .
1 = On and 0 = Off.
: : : RET :
▼
BRINE TEMP
-7,9˚C
COOLING AGENT TEMP
34,6˚C
PROGRAM VERSION
: 1.14
BRINE TEMP shows the present temperature of the brine
medium.
COOLING AGENT TEMP shows the present temperature of
the heat carrying medium. (Size 14 and 18 Coolers: CON-
DENSER TEMP is displayed).
PROGRAM VERSION shows the current program version of
the control equipment.
: : : RET :
*OPER TIME DAY AND NIGHT*
COMPRESSOR 1
999
COMPRESSOR
1998
OPER TIME DAY AND NIGHT shows current operation time
for each compressor. The time is measured in minutes
but specified in day and night, due to limited space in the
display.
gB.Cooler.inSt.060501