To change the id number of the room unit.
Settings
<Exit
Select>
Room unit no.
RF pair-up
......................
Room unit
<Exit
[First]
Figure 10. Image for selecting to change the id number of the room unit and the room unit
image.
The unit must be assigned an adress to enable connecting it up to ModBUS,
when the room unit is connected via cable to the controller.
1. Go to the Service menu.
2. Highlight Settings
3. Press OK or on the
►
Right key.
4. Highlight the id number of the Room unit.
5. Press OK.
6. Make one of the following selections:
• Select First whether the room unit is the first one in the room.
• Select Second if the room unit is the second one in the room.
7. Press OK in order to confirm the selection and return to the Service
menu.
45
20210201 Swegon reserves the right to make design changes.
CONDUCTOR
W4
Содержание 20210201
Страница 1: ...CONDUCTOR W4 Technical Manual sw 1 48 20210201...
Страница 2: ......
Страница 4: ...CONDUCTOR W4 4 Swegon reserves the right to make design changes 20210201...
Страница 6: ...CONDUCTOR W4 6 Swegon reserves the right to make design changes 20210201...
Страница 24: ...CONDUCTOR W4 24 Swegon reserves the right to make design changes 20210201...
Страница 36: ...CONDUCTOR W4 36 Swegon reserves the right to make design changes 20210201...
Страница 54: ...CONDUCTOR W4 54 Swegon reserves the right to make design changes 20210201...